What happened Hiwave, a Chinese data center infrastructure and digital energy solutions provider, published a technical position paper on 12 November 2026 outlining its "AIDC system collaborative solution" for AI data centers. The solution combines high-voltage power supply architecture with liquid cooling and is built around what Hiwave calls an "electricity x cooling x compute" (power-cooling-IT load) full-chain coordination concept. The paper argues that AI data centers are shifting from kilowatt to megawatt scale, with GPU loads that are high-frequency and highly dynamic, and that traditional data centers design and control power, cooling and IT equipment as largely independent systems. Hiwave proposes moving from device-level integration to system-level coordination across three areas: 1. System coordination — co-designing the power path for IT and cooling loads to cut conversion stages and distribution complexity; co-designing liquid-cooling CDUs, primary/secondary piping and the power system; and adding IT load sensing so electrical-side load changes are fed forward to the cooling control system. Air-liquid same-source and prefabricated skid/pod designs are cited as the engineering route to modular, scalable deployment. 2. Reliability reconstruction — a layered thermal buffer architecture: secondary-side micro-buffering for 0–30 second load fluctuations and primary-side large cold storage for 30–120 seconds, combined with load-aware feed-forward control (using PDU and other electrical-side devices to sense IT load) and dynamic following via high-speed control valves, variable-frequency pumps and predictive control algorithms on CDU, rack-side liquid loops and cold source systems. 3. Energy efficiency and sustainability — moving beyond a single PUE metric toward system-level efficiency across power transmission, multi-source cooling and full-lifecycle operation, including TCO and modular expansion flexibility. Hiwave positions the offering as a full-lifecycle capability spanning design, equipment development, system integration, project delivery and long-term O&M. No customer deployments, product model numbers, prices or delivery dates are disclosed in the text. ### Key figures - Load fluctuation buffering windows: secondary-side micro-buffer 0–30 seconds; primary-side large cold storage 30–120 seconds. - Scale framing: AI data centers moving from kilowatt-class to megawatt-class. - No specific figures disclosed for investment, revenue, production capacity, market share, efficiency percentages, PUE values, customer counts or timelines. ### Why it matters to ebm-papst This is a market signal that Chinese AIDC infrastructure vendors are pushing integrated power-plus-liquid-cooling architectures in which air movement is increasingly treated as one element of a coordinated thermal system rather than a standalone component. Hiwave explicitly references "air-liquid same-source" design and multi-source cooling, which keeps air-side heat rejection in scope alongside liquid cooling — relevant to ebm-papst's fan and motor portfolio for CDUs, air handling, dry coolers and hybrid cooling plants. Assessment (inference): Hiwave is not a direct competitor to ebm-papst; it is a potential channel and specification influencer. If Hiwave's prefabricated, modular AIDC pods gain traction, fan and motor selection will increasingly be driven by system-level requirements — load-following speed, communication with CDU and power controllers, and part-load efficiency — rather than by unit-level airflow specs. ebm-papst should engage early at the architecture/specification stage with Chinese AIDC integrators of this type, and ensure its EC fan and motor controls can expose load and status data compatible with feed-forward, predictive cooling control schemes. Assessment (inference): The emphasis on 0–30 second and 30–120 second buffering implies that fan and pump response dynamics become a differentiating factor in system reliability claims; suppliers able to document fast, deterministic response and wide modulation ranges may find an advantage. Conversely, if liquid cooling displaces air-side capacity in high-density halls, the addressable fan content per megawatt could shift — a risk worth monitoring in ebm-papst's data center segment planning. Assessment (inference): The absence of any disclosed deployments or figures means this should be treated as a positioning/technology-direction signal, not evidence of near-term volume. Recommend tracking Hiwave's project announcements and whether its "electricity x cooling x compute" architecture is adopted in reference sites before adjusting forecasts.
原文全文
原文
英文翻译
当人工智能加速重塑全球产业格局,算力已成为驱动数字经济发展的核心生产力。伴随大模型训练、智能推理及AI应用规模化发展,智算中心正从千瓦级迈向兆瓦级,高功率密度、高动态负载与高可靠运行,正在重新定义数据中心基础设施建设标准。
算力规模的跃升,不仅带来计算能力的突破,也对能源供给与热管理体系提出了更高要求。
一方面,GPU负载呈现高频、动态变化特征,对供电系统的响应速度与稳定性提出挑战;另一方面,高密度算力持续释放热量,传统相对独立的供电与制冷架构,难以充分适应电力与热负荷快速变化的需求。
算力的持续增长,正在推动数据中心从单一设备升级走向供电、制冷与算力的系统性重构。
面向AI时代基础设施变革,海悟立足液冷技术与数字能源系统工程能力,以高压供电与液冷融合为切入点,推动供电、制冷、IT负载深度协同,构建以系统协同为基础、可靠性重构为核心、高能效与可持续为目标的AIDC系统协同解决方案。
从能源供给到热管理,从动态响应到长期运营,重塑高密度算力基础设施的运行逻辑,让每一份算力都被可靠承载、高效释放。
一、从单点建设到系统重构,迎接兆瓦级算力挑战
AI算力的发展,正在打破传统数据中心基础设施的建设与运行边界。
传统数据中心中,供电、制冷与IT设备往往按照相对独立的系统进行设计与控制。随着高压供电架构与液冷技术加速融合,GPU负载快速波动、液冷系统动态响应以及供电系统稳定性之间的关联日益紧密。
当IT负载发生变化,功率需求随之波动,芯片热负荷也同步变化。如果供电、制冷系统缺乏有效联动,容易出现冷量供给与实际热负荷不匹配,影响系统运行效率与温控稳定性。
与此同时,单纯依靠提高供电电压或增加制冷设备容量,已难以充分解决兆瓦级算力基础设施的综合能效与可靠性问题。
未来AIDC建设需要的不只是更强的供电能力、更大的制冷容量,而是让能源供给、热量管理与算力负载形成协同响应机制。
海悟以「电×冷×算」全链路协同为核心,推动供电架构、液冷系统与IT负载从独立运行走向系统联动,实现基础设施从设备集成向系统协同的升级。
二、三大核心突破,重构AIDC系统协同能力
01 系统协同:从设备独立到电×冷×算全链联动
高密度算力时代,供电、制冷与IT负载不再是相互独立的系统,而是影响数据中心整体运行效率与可靠性的关键环节。
海悟围绕高压供电与液冷融合趋势,构建「电×冷×算」全链路协同架构,将供电系统、制冷系统与IT负载纳入统一的系统设计与协同控制体系,并结合风液同源及预制化方舱,推动技术架构向工程化、模块化和规模化落地。
供电侧:优化能源供给架构。
围绕高压供电发展趋势,推动IT负载与制冷系统供电架构协同设计,优化供电路径与系统配置,减少不必要的电能转换环节,降低配电复杂度与转换损耗。
制冷侧:推动电力与冷却系统深度融合。
将液冷CDU、一次侧及二次侧管路与供电系统进行协同设计,使制冷设备运行状态与电力系统需求相互匹配,提升系统集成度与整体运行协调性。
负载侧:建立算力负载感知机制。
针对GPU负载高动态变化特征,建立IT负载感知与系统联动控制机制,将电气侧负载变化及时传递至制冷控制系统,为冷量调节提供前馈信息,实现供电、制冷与算力需求的动态协同。
从能源输入到热量输出,从设备控制到系统联动,推动AIDC基础设施由单系统优化走向全链路协同。
核心价值:打通供电、制冷与IT负载之间的系统边界,提升基础设施整体协调能力,为兆瓦级算力部署提供系统级支撑。
02 可靠性重构:从被动保障到主动预测控制
AI算力负载具有高频波动、高动态变化等特征,芯片功率变化与热负荷变化相互关联,对制冷系统的响应速度提出更高要求。
传统温控系统主要依赖温度反馈进行调节,容易受到传感、控制及设备执行环节的响应延迟影响。当负载快速变化时,单纯依靠温度变化触发制冷调节,可能无法及时匹配瞬态热负荷。
海悟推动可靠性保障从传统被动响应向负载感知、分层缓冲与主动预测控制升级,构建多层次动态热管理机制。
分层缓冲:构建多级热惯性防护体系。
针对不同时间尺度的负载波动,构建二次侧微缓冲与一次侧大蓄冷的分层缓冲架构。
二次侧微缓冲(0—30秒)用于应对短时负载波动,一次侧大蓄冷(30—120秒)用于提供更大时间尺度的冷量缓冲。通过多级缓冲协同,增强制冷系统对负载突变的适应能力,提升系统抗冲击能力。
智能预判:让冷量调节先于热负荷变化。
通过PDU等电气侧设备感知IT负载变化,实时获取功率波动信息,并将负载变化趋势传递至制冷控制系统。
相较于单纯依靠温度反馈的传统控制方式,基于负载信息的前馈控制能够提前识别潜在热负荷变化,驱动制冷系统预先调整,实现从热量产生后的被动调节向负载变化驱动的主动响应转变。
动态跟随:实现冷量供给与算力需求精准匹配。
围绕CDU、机柜侧液冷回路及冷源系统,采用高速调节阀、变频泵与预测控制算法,推动冷量供给随IT负载变化动态调整。
通过全链路协同控制,减少冷量供给与实际热负荷之间的响应偏差,提升系统温控稳定性与运行效率。
核心价值:以分层缓冲提升系统韧性,以负载感知实现提前响应,以动态控制保障温控稳定,让可靠性从被动保障走向主动管理。
03 高能效与可持续:从单一PUE到系统综合能效
随着算力规模持续扩大,数据中心的能源消耗与资源利用效率成为产业可持续发展的重要议题。
高能效不再只是单一设备效率的提升,也不应局限于PUE指标的优化,而是需要从供电架构、制冷系统到长期运营进行系统性考量。
海悟以供电与制冷协同优化为抓手,推动基础设施从单点节能走向系统综合能效提升。
供电更高效:优化能源传输路径。
通过高压供电架构与供电系统协同设计,优化电能传输路径与转换环节,降低不必要的转换损耗,提升整体供电效率。
制冷更高效:推动多冷源与液冷协同。
结合不同地域气候条件、算力负载与制冷需求,灵活配置液冷与多元冷源方案,通过负载感知和动态调节优化冷量供给,提升制冷系统全年运行能效。
运营更可持续:兼顾TCO与全生命周期价值。
通过系统协同、设备运行优化与智能控制,降低不必要的能源消耗,减少设备长期运行负担,优化运维复杂度与全生命周期运营成本(TCO)。
同时,结合模块化设计与系统集成能力,提升基础设施建设与后续扩展的灵活性,为数据中心长期演进提供支撑。
核心价值:以供电效率、制冷效率与运营效率协同提升,推动数据中心从单一能效优化迈向全生命周期综合价值提升。
三、从系统协同到全生命周期,构建可靠算力能源底座
AIDC基础设施的竞争,已经不再局限于单一产品或技术的性能,而是涵盖方案设计、设备研发、系统集成、工程交付与长期运维的综合能力。
海悟持续深耕液冷技术与数字能源领域,将供电、制冷与IT负载的协同理念贯穿系统设计与运行管理全过程。
在前端,通过供电与制冷协同设计,优化系统架构与设备配置;在中端,通过模块化预制与全栈集成,提升系统建设效率与工程交付质量;在后端,通过负载感知、动态控制与全生命周期服务,提升系统运行可靠性与能源利用效率。
以全链路制冷、全场景覆盖和全生命周期服务为支撑,推动基础设施从单点设备交付向系统级解决方案升级。
从能源供给到热管理,从动态响应到长期运维,海悟以系统工程能力构建面向未来的算力基础设施保障体系。
四、算力与能源共生,赋能绿色数字经济发展
算力是数字经济发展的核心驱动力,能源则是支撑算力持续增长的重要基础。
随着AI产业规模不断扩大,如何在释放算力价值的同时提升能源利用效率、降低基础设施运行负担,已经成为数字基础设施绿色发展的重要课题。
高压供电与液冷技术的融合,不仅是数据中心基础设施的技术升级,更是推动算力与能源协同发展的重要探索。
海悟以「电×冷×算」系统协同为基础,通过优化供电路径、强化液冷与风冷协同、建立负载感知与主动控制机制,推动能源供给与算力需求精准匹配。
从供电架构优化到制冷系统高效运行,从动态响应到全生命周期运营,持续探索更高效、更可靠、更可持续的基础设施建设模式。
让每一度电发挥更大价值,让每一份算力得到可靠承载,让数字基础设施建设与绿色低碳发展协同前行。
五、算驭AI,破界而生,共筑智能时代新底座
AI竞争的本质,正在从算法与数据,延伸至算力与基础设施能力的比拼。
当智算中心迈向兆瓦级高密时代,供电、制冷与算力之间的协同能力,将成为决定基础设施效率、可靠性与可持续运营水平的重要因素。
面向未来,海悟将持续深耕高压供电、液冷技术与数字能源领域,以技术创新驱动产品升级,以系统协同重构基础设施能力,以全生命周期服务赋能产业发展。
算驭AI,破界而生。
海悟将携手产业生态伙伴,打破供电、制冷与算力之间的系统边界,推动能源与算力高效协同,为新一代数字基础设施建设注入持续动力,助力千行百业拥抱智能未来。
As artificial intelligence accelerates the reshaping of the global industrial landscape, computing power has become the core productivity driving the development of the digital economy. With the scaled development of large-model training, intelligent inference and AI applications, intelligent computing centers are moving from the kilowatt level to the megawatt level; high power density, highly dynamic loads and highly reliable operation are redefining the standards for data center infrastructure construction.
The leap in computing scale not only brings breakthroughs in computing capability, but also places higher demands on energy supply and thermal management systems.
On the one hand, GPU loads exhibit high-frequency, dynamic variation characteristics, posing challenges to the response speed and stability of power supply systems; on the other hand, high-density computing continuously releases heat, and the traditionally relatively independent power supply and cooling architectures struggle to fully adapt to the rapidly changing demands of power and thermal loads.
The continued growth of computing power is driving data centers from single-device upgrades toward a systemic reconstruction of power supply, cooling and computing.
Facing the infrastructure transformation of the AI era, Hiwave builds on its liquid cooling technology and digital energy system engineering capabilities, takes the integration of high-voltage power supply and liquid cooling as its entry point, promotes deep coordination of power supply, cooling and IT loads, and constructs an AIDC system collaborative solution based on system coordination, centered on reliability reconstruction, and aimed at high energy efficiency and sustainability.
From energy supply to thermal management, from dynamic response to long-term operation, it reshapes the operating logic of high-density computing infrastructure, so that every unit of computing power is reliably carried and efficiently released.
I. From single-point construction to system reconstruction, meeting the megawatt-scale computing challenge
The development of AI computing is breaking the construction and operation boundaries of traditional data center infrastructure.
In traditional data centers, power supply, cooling and IT equipment are often designed and controlled as relatively independent systems. As high-voltage power supply architectures and liquid cooling technology accelerate their integration, the links among rapid GPU load fluctuations, liquid cooling system dynamic response and power supply system stability are becoming increasingly close.
When IT loads change, power demand fluctuates accordingly, and chip thermal loads change in sync. If power supply and cooling systems lack effective linkage, it is easy for cooling supply to mismatch actual thermal load, affecting system operating efficiency and temperature control stability.
At the same time, simply raising supply voltage or increasing cooling equipment capacity can no longer fully solve the comprehensive energy efficiency and reliability problems of megawatt-scale computing infrastructure.
Future AIDC construction needs not only stronger power supply capability and larger cooling capacity, but also a coordinated response mechanism among energy supply, heat management and computing loads.
Hiwave takes "electricity x cooling x compute" full-chain coordination as its core, driving the power supply architecture, liquid cooling system and IT loads from independent operation toward system linkage, realizing the upgrade of infrastructure from device integration to system coordination.
II. Three core breakthroughs reconstructing AIDC system coordination capability
01 System coordination: from independent equipment to electricity x cooling x compute full-chain linkage
In the high-density computing era, power supply, cooling and IT loads are no longer mutually independent systems, but key links affecting the overall operating efficiency and reliability of data centers.
Centering on the trend of high-voltage power supply and liquid cooling integration, Hiwave builds an "electricity x cooling x compute" full-chain coordination architecture, bringing the power supply system, cooling system and IT loads into a unified system design and coordinated control system, and, combined with air-liquid same-source and prefabricated pods, drives the technical architecture toward engineering, modularization and scale implementation.
Power supply side: optimize the energy supply architecture.
Around the development trend of high-voltage power supply, promote the coordinated design of power supply architectures for IT loads and cooling systems, optimize the power supply path and system configuration, reduce unnecessary power conversion stages, and lower distribution complexity and conversion losses.
Cooling side: promote deep integration of power and cooling systems.
Conduct coordinated design of liquid cooling CDUs, primary-side and secondary-side piping and the power supply system, so that the operating status of cooling equipment and the needs of the power system match each other, improving system integration and overall operational coordination.
Load side: establish a computing load sensing mechanism.
Targeting the highly dynamic variation characteristics of GPU loads, establish an IT load sensing and system linkage control mechanism, transmit electrical-side load changes to the cooling control system in a timely manner, provide feed-forward information for cooling capacity adjustment, and achieve dynamic coordination of power supply, cooling and computing demand.
From energy input to heat output, from equipment control to system linkage, drive AIDC infrastructure from single-system optimization toward full-chain coordination.
Core value: break through the system boundaries among power supply, cooling and IT loads, improve the overall coordination capability of infrastructure, and provide system-level support for megawatt-scale computing deployment.
02 Reliability reconstruction: from passive assurance to active predictive control
AI computing loads have characteristics such as high-frequency fluctuation and high dynamic variation; chip power changes and thermal load changes are interrelated, placing higher demands on the response speed of cooling systems.
Traditional temperature control systems mainly rely on temperature feedback for regulation and are easily affected by response delays in sensing, control and equipment actuation. When loads change rapidly, triggering cooling adjustment solely on temperature change may fail to match transient thermal loads in time.
Hiwave drives reliability assurance from traditional passive response toward load sensing, layered buffering and active predictive control, building a multi-level dynamic thermal management mechanism.
Layered buffering: build a multi-level thermal inertia protection system.
Targeting load fluctuations at different time scales, build a layered buffer architecture of secondary-side micro-buffering and primary-side large cold storage.
Secondary-side micro-buffering (0–30 seconds) is used to cope with short-term load fluctuations, and primary-side large cold storage (30–120 seconds) is used to provide cooling capacity buffering at a larger time scale. Through multi-level buffer coordination, enhance the cooling system's adaptability to load surges and improve the system's impact resistance.
Intelligent prediction: let cooling capacity adjustment precede thermal load changes.
Sense IT load changes through electrical-side equipment such as PDUs, obtain power fluctuation information in real time, and transmit load change trends to the cooling control system.
Compared with traditional control methods that rely solely on temperature feedback, feed-forward control based on load information can identify potential thermal load changes in advance, drive the cooling system to adjust in advance, and realize the shift from passive adjustment after heat generation to active response driven by load changes.
Dynamic following: achieve precise matching of cooling supply and computing demand.
Around CDUs, rack-side liquid cooling loops and cold source systems, adopt high-speed control valves, variable-frequency pumps and predictive control algorithms to drive dynamic adjustment of cooling supply with IT load changes.
Through full-chain coordinated control, reduce the response deviation between cooling supply and actual thermal load, and improve temperature control stability and operating efficiency.
Core value: use layered buffering to improve system resilience, use load sensing to achieve advance response, and use dynamic control to ensure temperature control stability, so that reliability moves from passive assurance to active management.
03 High energy efficiency and sustainability: from single PUE to comprehensive system energy efficiency
As computing scale continues to expand, the energy consumption and resource utilization efficiency of data centers have become important issues for the sustainable development of the industry.
High energy efficiency is no longer just the improvement of single-device efficiency, nor should it be limited to the optimization of the PUE metric; rather, it requires systematic consideration from the power supply architecture and cooling system to long-term operation.
Hiwave takes the coordinated optimization of power supply and cooling as its lever, driving infrastructure from single-point energy saving toward comprehensive system energy efficiency improvement.
More efficient power supply: optimize the energy transmission path.
Through coordinated design of the high-voltage power supply architecture and the power supply system, optimize the power transmission path and conversion stages, reduce unnecessary conversion losses, and improve overall power supply efficiency.
More efficient cooling: promote coordination of multiple cold sources and liquid cooling.
Combined with climate conditions in different regions, computing loads and cooling needs, flexibly configure liquid cooling and multi-source cooling schemes, and optimize cooling supply through load sensing and dynamic adjustment, improving the cooling system's year-round operating energy efficiency.
More sustainable operation: balance TCO and full-lifecycle value.
Through system coordination, equipment operation optimization and intelligent control, reduce unnecessary energy consumption, reduce the long-term operating burden of equipment, and optimize O&M complexity and total cost of ownership (TCO).
At the same time, combined with modular design and system integration capabilities, improve the flexibility of infrastructure construction and subsequent expansion, providing support for the long-term evolution of data centers.
Core value: through the coordinated improvement of power supply efficiency, cooling efficiency and operational efficiency, drive data centers from single energy efficiency optimization toward comprehensive full-lifecycle value improvement.
III. From system coordination to full lifecycle, building a reliable computing energy foundation
Competition in AIDC infrastructure is no longer limited to the performance of a single product or technology, but covers comprehensive capabilities including solution design, equipment R&D, system integration, engineering delivery and long-term O&M.
Hiwave continues to deepen its work in liquid cooling technology and digital energy, applying the coordination concept of power supply, cooling and IT loads throughout the entire process of system design and operation management.
At the front end, through coordinated design of power supply and cooling, optimize the system architecture and equipment configuration; in the middle, through modular prefabrication and full-stack integration, improve system construction efficiency and engineering delivery quality; at the back end, through load sensing, dynamic control and full-lifecycle services, improve system operation reliability and energy utilization efficiency.
Supported by full-chain cooling, full-scenario coverage and full-lifecycle services, drive infrastructure from single-point equipment delivery toward system-level solutions.
From energy supply to thermal management, from dynamic response to long-term O&M, Hiwave builds a future-oriented computing infrastructure assurance system with system engineering capabilities.
IV. Symbiosis of computing and energy, empowering green digital economy development
Computing power is the core driving force of digital economy development, and energy is the important foundation supporting the continued growth of computing power.
As the scale of the AI industry continues to expand, how to improve energy utilization efficiency and reduce the operating burden of infrastructure while releasing the value of computing power has become an important topic for the green development of digital infrastructure.
The integration of high-voltage power supply and liquid cooling technology is not only a technical upgrade of data center infrastructure, but also an important exploration to promote the coordinated development of computing power and energy.
Based on "electricity x cooling x compute" system coordination, Hiwave promotes precise matching of energy supply and computing demand by optimizing the power supply path, strengthening the coordination of liquid cooling and air cooling, and establishing load sensing and active control mechanisms.
From power supply architecture optimization to efficient operation of cooling systems, from dynamic response to full-lifecycle operation, it continues to explore more efficient, more reliable and more sustainable infrastructure construction models.
Let every kilowatt-hour of electricity deliver greater value, let every unit of computing power be reliably carried, and let digital infrastructure construction advance in step with green and low-carbon development.
V. Computing drives AI, born by breaking boundaries, jointly building a new foundation for the intelligent era
The essence of AI competition is extending from algorithms and data to computing power and infrastructure capabilities.
As intelligent computing centers move into the megawatt-level high-density era, the coordination capability among power supply, cooling and computing will become an important factor determining the efficiency, reliability and sustainable operation level of infrastructure.
Looking to the future, Hiwave will continue to deepen its work in high-voltage power supply, liquid cooling technology and digital energy, drive product upgrades with technological innovation, reconstruct infrastructure capabilities with system coordination, and empower industry development with full-lifecycle services.
Computing drives AI, born by breaking boundaries.
Hiwave will join hands with industry ecosystem partners to break the system boundaries among power supply, cooling and computing, promote efficient coordination of energy and computing, inject sustained momentum into the construction of a new generation of digital infrastructure, and help thousands of industries embrace an intelligent future.