## Intelligence brief

### What happened TICA (Nanjing TICA Climate Solutions) published the final installment of its white paper series on liquid cooling for the high-density AI computing era, released via an aggregated company channel dated 18 September 2026. The first two installments covered rising server heat-removal demand and industry pain points, and the evolution of AIDC HVAC architectures; this closing part presents TICA's integrated AIDC HVAC solution for ultra-high-density computing scenarios, positioned around full-chain in-house development and manufacturing. The solution spans a primary-side cooling source, a secondary-side liquid cooling unit, and a secondary-side air-assisted terminal. On the primary side, TICA offers magnetic-bearing chillers and dry coolers. TICA states it wholly acquired Smardt, a leading global magnetic-bearing chiller brand, and that Smardt oil-free magnetic-bearing chillers deliver zero friction, zero oil and zero degradation, can run stably down to 2% load, and reach a part-load COP of up to 32.1; a "Smart Lift" function supports stable operation with high chilled-water supply temperatures. Dry coolers target "East Data West Computing" hub nodes and favorable climates, with free cooling exceeding eight months per year in northern China and spray/wet-film pre-cooling in hot-humid southern regions; chillers shut off entirely when outdoor dry-bulb temperature falls below 27.5 C, with supply/return water around 25/35 C. On the secondary side, TICA has developed high-power liquid cooling CDUs for 130-200 kW racks, matched to NVIDIA GB200 NVL72 and GB300 NVL72 cabinets, plus dual-source air walls sharing the same primary-side cooling water for cabinet air cooling loads. ### Key figures - Part-load COP of Smardt magnetic-bearing chillers: up to 32.1 - Minimum stable load: 2% - Energy saving versus traditional computer rooms via OPTSEEK platform: more than 40% - Free cooling duration in northern China: more than 8 months per year - Dry cooler changeover threshold: outdoor dry-bulb below 27.5 C; supply/return water about 25/35 C - CDU for GB200 NVL72: rated heat exchange capacity 1350 kW; secondary flow about 11.6 m3/h at 10 C supply-return differential; covers 115 kW liquid cooling load - CDU for GB300 NVL72: 1500 kW capacity; flow about 12.9 m3/h at 10 C differential; addresses 121 kW continuous liquid cooling load plus transient peaks - Rack power range addressed: 130-200 kW - Air cooling loads: GB200 17 kW, GB300 21 kW - Air wall supply air temperature: 18-27 C (recommended 22-26 C) - EC fan energy saving versus AC fans: 25%-40%; fan noise as low as about 60 dB(A) - Claimed efficiency gain of GB200 NVL72 liquid cooling versus traditional air cooling: 25x - WUE of dry-mode-first strategy: approximately 0 ### Why it matters to ebm-papst TICA is positioning itself as a full-stack AIDC thermal management supplier, from primary cooling source through CDU to rack-level air terminals, explicitly aligned to NVIDIA GB200 and GB300 NVL72 platforms. This is a competitive signal in the data center cooling value chain: a Chinese HVAC manufacturer is consolidating chiller, CDU and air-side content under one in-house portfolio, which could reduce the number of separate component suppliers per project. Assessment (inference): The air-side portion of TICA's architecture, specifically the dual-source air walls using EC variable-frequency fans, is the most directly relevant element for ebm-papst, since EC fans are a core ebm-papst product category and TICA does not state which fan supplier it uses. Assessment (inference): TICA's stated 25%-40% EC-versus-AC fan energy saving and roughly 60 dB(A) noise level are the performance benchmarks ebm-papst would need to match or beat in any bid for this class of air wall. Assessment (inference): The emphasis on high chilled-water temperatures (25 C supply) and extended free cooling favors fan-heavy dry cooler and air wall designs, which could expand the addressable fan content per megawatt of IT load. Assessment (inference): Because TICA claims full-chain self-development and self-production, ebm-papst should treat TICA primarily as a potential competitor at system level and as a possible OEM customer only for components TICA does not manufacture itself; the white paper does not disclose TICA's fan sourcing, so this remains uncertain.

## Full text (English translation)

TICA's white paper is dedicated to providing liquid cooling solutions in the high-density AI era. In the first installment, we pointed out the growth in server heat dissipation demand in the AI era and the industry's pain points; in the second installment, we discussed the latest evolution direction of AIDC HVAC architecture; this installment, building on the previous ones, presents TICA's overall AIDC HVAC solution for ultra-high-density computing scenarios, responding to the heat dissipation challenges of the AI computing era with full-chain in-house development and production capabilities.

AIDC full-link thermal management solution

TICA data center full-chain overall solution

Full-dimensional adaptation to GB200/GB300 servers

In response to the differentiated heat dissipation needs of NVIDIA's two ultra-high-power rack-scale systems, TICA, relying on its self-developed magnetic-bearing chillers, standardized liquid cooling CDUs, dual-source terminals, and smart energy-carbon management platform, has built an integrated HVAC system of primary-side common-source cooling plus secondary-side air-liquid dual-loop, with one cooling source simultaneously supporting GB200/GB300 air-cooled compartments, IT compartments and ultra-core compartments, perfectly balancing the needs of both new intelligent computing centers and existing computer room retrofits.

Primary-side cooling source system

Magnetic-bearing chiller units & dry coolers, adapted to high-temperature liquid cooling supply requirements

1. Magnetic-bearing chiller (core cooling source)

TICA wholly acquired the world's leading magnetic-bearing brand SMARDT; the magnetic-bearing solution, as the primary-side cooling source system, is deeply adapting to AIDC high-temperature liquid cooling supply needs, providing reliable cooling source guarantees for high-density computing scenarios where single-cabinet power exceeds the MW level. SMARDT oil-free magnetic-bearing chillers use magnetic-bearing technology to achieve zero friction, zero lubricating oil, and zero degradation operating characteristics. The unit has an ultra-wide adjustment capability to operate stably at loads as low as 2%, and can maintain high efficiency under low ambient temperature and high chilled water temperature conditions, with part-load COP up to 32.1. At the same time, the unit's unique "Smart Lift" function ensures stable operation under high-temperature chilled water supply conditions, omitting complex cooling water bypass design and directly matching the liquid cooling CDU's demand for medium-to-high temperature cooling sources.

At the system level, TICA, through an air-liquid common-source architecture, integrates high-efficiency magnetic-bearing chillers with liquid cooling CDUs, compatible with traditional air cooling and able to smoothly adapt to the new generation of liquid cooling. Relying on the OPTSEEK smart IoT platform for AI active optimization and energy efficiency visualization, it saves more than 40% energy compared with traditional computer rooms. This solution has already been applied in multiple ultra-large-scale intelligent computing projects.

2. Dry cooler (natural cooling source)

The dry cooler natural cooling source system is an efficient cooling solution designed for "East Data West Computing" hub nodes and climate-appropriate regions. In northern regions with a large annual dry-bulb/wet-bulb temperature difference, the system's annual natural cooling duration can exceed 8 months, effectively reducing mechanical refrigeration energy consumption; in the hot and humid southern regions, spray/wet-film pre-cooling technology is used to achieve isenthalpic cooling, bringing the dry-bulb temperature down to near the wet-bulb temperature, further extending the available period of natural cooling.

In terms of system control strategy, when the outdoor dry-bulb temperature is below 27.5 C, the chiller is completely shut down, and the dry cooler directly provides primary-side chilled water to the liquid cooling CDU, with supply and return water temperatures maintained at around 25/35 C, meeting the high-temperature liquid cooling needs of GB300 clusters and others. The unit uses fully variable-frequency EC fans, and the AI controller dynamically adjusts fan speed and spray volume based on outdoor temperature and humidity changes and real-time cabinet load fluctuations, ensuring stable and controllable chilled water outlet temperature, responding to instantaneous thermal shocks in seconds, and solving the cooling lag problem caused by drastic load fluctuations in AI training tasks.

In addition, the dry-mode-first strategy greatly reduces spray water use, with WUE approximately 0, achieving the balance between extreme water saving and efficient natural cooling. The system has a simple structure and low maintenance, and has been replicated and promoted in multiple large intelligent computing centers at home and abroad.

Secondary-side liquid cooling core unit

TICA's dedicated CDU cooling distribution system adapted to NVL72 cabinets

The CDU is the core hub connecting the primary-side cooling source and the GB200/GB300 liquid cooling cabinets. Based on mainstream industry design standards, TICA has independently developed high-power liquid cooling CDUs adapted to 130-200 kW ultra-high-density cabinets, perfectly matching the flow, pressure and temperature requirements of the two rack-scale systems:

1. Graded cooling capacity precise matching
(1) Adapted to GB200 NVL72 model: CDU rated heat exchange capacity 1350 kW, secondary-side rated flow matching low-temperature-difference high-efficiency heat exchange (e.g., under a supply-return liquid temperature difference of 10 C, flow about 11.6 m3/h), precisely covering 115 kW liquid cooling heat load, with peak redundancy reserved;
(2) Adapted to GB300 NVL72 model: upgraded 1500 kW large-capacity CDU, flow adapted to higher loads (under a supply-return liquid temperature difference of 10 C, flow about 12.9 m3/h), handling 121 kW continuous liquid cooling load and instantaneous peak heat generation;

2. Safety redundancy design adapted to 7x24-hour computing operation

The internal plate heat exchanger isolates the primary-side chilled water from the server's secondary-side deionized loop, preventing impurities from municipal cooling sources from entering the chip microchannel cold plates; dual variable-frequency redundant pump sets, where if one pump fails the other automatically runs at 100% load; built-in high-precision temperature, pressure and conductivity sensors monitor coolant leakage and water quality degradation in real time, and once abnormal, link to server warnings to avoid GPU overheating and downtime;

3. High-temperature heat exchange energy-saving characteristics

Supports 25 C standard supply liquid, and can achieve wide-range flexible adjustment. A higher supply liquid temperature greatly extends the available duration of natural cooling sources and reduces dependence on mechanical refrigeration. Compared with traditional air cooling architecture, the GB200 NVL72 liquid cooling system can achieve a 25-fold energy efficiency improvement, significantly reducing the data center's cooling energy consumption and carbon footprint.

Secondary-side air cooling auxiliary terminal

Dual-source air wall matching cabinet air cooling heat dissipation needs

GB200 air cooling load is 17 kW, GB300 air cooling load is 21 kW. TICA's dual-source air wall, as the auxiliary heat dissipation terminal of the computer room, shares the same primary-side cooling water with the liquid cooling system, realizing a cooling tower common-source architecture:

1. Dual-coil structure:
Pre-cooling natural coil + mechanical compression refrigeration coil two-stage water circuit, greatly extending the natural cooling operation duration and significantly reducing annual compressor energy consumption. Under low-load/low-temperature conditions, only the natural cooling coil operates, with outdoor cold source chilled water passed into the natural cooling coil, using the outdoor free cooling source to complete heat exchange, and the compressor and refrigerant system completely shut down; under medium-high load/high-temperature conditions, the compressor is started, and the hot air is first pre-cooled by the natural cooling coil, then deeply cooled by the compressor refrigeration coil, with the dual coils' heat exchange capacity superimposed to supplement the cooling capacity required by high heat loads and stably control the computer room inlet air temperature.

2. Precise temperature control:
The air wall outlet air temperature is strictly controlled at 18-27 C (recommended operating range 22-26 C), ensuring each GPU receives the design-condition inlet air temperature, effectively breaking the "thermal series effect" in high-density deployment, avoiding GPU frequency reduction caused by local hot spots, and ensuring the AI cluster continues to run at full load.

3. Quiet and low consumption:
Using EC variable-frequency fans, compared with traditional AC fans, fan energy consumption can be reduced by 25%-40% under different conditions. The fan body noise can be as low as about 60 dB(A), significantly improving the operation and maintenance working environment.

As an AIDC intelligent computing center thermal management expert, TICA builds a solid foundation from cooling source to cabinet for GB200/GB300 ultra-high-density computing power. This is not only a generational leap in heat dissipation technology, but also a deep response to the era proposition of "computing power is productivity" - cooling has become an irreplaceable key infrastructure for AI scale implementation.

Looking to the future, TICA will continue to deeply cultivate core heat dissipation technologies for high-density computing power, build a solid foundation of independent and controllable industrial resilience with self-developed components, and drive extreme energy efficiency and green operations with smart energy-carbon management, so that every kilowatt-hour of electricity is converted into surging computing power.

## Full text (original)

天加环境白皮书致力于在高密AI时代提供液冷解决方案。在第一篇内容中我们指出了AI时代服务器散热需求的增长与行业痛点；第二篇中，我们探讨了AIDC暖通架构最新演进方向；本篇将站在前文之上，给出天加面向超高密算力场景的AIDC暖通整体解决方案，以全链条自研自产能力回应AI算力时代的散热难题。
AIDC全链路热管理方案
天加数据中心全链条整体解决方案
全维度适配GB200/GB300服务器
针对英伟达两款超高功耗整机柜差异化散热需求，天加依托自研磁悬浮冷机、标准化液冷CDU、双冷源末端、智慧能碳管控平台，打造一次侧同源冷源+二次侧风液双回路一体化暖通体系，一套冷源同时支撑GB200/GB300风冷包间、IT包间与超核包间，完美平衡新建智算中心、存量机房改造两类场景需求。
一次侧冷源系统
磁悬浮主机＆干冷器，适配高温液冷供液需求
1.磁悬浮冷水机组（核心冷源）
天加全资并购全球头部磁悬浮品牌SMARDT，磁悬浮解决方案作为一次侧冷源系统，正深度适配AIDC高温液冷供液需求，为单柜功率突破MW级的高密度算力场景提供可靠冷源保障。SMARDT无油磁悬浮冷水机组，采用磁悬浮轴承技术实现0摩擦、0润滑油、0衰减的运行特性。该机组具备低至2%负荷率仍可稳定运行的超宽调节能力，并可在低环温、高冷冻水温工况下保持高效，部分负荷COP最高可达32.1。同时，机组特有的“Smart Lift”功能可确保高温冷冻水供水条件下的稳定运行，省略复杂的冷却水旁通设计，直接匹配液冷CDU对中高温冷源的需求。
在系统层面，天加通过风液同源架构融合磁悬浮高效主机与液冷CDU，既可兼容传统风冷，也能平滑适配新一代液冷散热。依托OPTSEEK智慧物联平台实现AI主动寻优与能效可视化，较传统机房节能40%以上。该方案已在多个超大规模智算项目。
2.干冷器（自然冷源）
干冷器自然冷源系统是针对“东数西算”枢纽节点及气候适宜地区设计的高效冷却方案。在北方年均干湿球温差较大的区域，该系统全年自然冷却时长可超过8个月，有效降低机械制冷能耗；在南方湿热地区，则通过喷淋/湿膜预冷技术实现等焓降温，将干球温度降至湿球温度附近，进一步延长自然冷却可用时段。
系统控制策略上，当室外干球温度低于27.5℃时，冷水机组完全关闭，由干冷器直接为液冷CDU提供一次侧冷冻水，供回水温度可维持在25/35℃左右，满足GB300集群等高温液冷需求。机组采用全变频EC风机，AI控制器依据室外温湿度变化及机柜实时负载波动，动态调节风机转速与喷淋量，确保冷水出水温度稳定可控，秒级响应瞬时热冲击，解决AI训练任务负载剧烈波动带来的供冷滞后难题。
此外，干模式优先策略大幅减少喷淋用水，WUE≈0，实现极致节水与高效自然冷却的平衡。该系统结构简洁、维护量低，已在海内外多个大型智算中心中复制推广。
二次侧液冷核心单元
天加适配NVL72机柜专用CDU冷却分配系统
CDU是连接一次侧冷源与GB200/GB300液冷机柜的核心枢纽，天加基于行业主流设计标准，自主研发适配130~200kW超高密机柜的大功率液冷CDU，完美匹配两款整机柜流量、压力、温度需求：
1. 分级制冷容量精准匹配
⑴ 适配GB200 NVL72机型：CDU额定换热容量1350kW，二次侧额定流量匹配低温差高效换热（如供回液温差10℃工况，流量约11.6m³/h），精准覆盖115kW液冷热负荷，并预留峰值冗余；
⑵ 适配GB300 NVL72机型：升级1500kW大容量CDU，流量适配更高负载（供回液温差10℃工况，流量约12.9m³/h），应对121kW持续液冷负荷与瞬时峰值发热；
2. 安全冗余设计适配7×24小时算力运行
内部板式换热器隔离一次侧冷冻水与服务器二次去离子回路，杜绝市政冷源杂质进入芯片微通道冷板；双变频冗余泵组，单泵故障另一台自动100%负荷运行；内置高精度温度、压力、电导率传感器，实时监测冷却液漏液、水质劣化，一旦异常联动服务器预警，避免GPU过热宕机；
3. 高温换热节能特性
支持25℃标准供液，并可实现宽区间弹性调节。更高的供液温度大幅延长了自然冷源的可用时长，减少了对机械制冷的依赖。相比传统风冷架构，GB200 NVL72液冷系统可实现25倍的能效提升，显著降低数据中心的冷却能耗与碳足迹
二次侧风冷辅助末端
双冷源风墙匹配机柜风冷散热需求
GB200风冷负荷17kW、GB300风冷负荷21kW，天加双冷源风墙作为机房辅助散热末端，与液冷系统共用同一套一次侧冷却水，实现冷塔同源架构：
1、双盘管结构：
预冷自然盘管+机械压缩制冷盘管两级水路，大幅延长自然冷却运行时长，显著降低全年压缩机能耗。低负载/低温环境工况仅自然冷却盘管运行，室外冷源冷水通入自然冷却盘管，利用室外免费冷源完成热量置换，压缩机、冷媒系统完全停机；中高负载/高温环境工况，启动压缩机，热风先经自然冷盘管预降温，再通过压缩机制冷盘管深度冷却，双盘管叠加换热容量，补足高热负载所需冷量，稳定控制机房进风温度。
2、精准控温：
风墙出风温度严格控制在18~27℃（推荐运行区间22~26℃），确保每台GPU获得设计工况的进风温度，有效打破高密度部署中的“热串联效应”，避免局部热点导致GPU降频，保障AI集群持续满负荷运行。
3、静音低耗：
采用EC变频风机，相较传统AC风机，在不同工况下可降低25%~40% 的风机能耗。风机本体噪音可低至60dB(A) 左右，显著改善运维工作环境。
天加作为AIDC智算中心热管理专家，为 GB200/GB300 超高密算力构筑起从冷源到机柜的坚实底座。这不仅是散热技术的代际跃迁，更是对 "算力即生产力" 时代命题的深度回应 —— 冷却，已成为 AI 规模落地不可替代的关键基础设施。
面向未来，天加将持续深耕高密算力散热核心技术，以自研部件筑牢自主可控的产业韧性，以智慧能碳管控驱动极致能效与绿色运营，让每一度电都转化为澎湃算力。