英特尔联合英维克、嘉实多发布单相冷板液冷工质测试验证成果

Intel, Envicool and Castrol certify single-phase cold plate liquid cooling fluids after 225-day, 9,000-data-point validation in Shanghai
聚合·英维克T22026-06-25 · CN · 英维克 Envicool (002837.SZ)
新品技术发布数据中心/IT散热政策法规/标准
▾ 1 条同事件报道

情报详报

What happened On June 24, 2026, Intel held a single-phase cold plate liquid cooling fluid qualification validation and ecosystem launch event in Shanghai, jointly announcing validation results with Envicool (Shenzhen Envicool Technology) and Castrol. Intel awarded single-phase cold plate liquid cooling fluid qualification plaques to both Envicool and Castrol. The validation was conducted under real data center operating conditions and under more stringent conditions than typical deployment, covering 30 batches of fluid sampling and more than 9,000 data points. Intel commissioned an authoritative third-party institution to carry out independent testing, with Intel itself making the unified determination of whether each test indicator fell within the qualified range. Qualification criteria included: corrosion inhibitor retention rate above 80% of the initial value; cold plate thermal performance deviation below 5%; and metal corrosion rates below 0.22 mils per year (thousandths of an inch per year). Three fluids passed all criteria, with several key data points significantly better than required. Envicool's SK-P25-C and SK-WT-C completed 225 days of fluid testing using two independent secondary-side real circulation loops in parallel. The liquid remained clear and transparent throughout; pH, ion concentration, metal element content and total bacterial count stayed stable and qualified; cold plate thermal resistance stability was high with thermal performance deviation far below 5%; and compatibility tests on EPDM seals, hoses and corrugated tubes all passed. Castrol PG 25 C completed validation over more than seven months. Sampling during that period showed the fluid remained clear and colorless throughout; metal corrosion rates for multiple metals were better than industry reference requirements; and EPDM mechanical property retention reached above 95%, confirming material compatibility and long-term stability. Intel Data Center Group Vice President and China General Manager Chen Baoli said Intel is closely following green computing development and pooling an open industry ecosystem, and that leading the validation both advances standardization of data center liquid cooling technology and helps cloud service providers and data center operators select single-phase cold plate fluids. Han Ren, Envicool Vice President and General Manager of the Liquid Cooling Business Unit, said the industry has long lacked unified fluid evaluation standards, leaving reliability risks for large-scale liquid cooling deployment, and that the joint validation fills a gap in the standardized fluid evaluation system. Huang Jiantang, Global President of Castrol's Thermal Management Business Unit, said unified standards will simplify customer selection and unlock liquid cooling advantages. ### Key figures - Event date: June 24, 2026; location: Shanghai - 30 batches of liquid cooling fluid sampled and collected - More than 9,000 data points collected - Corrosion inhibitor retention rate criterion: above 80% of initial value - Cold plate thermal performance deviation criterion: below 5% - Metal corrosion rate criterion: below 0.22 thousandths of an inch per year (mils per year) - Envicool SK-P25-C and SK-WT-C: 225 days of testing on two independent secondary-side real circulation loops - Castrol PG 25 C: more than 7 months of validation - Castrol EPDM mechanical property retention: above 95% - Three fluids qualified in total ### Why it matters to ebm-papst This development is a market signal that the single-phase cold plate liquid cooling ecosystem in China is moving toward standardized fluid qualification, with Intel acting as the convening authority and Envicool and Castrol as the first qualified fluid suppliers. For ebm-papst, whose data center portfolio includes fans and air-moving components for liquid-cooled and hybrid cooling architectures, the emergence of a de facto fluid qualification benchmark could accelerate adoption of cold plate liquid cooling in Chinese AI data centers, expanding the addressable market for associated thermal management hardware. Assessment (inference): The more relevant competitive angle is that Envicool is strengthening its position as an integrated liquid cooling solution provider with Intel's endorsement, which could increase pressure on component suppliers that are not embedded in such ecosystem partnerships. Assessment (inference): ebm-papst is not named in this announcement and no direct competitive overlap in fluids is implied, since ebm-papst does not supply cooling fluids; the opportunity lies in aligning fan and air-management products with the cooling architectures that this standardization effort legitimizes. Assessment (inference): If Chinese cloud and data center operators adopt these validated fluids as a selection baseline, specification cycles may shorten and favor vendors already positioned inside the Intel-led ecosystem, so ebm-papst should monitor whether similar qualification frameworks extend to air-side and hybrid cooling components.

原文全文

原文 英文翻译
正文内容 评论(0) 2026年6月24日,上海——今日,英特尔在上海举办单相冷板液冷工质资格验证暨生态发布会,携手英维克、嘉实多发布单相冷板液冷工质验证成果。单相冷板液冷工质验证的完成,标志着液冷工质有了关键的品质标杆,让液冷算力中心的稳定运行有了更可靠的保障。 英特尔向英维克授牌单相冷板液冷工质资格 英特尔向嘉实多授牌单相冷板液冷工质资格 英特尔数据中心集团副总裁、中国区总经理陈葆立表示:“英特尔紧跟绿色算力发展,聚力开放产业生态。牵头开展单相冷板液冷工质验证,既能推动数据中心液冷技术的规范发展,又能切实帮助云服务商、数据中心运营商的单相冷板液冷工质选型,这亦是英特尔深耕数据中心的价值所在。” 基于严苛的真实场景验证,三款单相冷板液冷工质全面达标 单相冷板液冷工质的验证过程采用了真实数据中心的工况,且在更为严苛的条件下运行,累计完成30批次液冷工质的取样、采集了逾9000个数据点。最终由英特尔委托权威第三方机构开展独立检测,由英特尔统一判定各项检测指标是否处于合格区间。 本次验证设定严格的合格判据,包括缓蚀剂保留率须高于初始值的80%,冷板热性能偏差须低于5%,各类金属腐蚀速率须低于0.22 千分之一英寸/年。三款液冷工质不仅全部达标,多项关键数据更显著优于上述要求: 英维克 SK-P25-C与SK-WT-C:以两条独立二次侧真实循环回路并行完成225天的液冷工质测试。液体全程清澈透明;pH值、离子浓度、金属元素含量及菌落总数等化学指标持续稳定并合格;冷板热阻稳定性高,热性能偏差远低于5%;EPDM密封件及软管、波纹管等全部触液材质兼容性测试均顺利通过。 嘉实多PG 25 C:历时7个多月完成验证。7个多月测试期间的液冷工质取样显示被测液体全程清澈透明、无变色;金属腐蚀测试中,多种金属腐蚀速率全面优于行业参考要求;EPDM材质各项力学性能保持率均达95%以上,充分验证了其卓越的材料兼容性与长期稳定性。 新成果赋能本土客户,护航AI稳定运行 AI算力的爆发和绿色算力的发展,驱动数据中心加速转向液冷散热,液冷工质作为液冷循环系统的“血液”,制约着液冷算力中心的稳定运行。这也是英特尔、英维克、嘉实多启动本次单相冷板液冷工质联合验证的契机——对散热能力需求的提高、绿色算力的推进,均离不开经过严格测试验证的液冷工质。 在服务于本土客户的过程中,英特尔捕捉到了客户的痛点:本土缺乏统一通用的单相冷板液冷工质测试验证规范,企业部署高密度AI算力时,容易因液冷工质选型,产生系统运行的可靠性隐患。本次三方协同统一测试流程,共享标准化验证规范,推动了本土单相冷板液冷工质测试验证规范的落地应用,也帮助数据中心客户选择更领先的本土液冷方案,为数据中心可靠、高效、长效的运营筑牢基础。 英维克副总裁、液冷事业部总经理韩忍表示:“液冷工质是数据中心液冷系统稳定运行的核心根基,长期以来行业缺乏统一的工质评测标准,工质性能、兼容性、长效稳定性无统一判定依据,直接给数据中心液冷规模化部署埋下可靠性隐患。我相信,此次联合验证成果的落地,能够补齐液冷工质标准化评测体系的空白,以统一业界规范和最佳实践筑牢工质长效可靠底线,让AI的规模化部署更加可靠和低碳。” 嘉实多热管理事业部全球总裁黄建棠表示:“我们很高兴与英特尔共同建立单相冷板液冷工质测试验证体系。统一标准将简化客户选型流程,充分释放液冷优势,以可靠的热管理产品支持绿色算力的发展。” 本文收录在 #快讯 - 热门文章 - 换一波 - 好物推荐 - 换一波 - 关注我们 - 微博:快科技官方快科技官方微博 - 今日头条:快科技带来硬件软件、手机数码最快资讯! - 抖音:kkjcn科技快讯、手机开箱、产品体验、应用推荐...