### What happened In an interview published by Bisnow and produced in collaboration between Stulz USA and Studio B, Dave Meadows, Director of Technology at Stulz, laid out how AI workloads are forcing a redesign of data center cooling. Stulz supplies cooling solutions and services for mission-critical facilities. Meadows said the installed US base of thousands of low-watt-density, air-cooled data centers was never designed for high-watt-density, high-heat-flux chip equipment, making retrofits difficult. As an interim measure, he pointed to liquid-to-air coolant distribution units (CDUs), which use liquid to cool AI-specific servers such as NVIDIA's GB200 or GB300 and reject the heat into the traditional white space so legacy cooling equipment can remove it. He described this as a stopgap rather than how a new data center would be designed. For a longer-term path, Meadows advocated a dual approach: assess existing infrastructure, take some of it offline and rework it into a more direct liquid-to-chip-cooled facility, and reuse existing chillers under new conditions such as higher return water temperatures and longer piping runs to the CDUs. He stressed that cooling structures must now be engineered around the specific IT equipment being cooled, given its requirements for flow rate, supply temperature and coolant type, and that this demands more engineering involvement than the all-air-cooled era. Meadows said Stulz is expanding both its application engineering and design engineering teams, developing new products for AI cooling infrastructure and helping operators convert air-cooled sites, including custom alterations to equipment. He added that Stulz built its first CDU in the US more than 20 years ago for hybrid liquid-air-cooled racks, and that the company shares its experience with the consulting engineering community, many of whom are encountering liquid-cooled AI data center requirements for the first time. Looking ahead, Meadows said NVIDIA has made clear the industry will need an 800-volt distribution architecture for very high-watt-density racks, citing 600 kilowatts and beyond, and that water-based cooling carries fire and explosion risk from electrolysis of coolant if a leak occurs near 800-volt DC power. He said the industry is therefore exploring direct refrigerant-to-chip cooling using a safe, low-GWP refrigerant, a technology he called very early but promising. He also argued the water debate should weigh source water used in power generation against site water consumed at the data center, and referenced The Green Grid's water usage impact metric. ### Key figures - Deloitte research estimate: US AI data center power demand could grow more than thirtyfold by 2035, reaching 123 gigawatts. - Rack power level cited by Meadows for the coming 800-volt era: 600 kilowatts and beyond. - Stulz built its first CDU in the US more than 20 years ago. - AI servers named as examples: NVIDIA GB200 and GB300. - No specific figures disclosed for Stulz revenue, CDU capacity, unit volumes, pricing or market share. ### Why it matters to ebm-papst Stulz is a direct competitor in mission-critical cooling, and its public positioning around liquid-to-air CDUs, liquid-to-chip retrofits and refrigerant-to-chip development signals where cooling architecture is heading as AI rack densities rise. For ebm-papst, the near-term retrofit wave keeps air movement relevant: CDUs, chillers, in-row and perimeter units still need fans and blowers to reject heat into white space, so legacy-site conversions represent a component opportunity even as liquid cooling spreads. Assessment (inference): The stated trajectory toward 600kW-plus racks and 800-volt DC distribution is a medium-term threat to air-cooling content per rack, because direct liquid-to-chip and refrigerant-to-chip designs reduce the airflow needed at the server level. Assessment (inference): At the same time, higher heat rejection at the facility level, plus the need for redundancy and precise airflow control in CDUs and heat rejection loops, should sustain demand for high-efficiency, high-static-pressure fans and for motorized impellers suited to compact, high-density cooling equipment. Assessment (inference): Stulz's investment in application and design engineering and its outreach to consulting engineers is a competitive signal that specification influence is being contested at the design phase, where ebm-papst should ensure its fan and blower platforms are validated and referenced for liquid-cooling-adjacent equipment. Assessment (inference): The refrigerant-to-chip discussion is early, but it is a market signal to monitor for future air-moving requirements in sealed, high-voltage-adjacent cooling architectures.

## Full text (original)

Artificial intelligence is transforming nearly every industry, but perhaps no sector is impacted as much as the data center market.
Deloitte research estimates that by 2035, power demand from AI data centers in the U.S. could grow more than thirtyfold, reaching 123 gigawatts. For data center developers, this not only means they need to build more facilities faster but also to prepare for things to get hot.
According to Stulz Director of Technology Dave Meadows, AI-centric data centers call for a new type of cooling technology that a significant number of current facilities may not be prepared for.
“In the U.S. we have thousands of data centers that were designed specifically as low-watt-density, air-cooled centers,” Meadows said. “Introducing high-watt-density, high-heat-flux chip equipment into those environments is very difficult because they were never built for it.”
Stulz provides cooling solutions and services for mission-critical facilities. Meadows walked Bisnow through some of the issues data centers may run into as they prepare for the AI-driven future and spoke on the solutions that will keep legacy centers running in this new era. 
Bisnow: What are some of the top challenges legacy data centers face as they work to meet today’s AI demands?
Meadows: As I mentioned, retrofitting these facilities for modern requirements has been very challenging. Now, there are strategies in place. One of the most prevalent, and it's really just a stopgap measure to allow us to continue to use these facilities in the time of AI, is liquid-to-air coolant distribution units, or CDUs. With those, operators use liquid to actually cool the AI-specific servers, the Nvidia GB200s or 300s, for example, and they’re pulling that heat out and dissipating it into the traditional white space in a facility so the legacy cooling equipment can take that heat energy, remove it from the white space and get it outside.
It’s not the way we would design a brand-new data center, but it can get us to where we can utilize legacy facilities while meeting the challenge of the AI environment. 
Bisnow: What’s the best solution for legacy data centers that are hoping to move forward with modern cooling products but are facing these challenges? 
Meadows: I believe the best approach is a dual one, where you look at your infrastructure and see what can be taken offline and reworked as a more direct liquid-to-chip-cooled facility, as opposed to purely air-cooled. More than likely, you're going to have chillers in the facility that can be utilized. It’s just about determining how to utilize them under new conditions — the higher return water temperatures, maybe the greater piping runs that will have to be supported to get the chilled water to the CDUs. There are strategies that can be used. It’s got to be well thought out, though.
One of the real challenges today is that we have to build a cooling structure very specific to the information technology equipment we're trying to cool, because it has very special requirements for the flow rate, the supply temperature, coolant type, and that all has to be worked out in the design phase. It’s going to require more engineering involvement than back in the day when everything was air-cooled and we really didn't care what kind of server was there. It needs to be addressed through thoughtful engineering. 
Bisnow: How is Stulz working to help data centers make this complex transition?
Meadows: We're building up our engineering teams, both our application engineering team and our design engineering team, to not only develop new products that work with AI data center cooling infrastructure needs but also to help operators transform their traditionally air-cooled data center into an AI-specific one. This requires customization on the part of the cooling equipment, because you're trying to put a square peg in a round hole to a certain extent. We have to make custom alterations within the equipment so it achieves the goal that we're trying to reach, which is to move the very high heat energy and high heat flux from that white space.
We’re also assisting the engineering community, specifically the consulting engineering community, by sharing our experiences and what we're seeing in this space. A lot of design engineers are seeing liquid-cooled AI data center requirements for the first time. While we’ve been working on them for several years now, we actually built our first CDU in the U.S. over 20 years ago to cool hybrid liquid-air-cooled racks. We make it a point through our applications engineering team to share our knowledge and help facilities get to the next level of heat removal. 
Bisnow: How should operators prepare for the future of data center cooling? 
Meadows: When it comes to data centers, futureproofing is very difficult — our crystal ball just doesn’t seem to be working very well in this ever-changing field. One of the big challenges we will be facing soon is that Nvidia has made it very clear that we're going to need to go to an 800-volt distribution architecture to power these very high-watt-density racks. We are talking 600 kilowatts and beyond, and to do that, we need special cooling systems.
Water-based systems will not be able to handle this without a serious risk of fire and explosion due to electrolysis of the coolant in the case of a leak in the proximity of 800-volt DC power. This is why there is a push to develop products that can remove high heat flux, high rack density heat, without having the danger of having water in a high-voltage environment. As an industry, we are looking at what we call direct refrigerant-to-chip, where we're using a safe, low GWP refrigerant instead of a water-based solution to remove heat. It’s very early days for this technology, but it’s very promising. 
Bisnow: What’s one thing you wish more people understood about the data center industry? 
Meadows: I would have to say the water issue. We fixate way too much on the water that's used on-site at data centers, and we don't really look at the water that's used in the production of the power that is being consumed in these data centers. We need a more nuanced approach outside of “water is always bad.” Sometimes, we can use water for very efficient cooling methodologies, including direct evaporative cooling or indirect evaporative cooling, but people seem to be under the impression that any cooling method involving water is harmful.
In the meantime, however, large amounts of water are used at the coal-burning power plant, the natural gas power plant, or even the nuclear power plant that's providing that power to that data center. The water used in power generation is often called “source water,” which is different from “site water,” which is typically water consumed at the data center through evaporative cooling. If we can take some of the power requirement off the grid through judicious use of on-site water, we have the potential to use less total water for the data center. There are many variables to look at in the source water-versus-site-water argument. The Green Grid recently came out with the water usage impact metric, which measures a data center's consumed water relative to the local water stress level, and I think that would be a good place to start this important conversation surrounding how much water these facilities really use and where that water comes from.