What happened Haiwu Technology published an industry overview on 22 September 2026 examining how China's data center cooling market is splitting across three liquid cooling architectures — cold plate, immersion and spray — as AI training and inference demand pushes rack power densities beyond what traditional air cooling can handle. The article frames liquid cooling as a necessity rather than an option for high-density intelligent computing centers, driven by China's "dual carbon" goals and green computing policies. The piece describes each architecture's working principle: spray cooling atomizes coolant directly onto heat-generating components; cold plate cooling transfers heat indirectly through copper or aluminum cold plates bonded to chips; immersion cooling submerges IT hardware entirely in dielectric coolant, split into single-phase and phase-change (two-phase) variants. It walks through system topology for each — cooling towers, CDU (coolant distribution units), primary and secondary loops, liquid-cooled racks, spray modules and immersion tanks — and weighs commercialization maturity, PUE performance, power density ceilings, retrofit difficulty and operating cost. The conclusion: cold plate remains the near-term mainstream; immersion becomes the core solution for ultra-high-density clusters as coolant costs fall and engineering matures, with phase-change immersion positioned as the industry's ultimate direction; spray cooling stays a niche, custom-project technology for now. ### Key figures - All three liquid cooling routes can hold data center PUE below 1.25, meeting green data center construction standards. - Cold plate accounts for 65% of China's liquid cooling market, per data cited from the Zhongshang Industry Research Institute. - Immersion accounts for 34% of that market; spray cooling 1%. - Cold plate cooling can push PUE below 1.25, versus roughly 1.5 typical for air cooling. - Cold plate cooling is described as reaching its limits in racks above 200 kW. - Single-phase immersion can achieve PUE below 1.2; phase-change immersion below 1.1. - Traditional air cooling supports only 10–15 kW per rack; immersion cooling readily exceeds 100 kW per rack and can reach above 200 kW. - Cold plate technology has undergone more than a decade of iteration in China. ### Why it matters to ebm-papst This is a structural demand signal for air-moving equipment in data centers, and it cuts both ways. The article's core claim — that air cooling cannot keep pace with chip power growth — is the same pressure that has driven ebm-papst's data center fan and cooling business, and it is the reason the company has invested in high-static-pressure, high-efficiency fan platforms and in liquid-cooling-adjacent components. Assessment (inference): The 65/34/1 split matters less than the direction of travel. Cold plate is retrofit-friendly and preserves most existing server and rack architecture, which means fan content per rack does not disappear — it shifts from front-panel server fans toward rack-level, CDU and sidecar heat-exchanger air movement. That is a nearer-term opportunity than immersion. Assessment (inference): Immersion's trajectory is the real competitive threat. If single-phase and phase-change immersion scale as the article predicts, server fans are eliminated entirely and rack-level air movement shrinks sharply. The 100–200 kW per-rack figures imply that a single immersion deployment can displace the air-moving content of roughly ten conventional racks. ebm-papst should treat immersion timelines — not cold plate growth — as the key variable to monitor. Assessment (inference): Spray cooling at 1% share with unresolved nozzle clogging, drift and uniformity problems is not a near-term market. It is worth tracking only as a technology watch item. Assessment (inference): The most actionable near-term play is the cold plate ecosystem: CDU pumps and heat exchangers, coolant distribution, and the air side of liquid-to-air and liquid-to-liquid heat rejection all still require fans and blowers. ebm-papst's opportunity is to be designed into CDU and heat-rejection subsystems before immersion erodes the rack-level fan market. Assessment (inference): The article cites no vendor names, procurement volumes or investment figures, so no customer-specific conclusions can be drawn from it. It is a market-structure signal, not a lead.
Full text
Original
English translation
AI computing power is surging — how to choose among the three major liquid cooling routes? Cold plate liquid cooling holds the present, immersion and spray liquid cooling are poised for takeoff.
Demand for AI large-model training and inference continues to explode, high-density computing clusters are being deployed rapidly, and traditional air cooling can no longer keep up with the soaring power consumption of chips. Driven by the "dual carbon" goals and green computing policies, liquid cooling technology has become the core solution for intelligent computing center construction.
At present, the industry's mainstream liquid cooling solutions include three types: cold plate, immersion and spray. All three routes can control data center PUE below 1.25, meeting green data center construction standards. The most core difference among the three lies in the way the coolant contacts the heat-generating components of the servers. Spray cooling sprays directly onto the chip for heat exchange; cold plate cooling relies on a metal cold plate for indirect heat conduction; immersion cooling directly soaks the equipment in coolant, and can be further divided into two major branches: single-phase immersion and phase-change immersion.
Cold plate liquid cooling: retrofit-friendly, the market's first choice at present
Cold plate liquid cooling is the most mature solution for commercial deployment in China. The complete system consists of cooling towers, CDU coolant distribution units, primary and secondary side circulation piping, cooling medium and liquid-cooled racks. Inside the rack are core components such as liquid cooling plates, built-in piping, fluid connectors and manifolds.
Its working logic is simple and clear: heat generated by server chips is conducted to copper or aluminum liquid cooling plates that sit tightly against the components; driven by the CDU circulation pump, working fluids such as water, glycol solution or fluorinated liquid flow inside the cold plate and carry away the heat. The heated working fluid enters the CDU heat exchanger, transfers the heat to the outdoor cooling tower, and after the medium cools down it flows back again, forming an uninterrupted cycle.
After more than a decade of technological iteration, cold plate liquid cooling has a solid industrialization foundation. According to data from the Zhongshang Industry Research Institute, cold plate accounts for as much as 65% of China's liquid cooling market, far exceeding immersion's 34% and spray's 1% market share.
Compared with traditional air cooling, cold plate has prominent advantages. PUE can be reduced to below 1.25, better than the roughly 1.5 level common for air cooling. The biggest highlight is strong hardware compatibility: there is no need to substantially modify existing server motherboard structures, retrofit difficulty for existing computer rooms is low, and large-scale replication and deployment are easy. At the same time, the coolant does not directly contact the circuit boards, so the risk of equipment damage from leakage is lower and operational stability is stronger.
Its shortcomings are equally objective: heat must pass through the cold plate medium, the heat exchange chain is longer, and compared with immersion solutions the heat dissipation capability has a ceiling — it becomes somewhat strained in ultra-high-density rack scenarios above 200 kW.
Immersion liquid cooling: maximum heat exchange efficiency, the rising star for high-computing-power scenarios
Immersion liquid cooling means placing IT hardware entirely into insulating coolant, with heat sources and liquid exchanging heat in direct contact. The complete system is divided into outdoor cooling units, primary pipe networks, indoor CDUs, immersion chambers, IT equipment and secondary circulation piping, and comes in two modes: single-phase immersion and phase-change immersion.
Single-phase immersion: low-temperature coolant flows in from the bottom of the chamber, wraps around server components and carries away heat; the heated medium returns from the top of the chamber to the CDU, and then discharges the heat externally through a heat exchanger. The coolant remains liquid throughout, using high-boiling-point, insulating, low-corrosion hydrocarbon or fluorocarbon media.
The phase-change immersion heat exchange process is broadly the same, but the coolant has a lower boiling point. After the medium absorbs heat from the chip it boils and vaporizes; the vapor rises to the top of the chamber, condenses back into liquid upon meeting the condenser, and falls back to the bottom of the chamber by gravity to continue circulating. Relying on latent heat of phase change, its heat exchange capability is stronger.
The core advantage of immersion liquid cooling is extreme heat dissipation. Single-phase immersion can achieve PUE below 1.2, and phase-change immersion can even push it below 1.1. Its advantage in power density is enormous: traditional air cooling can carry only 10–15 kW per rack, while immersion liquid cooling easily exceeds 100 kW per rack and can reach above 200 kW, perfectly matching high-power computing clusters such as AI intelligent computing.
At the same time, immersion computer rooms can eliminate server cooling fans, achieving low-noise operation; they dispense with supporting facilities such as hot and cold aisle containment and raised floors, making the computer room layout more compact and suitable for projects with limited space.
But large-scale adoption still faces many difficulties. Immersion chambers use horizontal tank bodies, completely different from traditional vertical rack architecture, and the initial investment cost for new construction or retrofit is relatively high. Dedicated coolants such as fluorinated liquids are expensive, some media carry safety risks, and later-stage operations and maintenance processes are also more complex.
The industry generally predicts that in the short term cold plate will remain the market mainstay; in the long term, as coolant costs fall and engineering solutions are continuously optimized, immersion liquid cooling will become the core solution for ultra-high-density computing scenarios, and phase-change immersion is regarded as the ultimate direction of liquid cooling technology.
Spray liquid cooling: chip-level precise cooling, industrialization still on the way
Spray liquid cooling belongs to direct-contact cooling — figuratively speaking, it "sprays targeted cooling" onto chips. Relying on pump pressure or gravity, it precisely sprays coolant onto the surface of heat-generating components on the circuit board, directly carrying away heat. The system includes cooling towers, CDUs, circulation piping and spray racks; inside the rack are liquid distribution piping, spray modules and a return liquid collection system.
Cooling process: after the coolant is cooled in the CDU it is delivered into the rack, and sprayed through spray modules aimed at heat sources such as chips; the liquid that has absorbed heat collects in the return liquid tank at the bottom and is pumped back to the CDU for re-cooling and circulation.
In terms of heat dissipation performance, spray cooling is similar to immersion, likewise supporting high-power racks, with low noise during computer room operation. But this technology is insufficiently mature, with many pain points in engineering implementation. The spraying process easily produces liquid drift and volatilization, polluting the computer room environment; nozzle clogging and difficulty in controlling spray uniformity restrict its promotion. At present there are few deployment cases, mostly used only in a small number of customized scenarios.
Conclusion
Facing the rapid expansion of AI computing power, liquid cooling has gone from a bonus item to a hard requirement for high-density data centers. The three major liquid cooling routes each have their strengths, and there is no absolute "best solution." Cold plate wins on stability and ease of deployment; immersion is strong in heat dissipation ceiling, aimed at future high-density computing power; spray focuses on precise chip cooling and is a niche solution in the short term.
When planning intelligent computing centers, enterprises should comprehensively evaluate rack power, project budget and computer room infrastructure conditions, choose the appropriate liquid cooling technology, and find the optimal balance among computing performance, energy consumption level and construction cost.