# Daikin Applied launches 60 MW D60-W cooling architecture for NVIDIA-based AI factories, CDUs due H2 2027

- Source: News · Daikin (T2)
- Published: 2026-11-12
- Score: 67.6
- Tags: Product launch, Datacenter, HVAC
- Companies: Daikin, NVIDIA
- Original: https://refindustry.com/news/daikin-applied-introduces-60-mw-cooling-architecture-for-ai-factories/

## Intelligence brief

### What happened Daikin Applied has introduced the D60-W Water-Cooled Chillers with Dry Coolers reference architecture, a 60 MW cooling design aimed at AI factories built on the NVIDIA DSX AI Factory Platform with NVIDIA Vera Rubin NVL72. The announcement was dated 2026-11-12 in the aggregated feed; no venue or event was specified in the source text. The architecture integrates rack-level cooling, chillers, dry coolers and controls into a single system intended to support data center engineering and deployment. It uses two temperature loops: a high-temperature loop serving coolant distribution units (CDUs) and a low-temperature loop serving DDC Solutions S-Series rack containment units (RCUs). The RCUs capture residual rack heat and incorporate fire suppression and water-loop protection. The chiller core is Daikin Applied's Magnitude WME oil-free magnetic bearing centrifugal chiller line. In suitable climates dry coolers carry most of the annual cooling load, with chillers supporting the hottest periods. D60-W runs in three modes: dry cooling with compressors off, hybrid cooling using waterside economizers plus chillers, and full mechanical cooling. Dry coolers replace evaporative cooling towers, eliminating cooling-tower make-up water. Daikin Applied's iDCM supervisory system coordinates RCUs, CDUs, chillers and dry coolers, managing load sharing, equipment operating hours and mode transitions. RideThrough and RapidRestore chiller technologies address power disturbances and post-shutdown restart, alongside system-level redundancy, and capacity can be expanded by adding deployable units. Karim Shalash, director of Data Center Solutions at Daikin Applied, framed an AI factory as "a system of systems," saying D60-W gives engineering teams a framework for working through dependencies between rack-level decisions and plant operation. ### Key figures - 60 MW IT load supported by the reference architecture - Six deployable units make up the 60 MW design - 92% of load handled by liquid cooling; 8% by air cooling - Chiller capacity up to 10 MW per unit (approximately 2,843 refrigeration tons) - Two temperature loops (high-temperature for CDUs, low-temperature for RCUs) - Three operating modes (dry, hybrid, full mechanical cooling) - Daikin Applied CDU and data center dry cooler still under development; availability targeted for the second half of 2027 ### Why it matters to ebm-papst This is a direct competitive signal in the AI data center cooling chain: a major HVAC incumbent is packaging chillers, CDUs, dry coolers and supervisory controls into a single reference architecture co-designed around NVIDIA's DSX platform and Vera Rubin NVL72 racks. Standardized, vendor-blessed architectures tend to shorten component shortlists, so fan and air-movement content inside dry coolers, CDUs and RCUs may increasingly be specified at the architecture level rather than by the data center operator. The 8% air-cooled share is small in load terms but still represents meaningful fan content across six deployable units, and the dry-cooler-centric design (replacing evaporative towers) shifts the fan duty profile toward large air-cooled heat rejection with variable outdoor conditions and three-mode operation. That favors fans with wide modulation range, low noise and high efficiency at part load. Assessment (inference): ebm-papst should treat the H2 2027 availability target for Daikin Applied's CDU and data center dry cooler as the practical window to be designed into this ecosystem, since component selection for those still-under-development products is likely being locked now. Assessment (inference): the NVIDIA DSX/Vera Rubin anchor makes this architecture a potential template for other AI factory builds, so early engagement with Daikin Applied and with NVIDIA-aligned data center integrators could yield design-win leverage beyond a single project. Assessment (inference): the oil-free chiller and dry-cooler emphasis also signals a market preference for water-lean cooling, which raises the strategic value of high-efficiency axial and centrifugal fan platforms for heat rejection rather than tower-based evaporative solutions.

## Full text (original)

Daikin Applied has introduced its D60-W Water-Cooled Chillers with Dry Coolers reference architecture, a 60 MW cooling design for AI factories based on the NVIDIA DSX AI Factory Platform with NVIDIA Vera Rubin NVL72. The architecture integrates rack-level cooling, chillers, dry coolers and controls into a single system to support data center engineering and deployment.
D60-W supports a 60 MW IT load across six deployable units, with liquid cooling handling 92% of the load and air cooling the remaining 8%. The design uses two temperature loops: a high-temperature loop serving coolant distribution units (CDUs) and a low-temperature loop serving DDC Solutions S-Series rack containment units (RCUs). The RCUs capture residual rack heat and incorporate fire suppression and water-loop protection.
The architecture incorporates Daikin Applied Magnitude WME oil-free magnetic bearing centrifugal chillers with capacities up to 10 MW (approximately 2,843 refrigeration tons). In suitable climates, dry coolers handle most of the annual cooling load, while chillers provide support during the hottest periods. Oil-free operation eliminates oil heaters, pumps and standard oil servicing requirements, as well as oil-related startup delays.
D60-W operates in three modes depending on outdoor conditions: dry cooling with compressors off, hybrid cooling using waterside economizers and chillers, and full mechanical cooling. Dry coolers replace evaporative cooling towers, eliminating cooling-tower make-up water. Daikin Applied’s iDCM supervisory system coordinates RCUs, CDUs, chillers and dry coolers, managing load sharing, equipment operating hours and transitions between operating modes.
The design includes RideThrough and RapidRestore chiller technologies for managing power disturbances and restarting after shutdown, alongside system-level redundancy. Capacity can be expanded by adding deployable units. Daikin Applied’s CDU and data center dry cooler remain under development, with availability targeted for the second half of 2027.
“An AI factory is a system of systems,” said Karim Shalash, director of Data Center Solutions at Daikin Applied. “A cooling decision at the rack carries implications for water temperatures, flow requirements, plant operation and heat rejection. D60-W gives engineering teams a framework for working through those dependencies and developing a cooling architecture around the facility’s operating requirements.”