Data Center Knowledge: Water Becomes Core Siting Constraint as Virginia Study Caps Groundwater at 360,000 Gallons/Day
Intelligence brief
What happened On September 23, 2026, Data Center Knowledge published a roundup examining how water has shifted from a background utility to a core constraint shaping data center siting, design, operations, and community relations. The article aggregates the outlet's prior reporting across metrics, cooling technology, water sourcing, siting, environmental impact, policy, and community response. Key reported developments include: water treatment specialist Dr. Marcello Serrano arguing that water resilience cannot be judged by Water Use Effectiveness (WUE) or "waterless" claims alone but must be proven under peak stress, using a dispute in California's Imperial Valley over a proposed AI data center as his example. A July 2026 Virginia Department of Environmental Quality assessment concluded that, under current permitting standards, no location in the Virginia Coastal Plain can support a major new groundwater withdrawal at the scale typical of some hyperscale data centers. A joint report by BSI Group and Waterwise found data centers rank among the world's top 10 most water-intensive industries. In Alberta, a large proposed campus near Calgary was rejected, with water use cited alongside environmental, power, and agricultural issues. The article also describes cooling technology tradeoffs: direct evaporative cooling remains dominant because it is cheap to install and operate, scales to very large facilities, and uses less electricity than mechanical refrigeration, but it consumes large volumes of water and most intake exits as vapor, with mineral-concentrated blowdown requiring treatment before reuse. Liquid cooling (direct-to-chip and immersion), mechanical refrigeration, and free cooling are available alternatives, but high installation costs, energy availability constraints, and scalability considerations have slowed adoption. Seawater cooling via approaches such as wet surface air cooling is described as technically feasible, with the main obstacle financial rather than technical. ### Key figures - Virginia DEQ assessment (July 2026): no location in the Virginia Coastal Plain can support a major new groundwater withdrawal at hyperscale scale under current permitting standards. - Near the I-95 data center corridor: modeled sustainable groundwater capacity below 30,000 gallons per day. - Highest regional estimate: around 360,000 gallons per day in the eastern Northern Neck, still far below hyperscale needs. - About 95% of total data center water use comes from municipal water, per the article. - A single 1 MW facility can consume over 25 million liters of water annually, per the BSI Group and Waterwise joint report. - Global data center capacity is projected to nearly double by 2030. - WUE is defined as total water consumed per kilowatt-hour of IT energy (liters/kWh). ### Why it matters to ebm-papst This roundup is a demand-side signal for cooling architecture rather than a direct competitive event. The article states that evaporative cooling remains prevalent on cost and electricity grounds, while liquid cooling adoption has been slowed by high installation costs, energy availability constraints, and scalability considerations. It also states that closed-loop or hybrid heat-rejection systems can cut potable demand but add cost, complexity, footprint, and often higher electricity use in many climates, and that economics in many markets still favor conventional evaporative designs. Assessment (inference): For ebm-papst, a tightening water constraint that pushes operators toward closed-loop, hybrid, and liquid-cooling architectures expands the addressable market for high-efficiency air-moving and pump-adjacent thermal management content, since these designs shift the heat-rejection burden toward dry and hybrid systems that depend more heavily on fans and blowers. Assessment (inference): The Virginia finding that groundwater cannot support hyperscale withdrawals, combined with sub-30,000-gallon-per-day modeled capacity along the I-95 corridor, suggests that siting decisions in that corridor will increasingly be decided by water and power availability together, which favors suppliers able to offer low-water cooling solutions as part of a siting-enablement story. Assessment (inference): The article's emphasis on peak-stress performance rather than average WUE implies that customers will increasingly specify cooling equipment against extreme-heat design conditions, a specification regime in which fan performance curves and high-ambient reliability become differentiating. Assessment (inference): The Alberta rejection and the Imperial Valley dispute indicate rising community and regulatory friction, which may lengthen project timelines and shift procurement toward vendors with documented low-water and low-noise product lines. No specific figures on ebm-papst, its competitors, or its customers were disclosed in the source material.
Full text
Data Center Water Use: From Efficiency Metrics to Real-World Resilience
Water has shifted from a background utility to a core constraint for data centers, requiring site-specific resilience planning that addresses peak stress, local hydrology, and community impact, not just average efficiency metrics.
September 23, 2026
Data centers are facing a new reality: water is no longer a background utility but a core constraint that shapes siting, design, operations, and community relations. The conversation is moving beyond average efficiency metrics to show that facilities can operate under peak stress conditions without exacerbating local water stress or pollution. This roundup of Data Center Knowledge articles connects technical, economic, and policy dimensions of data center water use and highlights where the industry is headed next.
Metrics and Measurements
Water Use Effectiveness (WUE) measures a data center’s total water consumed per kilowatt-hour of IT energy (liters/kWh). Tracking WUE supports sustainability goals, cost control, cooling optimization, and transparent community reporting. However, WUE can be misleading if taken alone because it doesn’t reflect water sourcing or consistently measured boundaries, and it’s a relative metric (not total water use). Ambient conditions and metering practices can also affect comparability across sites.
Beyond WUE: Measuring Resilience Where It Matters
Water resilience for data centers can’t be judged by WUE or “waterless” claims alone; it must be proven under peak stress, according to water treatment specialist Dr. Marcello Serrano. Using California’s Imperial Valley dispute over a proposed AI data center as an example, Serrano argues that credible stewardship hinges on site-specific, transparent assessments that address five areas:
- Peak operations under extreme heat
- Water rights and curtailment risks during shortages
- Reclaimed water availability and quality onsite
- Discharge constraints (sewer capacity, permits, and thermal/chemical limits)
- Water-energy tradeoffs vs. grid and environmental conditions
Applied early in site selection and operations, this framework helps operators and utilities plan, align on capacity and discharge requirements, and avoid escalating resource conflicts into litigation.
Cooling Technologies
Why Cooling Water Is Hard to Reuse
Since most data centers rely on direct evaporative cooling, most intake water exits as vapor, while the mineral-concentrated remainder is periodically flushed as blowdown, which typically requires treatment before any onsite reuse. While facilities can cut potable demand by implementing closed-loop or hybrid heat-rejection systems, treating blowdown, or repurposing residual water as graywater, these approaches add costs, complexity, footprint, and often higher electricity use in many climates. As of now, economics in many markets still favor conventional evaporative designs, though rising water prices and evolving regulations could change that.
Technology Trajectory: Evaporative Today, Liquid Tomorrow
Evaporative cooling remains prevalent because it is inexpensive to install and operate, scales effectively to very large facilities, and uses less electricity than mechanical refrigeration. However, it consumes large amounts of water and can strain local supplies. Alternatives such as liquid cooling (direct-to-chip and immersion), mechanical refrigeration, and free cooling are available, but high installation costs, energy availability constraints, and scalability considerations have slowed adoption.
Water Sources and Treatment
Practical Pathways to Lower Freshwater Demand
Most data centers use municipal water for cooling – about 95% of total data center water use – which can burden communities by contributing to shortages and higher costs. Alternatives can reduce pressure on potable systems, including surface water (rivers and lakes), seawater (with corrosion and distillation considerations), groundwater (where available), wastewater, and graywater. As data center power use grows and groundwater constraints intensify, shifting from municipal supplies to alternative sources is increasingly important for sustainability and community impact.
Turning to the Sea: When Seawater Makes Sense
Standard evaporative cooling systems cannot use seawater without extensive pretreatment to manage scaling and corrosion. Alternative approaches, such as wet surface air cooling, can tap the sea as a heat sink. The main obstacle is financial, not technical, and growing water concerns alongside AI-driven demand may prompt more coastal facilities to evaluate seawater options despite higher upfront costs.
Siting and Infrastructure
AI-Scale Compute Makes Water a Siting Constraint
As dense GPU clusters concentrate unprecedented thermal loads, water is emerging as a siting constraint on par with power. Nearly all server energy becomes heat that must be rejected, and cooling choices create explicit electricity-water tradeoffs. Municipal systems, built for distributed, steady loads, can struggle to meet data centers’ high peaking factors during extreme conditions, and wastewater capacity and reclaimed water access are becoming strategic constraints.
Infrastructure Reality Check: Virginia’s Groundwater and Urban Utilities
A July 2026 Virginia DEQ assessment concluded that, under current permitting standards, no location in the Virginia Coastal Plain can support a major new groundwater withdrawal at the scale typical of some hyperscale data centers. Near the I-95 data center corridor, modeled sustainable capacity is below 30,000 gallons per day, with the highest regional estimate around 360,000 gallons per day in the eastern Northern Neck – still far below hyperscale needs. As a result, future developments in the region would need to rely on municipal or alternative water supplies, making water availability a key constraint alongside power and transmission.
Environmental and Health Impacts
Water Pollution Risks from Cooling Systems
Data centers’ evaporative cooling can introduce biocides, corrosion inhibitors, and metals into local waters, especially at high discharge volumes. To reduce the impact, operators should favor lower- or no-water cooling where possible, use safer chemistry, distribute discharges, and route or treat wastewater before release.
Policy and Governance
The Global Picture: Rapid Growth, Patchwork Governance
Data centers rank among the world’s top 10 most water-intensive industries, per a joint report by BSI Group and Waterwise. A single 1 MW facility can consume over 25 million liters of water annually. Many high-growth markets lack robust water governance and water-efficiency policies, even as the global data center capacity is projected to nearly double by 2030. Without coordinated policy, enforceable standards, and broader adoption of alternative cooling and non-potable water sources, AI- and cloud-driven expansion may deepen water stress in already constrained regions.
Community and Stakeholders
Community Impacts: Alberta’s Debate
Calgary and other Alberta communities have experienced recent water main breaks and restrictions, fueling concerns that data center growth may increase pressure on municipal systems. A large proposed campus near Calgary was rejected, with water use cited alongside environmental, power, and agricultural issues, even as other projects and AI hubs move forward. Given Canada’s cold climate, experts note that low- or zero-water cooling can be economically attractive and help mitigate municipal water dependencies, though it’s not universally necessary or appropriate in every region.
The Bottom Line
Proving water resilience is becoming central to data centers’ license to operate. That entails planning for extremes, matching designs to local hydrology and infrastructure, prioritizing non-potable sources and closed-loop systems where feasible, tightening discharge controls, and engaging transparently with regulators and communities. Metrics such as WUE remain useful, but context-based, site-specific resilience will determine whether facilities can grow sustainably in a water-constrained world.