# Intel certifies Castrol and Envicool single-phase cold plate coolants in Shanghai, targeting 80%+ liquid cooling market

- Source: News · Envicool (T2)
- Published: 2026-06-26
- Score: 63.6
- Tags: Product launch, Policy / standards, Datacenter, Supply chain
- Companies: Envicool (002837.SZ)
- Original: https://www.sohu.com/a/1042085498_121948415

## Intelligence brief

### What happened On June 24, 2026, Intel held a "Cold Plate Coolant Qualification Verification and Ecosystem Launch Event" in Shanghai, releasing the results of its single-phase cold plate liquid cooling coolant test and verification program. Two companies' products passed Intel's stringent validation: Castrol (with its PG 25 C propylene glycol-based coolant) and Envicool (Shenzhen Envicool Technology). Intel presented qualification plaques to both. Intel positioned this as more than a product certification exercise. According to David Zhou (Zhou Shaorong), Senior Principal Engineer at Intel China's Data Center Group, Intel is acting as a neutral industry party to build a standardized coolant certification system and cultivate a local liquid cooling supply chain. Intel combined its internal Liquid Cooling Design Guide (LCDG) with OCP single-phase cold plate specifications to create the validation framework. Unlike traditional single-sample lab testing, the validation was based on a real secondary-side circulation loop replicating cold plates, manifolds, tubing, and seals as deployed in data centers. Boundary conditions were set at 1.5 m/s inlet flow velocity and 65 degrees C outlet liquid temperature, using high-temperature accelerated aging to simulate long-term effects. All samples were sent to third-party authoritative institutions under a double-blind protocol, with Intel making final compliance determinations. The test cycle lasted over seven months, covering 30 sampling batches and more than 9,000 data points. Zhou noted that previously only two North American coolant suppliers had passed Intel validation, but they lacked local production bases, had delivery lead times exceeding six weeks, and carried high costs, so leading domestic CSP customers in China largely did not adopt them. This drove Intel China to launch its "Liquid Cooling Innovation Acceleration Plan." Castrol's project ran 14 months from April 2025 project initiation to June 2026 results release, working with local partner Yixintong to build the complete test loop using Intel TTV thermal test vehicles. ### Key figures - Single-phase cold plate liquid cooling accounts for over 80% of the current liquid cooling market - AI chip power consumption has risen from several hundred watts to over 1,000 watts per chip - Validation boundary conditions: 1.5 m/s inlet flow velocity, 65 degrees C outlet liquid temperature - Qualification thresholds: corrosion inhibitor retention rate above 80% of initial value; cold plate thermal performance deviation below 5%; metal corrosion rate below 0.22 mils per year (0.22 thousandths of an inch per year) - Test duration: over 7 months; 30 sampling batches; over 9,000 data points collected - Castrol PG 25 C formulation: 25% propylene glycol + 75% deionized water - Castrol accelerated aging test: 180 days, liquid remained clear with no precipitation or discoloration - EPDM seal retention rates: above 95% for hardness, mass, volume, and tensile properties - Castrol project timeline: 14 months from April 2025 to June 2026 - Previous North American coolant suppliers: delivery lead times exceeding 6 weeks - Castrol heritage: 127 years of fluid technology accumulation - Servers account for 60%-70% of total investment in high-density data centers (per Castrol Greater China Business Director Qiu Yuanyuan) - Castrol test temperature set at 65 degrees C, approximately 20 degrees C above normal server operating temperature ### Why it matters to ebm-papst This development signals accelerating standardization in the liquid cooling ecosystem, which directly affects ebm-papst's data center cooling business. Intel's validation framework is expanding beyond coolants to cold plates, quick connectors, CDUs, and manifolds, meaning the entire cold plate liquid cooling supply chain will face standardized certification requirements. Assessment (inference): For ebm-papst, this represents both a competitive threat and a market opportunity. As a major supplier of fans and blowers for data center cooling, ebm-papst should monitor whether Intel's certification framework will eventually extend to air-movement components within CDUs and cold plate systems. If standardized certification becomes a procurement prerequisite, ebm-papst may need to engage with Intel's Liquid Cooling Innovation Acceleration Plan to ensure its products are qualified for the ecosystem. Conversely, the growth of liquid cooling does not eliminate fan demand; CDUs, heat rejection units, and hybrid cooling architectures still require high-efficiency air movement, and ebm-papst's expertise in high-static-pressure, energy-efficient fans positions it well for CDU and sidecar cooling applications. The localization push in China's liquid cooling supply chain, driven by Intel's initiative, suggests that ebm-papst's local manufacturing and R&D presence in China could be a competitive advantage when serving domestic CSP customers who prioritize local supply and fast response. The emphasis on end-to-end service models (as Castrol is pursuing) also suggests that component suppliers may need to offer broader lifecycle support rather than just products.

## Full text (English translation)

With the explosive growth of AI large models and high-performance computing, the power consumption of a single AI chip has surged from several hundred watts to over a thousand watts, and data center heat density continues to climb. Under this trend, liquid cooling is rapidly transitioning from a high-end option to a "must-have" for high-computing-power deployments.

From the market perspective, single-phase cold plate liquid cooling, with advantages such as flexible deployment and adaptability to existing computer rooms, occupies more than 80% of the current market share, becoming the mainstream route for large-scale liquid cooling deployment today.

However, behind the rapid expansion of the industry, the liquid cooling sector also faces pain points such as inconsistent standards, no basis for selection, lack of unified testing and certification for key components, and insufficient supply chain collaboration, which directly constrain the long-term reliable operation of data centers.

On June 24, 2026, Intel held the "Cold Plate Coolant Qualification Verification and Ecosystem Launch Event" in Shanghai, officially releasing the single-phase cold plate liquid cooling coolant test and verification results. Products from Castrol and Envicool successfully passed Intel's stringent validation.

This launch event was not just a product certification ceremony, but a key step by Intel, in its neutral industry capacity, to lead the construction of a standardized coolant certification system and cultivate a local liquid cooling supply chain, anchoring a quality benchmark for the standardized development of the entire liquid cooling ecosystem.

Liquid cooling solutions accelerate, Intel fills the industry standard gap

"Liquid cooling coolant is the most critical factor in the entire liquid cooling circulation loop. It is equivalent to human blood. Its performance and quality determine the upper limit of heat dissipation capability. Its material compatibility with pipes and cold plates directly relates to risks such as leakage, scaling, and corrosion. It is the most critical factor for the long-term reliable operation of the entire liquid cooling loop," said David Zhou (Zhou Shaorong), Senior Principal Engineer at Intel China Data Center Group, in his speech.

But during the rapid development phase of the industry, there has always been a lack of a neutral, credible, and comprehensive coolant verification system. Customers mostly rely on manufacturers' self-certification for selection, lacking authoritative basis for horizontal comparison.

"In earlier years, only two North American manufacturers had liquid cooling coolants verified by Intel. They had no local production bases, delivery lead times exceeded 6 weeks, and costs were high. Leading domestic CSP customers almost none adopted them," Zhou admitted at the launch event. Local customers have strong demands for nearby supply, rapid response, and cost-controllable liquid cooling coolants, which is the core motivation for Intel China to initiate the "Liquid Cooling Innovation Acceleration Plan" and lead local coolant verification.

As one of the core formulators of the OCP single-phase cold plate liquid cooling specification, Intel combined its internal Liquid Cooling Design Guide (LCDG) with OCP industry standards to build a stringent verification system close to real scenarios. Unlike traditional laboratory single-sample testing, this verification was entirely based on a real secondary-side circulation loop, fully replicating cold plates, manifolds, pipes, seals, and other actual data center deployment components, and set stringent boundary conditions of 1.5 m/s inlet flow velocity and 65 degrees C outlet liquid temperature, using high-temperature accelerated aging to simulate long-term aging effects.

According to reports, the verification set clear qualification thresholds: corrosion inhibitor retention rate must be above 80% of the initial value, cold plate thermal performance deviation must be below 5%, and various metal corrosion rates must be below 0.22 thousandths of an inch per year. The entire test cycle lasted over 7 months, completing 30 sampling batches and collecting over 9,000 data points. The test dimensions also expanded from traditional coolant chemical composition analysis to system-level indicators such as metal contact material corrosion rates, non-metal material mechanical property changes, and cold plate thermal performance stability.

Notably, to ensure objective and neutral results, all samples were sent to third-party authoritative institutions under a double-blind mode, with Intel making final compliance determinations.

"What we did is not just product qualification testing, but giving the industry a reusable verification methodology," Zhou emphasized. This verification standard is not exclusive to the China region. All verified products will be simultaneously published on Intel's global IDC technical documentation platform, with equal validity to certification results from North American and European laboratories, and global customers can directly reference them for selection.

From formulation to full lifecycle: Castrol's technical accumulation and local practice

Among the products that passed verification this time, Castrol PG 25 C propylene glycol-based coolant, with its excellent comprehensive performance, became the first batch of internationally branded locally supplied products to receive Intel certification.

Intel presented Castrol with the single-phase cold plate liquid cooling coolant qualification plaque.

According to reports, from project initiation in April 2025 to results release in June 2026, the entire project lasted 14 months. Castrol worked with local partner Yixintong to build a complete test loop, using Intel TTV thermal test vehicles to simulate real chip cooling conditions, completing the full process from laboratory formulation to system-level verification.

"PG 25 is not an arbitrarily set concentration, but the optimal balance point verified by long-term industry practice," explained Fan Qinghua, Technical Manager of Thermal Management Fluids at Castrol, in a technical sharing. Deionized water itself has excellent thermal conductivity but has shortcomings such as easy bacterial growth and metal corrosion; the higher the propylene glycol concentration, the stronger the antibacterial and anti-corrosion ability, but the thermal conductivity decreases accordingly. After extensive practical verification, the ratio of 25% propylene glycol + 75% deionized water can achieve the best balance among thermal conductivity, antibacterial performance, and anti-corrosion ability, and is also a general consensus in the global liquid cooling industry.

From the test results, various indicators of Castrol PG 25 C significantly outperformed industry benchmarks:
- In the 180-day accelerated aging test, the liquid remained clear and transparent throughout, with no precipitation or discoloration;
- In metal corrosion testing, corrosion rates of various materials such as copper, solder, brass, steel, and cast iron all outperformed ASTM D1384 standard requirements;
- In non-metal compatibility testing, the retention rates of hardness, mass, volume, and tensile properties of EPDM seals all reached above 95%, effectively avoiding leakage risks caused by seal deformation and ion precipitation after long-term immersion.

In a post-event interview, Qiu Yuanyuan, Business Director of Castrol Greater China, further interpreted the value of coolant reliability from the perspective of customer asset safety: "In high-density computer rooms, servers account for 60%-70% of total investment, and CPUs and GPUs are core value components. Coolant may seem to account for a low cost proportion, but it is a potential single point of failure in the system - once leakage occurs, it may directly destroy IT equipment worth millions of dollars; if scaling or bacterial growth occurs, it will lead to decreased heat dissipation capability, ultimately dragging down computing power output."

Interviewed guests (from left to right):
Song Ting, Global Marketing Director of Castrol Thermal Management Division
Qiu Yuanyuan, Business Director of Castrol Greater China
David Zhou (Zhou Shaorong), Senior Principal Engineer at Intel China Data Center Group

He stated that Castrol proactively collected mainstream non-metal piping and seal products on the market before testing and completed compatibility verification in advance, precisely to help customers avoid hidden risks in long-term operation ahead of time. "We set the test temperature at 65 degrees C, about 20 degrees C higher than normal server operating temperature. The essence is to do accelerated aging experiments, using stringent conditions to verify product stability throughout the full lifecycle, giving customers sufficient confidence."

Beyond the technical performance of the product itself, Castrol is the first in the industry to propose the concept of "end-to-end integrated service," attempting to break the traditional model of liquid cooling coolant "selling products." Song Ting, Global Marketing Director of Castrol Thermal Management Division, said in the interview: "Castrol has 127 years of fluid technology accumulation. We are not just a lubricant brand; we want to transform into a thermal management solution service provider based on fluid technology capabilities."

According to reports, this end-to-end service covers the full lifecycle of the liquid cooling system: on-site liquid testing and filling services during the installation phase; regular laboratory monitoring and online fault handling during the operation phase; and global liquid recovery services at the end of life, helping customers achieve closed-loop management. The layout of local production bases allows Castrol to significantly shorten delivery cycles and reduce logistics costs, precisely matching local customers' demands for supply chain localization.

Beyond coolant: the long-term landscape of the liquid cooling ecosystem

The release of these coolant verification results is only a phased milestone in Intel's liquid cooling ecosystem layout.

Zhou revealed that the verification scope of the Liquid Cooling Innovation Acceleration Plan will not stop at coolants, but will gradually expand to cold plates, quick connectors, CDUs, manifolds, and other key components across the entire cold plate liquid cooling chain, continuously improving the standardization system of the entire ecosystem.

Regarding the industry-wide debate between cold plate liquid cooling and immersion liquid cooling technology routes, the interviewed guests also gave rational judgments. Zhou stated that single-phase cold plate liquid cooling currently occupies more than 80% of the market share and is the mainstream solution for large-scale deployment today; immersion liquid cooling has advantages in scenarios with higher computing power density and stronger waste heat recovery needs, and its share will gradually increase in the future, but the pace depends on industry collaboration progress, especially challenges such as load-bearing and operations in existing computer room renovations.

Meanwhile, environmental controversies over low-boiling-point fluorinated liquids have made single-phase immersion technology a more closely watched direction. Intel has also developed environmentally friendly single-phase immersion liquid cooling technology based on synthetic oil.

Castrol has also adopted a dual-line layout strategy. Qiu Yuanyuan told Semiconductor Industry Observer that in the cold plate liquid cooling field, Castrol PG 25 C has achieved large-scale batch deployment; in the immersion liquid cooling direction, Castrol's DC 15, DC 20, and other products have already conducted POC pilots in data centers in the UK, Australia, and domestically, and have also received Intel's single-phase immersion ecosystem cooperation recommendation. "Cold plate is the technology of the moment, immersion is the future waiting to bloom. We will walk on two legs and iterate in sync with industry demand."

From a broader industrial perspective, this coolant verification led by Intel not only fills a product standard gap, but also promotes the local liquid cooling supply chain from "scattered manufacturing" to "systematic certification," helping local manufacturers obtain authoritative endorsement in the global market.

For customers, unified certification standards greatly reduce selection costs and trial-and-error risks, giving liquid cooling deployment a clear quality reference; for the entire industry, a neutral third-party verification system will gradually end the fragmentation of coolant market standards, promoting the liquid cooling industry from rapid expansion to high-quality standardized development.

Solidifying the computing power foundation, pushing green AI one step forward

When the cooling needs of AI computing power collide with green and low-carbon policy requirements, liquid cooling has become a mandatory question for data center infrastructure upgrades. And the large-scale popularization of liquid cooling has never been a proposition that a single manufacturer can complete independently. It requires full-chain collaboration among chip manufacturers, coolant companies, system integrators, and end customers.

The release of Intel's cold plate liquid cooling coolant verification is a typical example of industrial collaboration: Intel builds the standard framework with its technical accumulation and industry credibility, while Castrol, Envicool, and other companies land products with technical accumulation and local production capacity. Together they output a reusable and trustworthy coolant quality benchmark for the industry.

With the continuous expansion of the liquid cooling ecosystem and the continuous improvement of the standard system, the cooling foundation of AI computing power will become more solid, and the entire data center industry will steadily move toward a more efficient, more reliable, and greener direction. Return to Sohu, view more

## Full text (original)

随着AI大模型与高性能计算的爆发式增长，单颗AI芯片的功耗已从几百瓦飙升至上千瓦，数据中心热密度更是持续攀升。在此趋势下，液冷散热正从高端选配迅速转变为高算力部署的“必选项”。
从市场现状来看，单相冷板液冷凭借部署灵活、适配存量机房等优势，占据当前市场80%以上份额，成为当下液冷规模化落地的主流路线。
然而行业快速扩容的背后，液冷行业也面临着标准不统一、选型无依据、关键部件缺乏统一测试认证以及供应链协同不足等痛点，直接制约着数据中心的长期可靠运行。
2026年6月24日，英特尔在上海举办“冷板冷却液资格验证暨生态发布会”，正式发布单相冷板液冷工质测试验证成果，嘉实多、英维克两家企业的产品顺利通过英特尔严苛验证。
这场发布会不仅是一次产品授牌，更是英特尔以中立行业身份牵头构建标准化工质认证体系、培育本土液冷供应链的关键一步，为整个液冷生态的规范化发展锚定了品质基准。
液冷方案提速，英特尔补位行业标准空白
“液冷工质是液冷整个循环回路中最关键的因素，它相当于人的血液，它的性能和品质决定了散热能力的上限，与管路、冷板的材料相容性直接关系到泄漏、结垢、腐蚀等风险，是整个液冷循环能够长期可靠运行的最关键因素。”英特尔中国数据中心集团高级主任工程师周绍荣（David Zhou）在演讲表示。
但在行业快速发展阶段，业内始终缺乏一套中立、可信、覆盖全维度的工质验证体系，客户选型多依赖厂商自证，缺乏横向对比的权威依据。
“早些年通过英特尔验证的液冷工质只有两家北美厂商，它们在本土没有生产基地，交货周期长达6周以上，成本也居高不下，国内头部CSP客户几乎都没有采用。”周绍荣在发布会上坦言，本土客户对就近供应、快速响应、成本可控的液冷工质有着强烈诉求，这也是英特尔中国发起“液冷创新加速计划”、牵头本土工质验证的核心动因。
作为OCP单相冷板液冷规范的核心制定者之一，英特尔将自身内部的液冷设计指南（LCDG）与OCP行业标准相结合，搭建了一套严苛且贴近真实场景的验证体系。与传统实验室单一样品测试不同，本次验证完全基于真实的二次侧循环回路，完整复刻了冷板、分水器、管路、密封件等数据中心实际部署部件，并设定了1.5m/s入口流速、65℃出口液温的严苛边界条件，通过高温加速模拟长期老化效应。
据介绍，验证设定了明确的合格阈值：缓蚀剂保留率须高于初始值的80%，冷板热性能偏差须低于5%，各类金属腐蚀速率须低于0.22千分之一英寸/年。整个测试周期长达7个多月，累计完成30批次取样、采集超9000个数据点，测试维度也从传统的工质化学组分分析，扩展到了金属触液材质腐蚀速率、非金属材质力学性能变化、冷板热性能稳定性等系统级指标。
值得关注的是，为确保结果客观中立，所有样本均采用双盲模式送往第三方权威机构检测，最终由英特尔统一判定合规性。
“我们做的不只是产品合格性测试，更是给行业一套可复用的验证方法论。”周绍荣强调，这套验证标准并非中国区域专属，所有通过验证的产品都会同步发布在英特尔全球IDC技术文档平台，与北美、欧洲实验室的认证成果具备同等效力，全球客户均可直接参考选型。
从配方到全周期：嘉实多的技术沉淀与本土实践
在本次通过验证的产品中，嘉实多PG 25 C丙二醇基冷却液凭借优异的综合表现，成为首批获得英特尔认证的国际品牌本土供应产品。
英特尔向嘉实多授牌单相冷板液冷工质资格
据了解，从2025年4月项目立项到2026年6月成果发布，整个项目历时14个月，嘉实多联合本土合作伙伴奕信通搭建完整测试回路，以英特尔TTV热测试载体模拟真实芯片散热工况，完成了从实验室配方到系统级验证的全流程落地。
“PG 25不是随意设定的浓度，而是行业长期实践验证的最优平衡点。”嘉实多热管理流液技术经理范清骅在技术分享中解释，去离子水本身导热性能优异，但存在易滋生菌群、腐蚀金属的短板；丙二醇浓度越高，抑菌防腐蚀能力越强，但导热效率会随之下降。经过大量实测验证，25%丙二醇+75%去离子水的配比，能够在导热效率、抑菌性能、防腐蚀能力三者间实现最佳平衡，也是全球液冷行业的通用共识。
从测试结果来看，嘉实多PG 25 C的各项指标均显著优于行业基准：
- 在长达180天的加速老化测试中，液体全程清澈透明、无沉淀变色；
- 金属腐蚀测试中，紫铜、焊料、黄铜、钢、铸铁等多种材质的腐蚀速率全面优于ASTM D1384标准要求；
- 非金属兼容性测试中，EPDM密封圈的硬度、质量、体积及拉伸性能保持率均达到95%以上，有效规避了长期浸泡后密封件形变、离子析出引发的泄漏风险。
在会后专访中，嘉实多大中华区业务总监仇圆圆从客户资产安全的视角，进一步解读了工质可靠性的价值：“高密机房里，服务器占总投资的60%-70%，CPU、GPU又是核心价值部件。冷却液看似成本占比不高，却是系统里的潜在单点故障——一旦发生泄漏，可能直接损毁价值数百万美元的IT设备；如果出现结垢、菌群滋生，又会导致散热能力下降，最终拖累算力输出。”
受访嘉宾（从左到右）：
嘉实多热管理事业部全球市场营销总监宋婷
嘉实多大中华区业务总监仇圆圆
英特尔中国数据中心集团高级主任工程师周绍荣（David Zhou）
他表示，嘉实多在测试前就主动收集了市场主流非金属管路、密封件产品，提前完成兼容性验证，就是为了帮客户提前规避长期运行的隐性风险。“我们把测试温度设定在65℃，比常规服务器运行温度高出20℃左右，本质就是做加速老化实验，用严苛条件验证产品在全生命周期内的稳定性，给客户足够的信心。”
除了产品本身的技术性能，嘉实多更在行业内率先提出“端到端整合服务”的理念，试图打破液冷工质“卖产品”的传统模式。嘉实多热管理事业部全球市场营销总监宋婷在采访中表示：“嘉实多拥有127年的液体技术积累，我们不止步于润滑油品牌，而是要基于流体技术能力，向热管理解决方案服务商转型。”
据介绍，这套端到端服务覆盖液冷系统的全生命周期：装机阶段提供现场液体检测与注液服务；运行阶段提供定期实验室监测与在线故障处理；寿命末期还可提供全球范围的液体回收服务，帮助客户实现闭环管理。而本土生产基地的布局，则让嘉实多能够大幅缩短交付周期、降低物流成本，精准匹配本土客户对供应链本土化的诉求。
不止于工质：液冷生态的长期版图
本次工质验证成果的发布，只是英特尔液冷生态布局的一个阶段性节点。
周绍荣透露，液冷创新加速计划的验证范围不会止步于工质，后续将逐步扩展到冷板、快接头、CDU、分水器等冷板液冷全链路关键部件，持续完善整个生态的标准化体系。
针对行业普遍关注的冷板液冷与浸没式液冷技术路线之争，受访嘉宾也给出了理性判断。周绍荣表示，当前单相冷板液冷占据80%以上的市场份额，是当下规模化落地的主流方案；而浸没式液冷在更高算力密度、余热回收需求更强的场景具备优势，未来占比会逐步提升，但节奏取决于行业协同进度，尤其是存量机房改造的承重、运维等挑战。
与此同时，低沸点氟化液的环保争议也让单相浸没式技术成为更受关注的方向，英特尔也已开发出基于合成油的环保型单相浸没式液冷技术。
嘉实多同样采取了双线布局的策略。仇圆圆向半导体行业观察表示，在冷板式液冷领域，嘉实多PG 25 C已实现大规模批量部署；而在浸没式液冷方向，嘉实多的DC 15、DC 20等产品已在英国、澳大利亚及国内的数据中心开展POC试点，且同样获得了英特尔单相浸没生态的合作推荐。“冷板是正当时的技术，浸没式是静待花开的未来，我们会两条腿走路，跟着行业需求同步迭代。”
从更宏观的产业视角看，本次英特尔牵头的工质验证，不仅是补齐了一块产品标准短板，更在推动本土液冷供应链从“零散制造”走向“体系化认证”，帮助本土厂商获得全球市场的权威背书。
对于客户而言，统一的认证标准大幅降低了选型成本与试错风险，让液冷部署有了清晰的品质参照；对于整个行业而言，中立的第三方验证体系，将逐步终结工质市场标准碎片化的局面，推动液冷产业从快速扩张走向高质量规范化发展。
夯实算力底座，推动绿色AI向前一步
当AI算力的散热需求撞上绿色低碳的政策要求，液冷已经成为数据中心基础设施升级的必答题。而液冷的规模化普及，从来不是单一厂商能够独立完成的命题，它需要芯片厂商、工质企业、系统集成商、终端客户的全链路协同。
本次英特尔冷板液冷工质验证的发布，正是产业协同的典型样本：英特尔以技术积累与行业公信力搭建标准框架，嘉实多、英维克等企业以技术沉淀与本土产能落地产品，双方共同为行业输出了一套可复用、可信赖的工质品质标尺。
随着液冷生态的持续扩容与标准体系的不断完善，AI算力的散热底座将愈发坚实，整个数据中心产业也将向着更高效、更可靠、更绿色的方向稳步前行。返回搜狐，查看更多