# Haiwu Tech publishes full technical breakdown of cold plate, immersion and spray liquid cooling for high-density AI servers

- Source: Hiwave News (T1)
- Published: 2026-11-03
- Score: 23.0
- Tags: Datacenter, Product launch
- Original: https://www.haiwu.com/news/dynamic/2184.html

## Intelligence brief

### What happened Haiwu Technology (Shenzhen-based data center cooling and thermal management equipment supplier) published a technical explainer on 2026-11-03 covering liquid cooling for server thermal management. The article is an educational/technical piece rather than a product or contract announcement: it explains why data center cooling is shifting from air to liquid as AI, large-model training and HPC push rack power density upward, then compares the three mainstream liquid cooling routes — cold plate, immersion (single-phase and two-phase) and spray cooling — across heat-transfer principle, system architecture, construction cost and O&M model. It further details the composition of a cold-plate liquid cooling loop (cold plates, CDU, manifold, hoses and quick disconnects, cold source, monitoring platform), the key engineering hurdles (leak risk, higher initial capex, O&M skills, retrofit of existing halls, interface/standard compatibility, coolant management), the drivers in AI data centers (high-density clusters, hybrid air-liquid architectures, waste heat recovery, edge computing), and a five-step implementation path from power/thermal assessment through design, equipment selection, monitoring/safety systems, commissioning and O&M handover. No customer, order, capacity or revenue figures are disclosed. ### Key figures - Traditional rack power density: typically about 5 kW to 10 kW per rack under air cooling. - High-density evolution: rack density moving from the 10 kW class toward 30 kW, 50 kW or even above 80 kW. - Air properties cited: specific heat capacity at constant pressure ~1.005 kJ/(kg·K), density ~1.2 kg/m³. - Water properties cited: specific heat capacity ~4.18 kJ/(kg·K), density ~1000 kg/m³; water's heat capacity per unit mass is about 4x that of air. - 700 W chip example: air cooling with 15 °C air temperature rise theoretically needs ~0.046 kg/s air mass flow, about 38 L/s volumetric flow; water cooling with 10 °C water temperature rise theoretically needs only ~1 L/min water flow. - TCO example: 15 MW IT load, air-cooled PUE 1.45 vs liquid-cooled PUE 1.15; total facility power ~21.75 MW vs ~17.25 MW, a 4.5 MW difference; at 8,760 h/year and an average electricity price of 0.6 CNY/kWh, theoretical annual electricity cost difference ~CNY 23.65 million (stated as an assumption-based estimate). - No specific figures disclosed on Haiwu's own revenue, order intake, production capacity or market share. ### Why it matters to ebm-papst This is a market-signal document rather than a competitive product launch: a Chinese thermal-management vendor is publicly framing liquid cooling as the default path for AI/high-density racks, with rack densities cited at 30–80 kW and above. For ebm-papst, the relevant read-across is to fan and air-movement demand. Cold-plate systems are explicitly described as hybrid air-liquid architectures in which memory, PSUs, storage and other components still rely on air cooling, and the article stresses that fans alone cannot fix local hot spots at very high density — implying continued but re-scoped fan content per rack (fewer server fans, more CDU/cold-source-side air movement, dry coolers, cooling towers and air-liquid hybrid units). Immersion and spray routes are presented as reducing or eliminating chassis fans, which is a longer-term substitution risk for server-level fan content. Assessment (inference): the most immediate opportunity for ebm-papst is on the infrastructure side of liquid cooling — CDU heat rejection, dry coolers, cooling towers and hybrid air-liquid halls — where fan and EC motor content per MW may hold up or grow even as per-server fan counts fall. Assessment (inference): Haiwu is positioning itself as a system-level liquid cooling integrator; if it scales in Chinese AI data center projects, it becomes a channel partner or competitor for air-movement components depending on whether it sources fans externally. Assessment (inference): the article's emphasis on standard interfaces, quick-disconnect reliability and O&M capability suggests procurement will increasingly be judged on system compatibility and lifecycle cost, favoring suppliers who can document interoperability and service support rather than unit price alone. Assessment (inference): no evidence in the text indicates Haiwu is entering fan manufacturing, so the near-term threat to ebm-papst's core business appears limited, but the shift toward liquid-first designs in China's AI buildout warrants monitoring of fan content per rack and per MW.

## Full text (English translation)

With the rapid development of artificial intelligence, large-model training and high-performance computing, data center servers are continuously evolving toward high power and high density. Traditional air cooling is gradually facing challenges in heat dissipation capability, space layout and energy efficiency, and liquid cooling technology has moved from being an auxiliary cooling option in the past to gradually becoming an important technical direction for high-density computing infrastructure.

From cold plate liquid cooling to immersion liquid cooling and further to spray liquid cooling, different technical routes differ markedly in heat dissipation principles, system architecture, construction cost and O&M models. How to select a suitable liquid cooling solution based on server power, rack density, room conditions and long-term operating requirements has become a key issue to be considered in data center construction and retrofit.

This article analyzes the working principles of server liquid cooling technology, the three mainstream technical routes, system construction difficulties, application scenarios and engineering implementation paths, to help readers fully understand liquid cooling technology and its application value in next-generation data centers.

I. Why is server cooling starting to move from air to liquid?
1. AI computing growth drives continuous rise in server power density
In traditional data centers, the power consumption of CPUs, memory and storage devices is relatively controllable, with single-rack power typically around 5 kW to 10 kW, and room precision air conditioners plus server internal fans can meet most cooling needs.
With the large-scale deployment of GPU servers, AI accelerator cards and high-performance computing equipment, server power consumption has grown significantly.
A high-performance AI server may be equipped with multiple GPUs or other AI acceleration chips, with total system power reaching several kilowatts. With concentrated deployment of high-density servers, single-rack power density is gradually developing from the traditional 10 kW class toward 30 kW, 50 kW or even above 80 kW.
The concentrated operation of high-power equipment not only increases the heat load inside the rack, but also places higher demands on room supply/return air organization, air conditioning cooling capacity and the power supply system.
When the heat generated per unit space exceeds the effective heat dissipation capability of the air cooling system, even continuously increasing fan speed and supply air volume cannot fundamentally solve local hot spots and uneven heat dissipation.
Therefore, finding a more efficient heat transfer method has become an important topic in building high-density computing infrastructure.
2. The physical properties of air and liquid determine the difference in heat dissipation capability
An important reason liquid cooling technology has attracted attention is the obvious difference between air and liquid in heat transfer capability.
The specific heat capacity at constant pressure of air is about 1.005 kJ/(kg·K), and its density is about 1.2 kg/m³; the specific heat capacity of water is about 4.18 kJ/(kg·K), and its density is about 1000 kg/m³.
Under the same mass conditions, the heat capacity of water is about 4 times that of air. Considering the density difference between water and air, the same volume of water can carry more heat.
Taking a 700 W chip as an example:
If air cooling is used, assuming an air temperature rise of 15 °C, a theoretical air mass flow of about 0.046 kg/s is required, corresponding to a volumetric flow of about 38 L/s.
If water cooling is used, assuming a cooling water temperature rise of 10 °C, a theoretical water flow of only about 1 L/min is needed to remove the same heat.
This means liquid can carry a larger heat load with a smaller volumetric flow, which helps improve the heat dissipation efficiency of high-power chips.
Of course, actual systems also need to comprehensively consider heat exchange area, flow channel design, fluid resistance, heat exchange temperature difference and equipment operating conditions, and the final heat dissipation capability cannot be judged solely by the specific heat capacity of the medium.
3. Energy efficiency and green development requirements drive liquid cooling application
Data center energy consumption continues to grow, and energy utilization efficiency has become an important indicator for measuring the construction and operation level of data centers.
PUE (Power Usage Effectiveness) is a commonly used energy efficiency evaluation indicator for data centers; the closer its value is to 1, the lower the proportion of energy consumption of auxiliary facilities other than IT equipment.
Traditional air-cooled data centers need to continuously remove heat generated by servers through air conditioning systems, fans and cold source equipment. In high-density deployment scenarios, problems such as air delivery distance, duct resistance and local hot spots may further increase cooling energy consumption.
Liquid cooling technology can directly remove most of the heat generated by servers through liquid, reducing dependence on large-airflow air circulation. In projects with suitable cooling water temperature and free cooling conditions, it can also be combined with cooling towers, dry coolers and other equipment to improve free cooling utilization and reduce mechanical refrigeration operating time.
Therefore, liquid cooling is not only a technical means to solve the heat dissipation problem of high-density servers, but also an important direction for data centers to optimize energy efficiency and reduce long-term operating costs.
It should be noted that liquid cooling does not mean all projects can achieve the same PUE level; the final energy efficiency performance still depends on climate conditions, cold source architecture, equipment selection, operating load and system control strategy.

II. What server liquid cooling technologies are there? Analysis of the three major routes: cold plate, immersion and spray
Liquid cooling is not a single technical solution, but a technical system composed of different heat dissipation principles and system architectures.
At present, server liquid cooling mainly includes three technical routes: cold plate liquid cooling, immersion liquid cooling and spray liquid cooling.
1. Cold plate liquid cooling: the currently more mature mainstream route
Cold plate liquid cooling is one of the liquid cooling technologies widely used in data centers today.
Its basic principle is to install liquid cooling cold plates on the surface of high-heat chips such as CPUs and GPUs; through flow channels designed inside the cold plate, coolant continuously flows and absorbs heat generated by the chip, then transfers the heat to an external cooling system.
The whole process forms a relatively complete cycle:
coolant enters the cold plate → absorbs chip heat → heated coolant flows out → enters the heat exchange system → recirculates after cooling.
Main advantages of cold plate liquid cooling:
First, strong retrofit adaptability.
Cold plate liquid cooling usually only requires liquid cooling retrofit of main heat-generating devices such as CPUs and GPUs, while some memory, power supplies, storage and other components in the server can still use air cooling.
Therefore, the overall server structure is relatively close to traditional equipment, and the original server architecture and room infrastructure can be reused to a certain extent.
Second, relatively high system maturity.
Key components such as cold plates, CDUs, manifolds, liquid cooling hoses and quick disconnects have formed a relatively complete industrial chain, which is conducive to project design, equipment procurement and large-scale deployment.
Third, wide application scenarios.
Whether for new AI data centers or high-density retrofit of existing data centers, cold plate liquid cooling has strong application adaptability.
Main limitations of cold plate liquid cooling:
Cold plates usually prioritize main heat-generating devices such as CPUs and GPUs, while other components such as memory, hard drives and power modules may still require air cooling assistance, so it is usually a hybrid air-liquid cooling architecture.
At the same time, the heat exchange capability of the cold plate is affected by factors such as flow channel structure, coolant flow, heat exchange area and contact thermal resistance. As chip power continues to increase, requirements for cold plate design, system flow and supply liquid temperature will also continue to rise.
Overall, cold plate liquid cooling balances heat dissipation performance, equipment compatibility and engineering implementation difficulty, and is a relatively mature choice for current AI servers and high-density data centers.
2. Immersion liquid cooling: achieving overall server immersion cooling
Immersion liquid cooling is to immerse servers or computing equipment entirely in insulating dielectric coolant, so that heat-generating components are in direct contact with the coolant, and heat is removed through liquid circulation or phase change.
Depending on whether the coolant undergoes phase change, immersion liquid cooling is mainly divided into single-phase immersion and two-phase immersion.
Single-phase immersion liquid cooling
In a single-phase immersion system, the coolant always remains liquid, absorbs server heat through pump circulation or natural convection, and then transfers heat to an external cooling system through a heat exchanger.
Its system structure is relatively simple, and the operation process does not involve coolant boiling and condensation, making it easy to establish a stable circulation control system.
Two-phase immersion liquid cooling
Two-phase immersion uses the phase change characteristics of the coolant for heat dissipation.
When the coolant contacts a high-temperature chip, it absorbs heat and boils and vaporizes; the generated vapor rises and enters the condensation area, releases heat and re-condenses into liquid, flowing back into the immersion tank.
Heat transfer is achieved through the phase change cycle between liquid and gas.
Two-phase immersion can use latent heat of phase change for efficient heat exchange, but the system has higher requirements for sealing, coolant management, pressure control and material compatibility.
Main advantages of immersion liquid cooling:
- Heat-generating devices can be in direct contact with the coolant, reducing the thermal resistance of traditional heat dissipation interfaces.
- It is conducive to overall server heat dissipation and reduces the need for fans inside the chassis.
- It has high heat load carrying potential and is suitable for high-density computing scenarios.
- It can reduce the noise generated by server fan operation.
Main challenges of immersion liquid cooling:
Servers need to meet material compatibility requirements in a coolant immersion environment; some traditional hard drives, connectors, power supplies and sealing materials may not be directly applicable.
At the same time, equipment maintenance methods also change significantly. Replacement of server components usually requires processes such as extraction, draining, cleaning and reinstallation, placing higher demands on O&M tools, personnel skills and on-site management.
Therefore, immersion liquid cooling is more suitable for new projects where the server ecosystem, coolant management and O&M system are fully considered at the planning stage.
3. Spray liquid cooling: directly delivering cooling medium to heat-generating devices
Spray liquid cooling is a technical route that delivers cooling medium directly to the surface of chips or other heat-generating components through nozzles to achieve rapid heat transfer.
Its core lies in using nozzle structure, droplet distribution and fluid control so that the cooling medium can cover the target heat-generating area, and completing recycling through a recovery system.
Compared with cold plate liquid cooling, spray liquid cooling can reduce the influence of some solid heat exchange interfaces; compared with immersion liquid cooling, its cooling medium does not need to completely fill the entire server immersion space.
Main advantages of spray liquid cooling:
- The cooling medium can act directly on heat-generating components.
- Spray flow and coverage area have some adjustment space.
- Under specific structures, high local heat exchange capability can be achieved.
- The amount of cooling medium and system structure can be optimized according to application requirements.
Main challenges of spray liquid cooling:
Nozzle arrangement, spray pressure, droplet size and coverage uniformity directly affect heat dissipation performance.
If nozzles become clogged, spray angles deviate or local liquid supply is insufficient, local hot spots may occur. In addition, coolant recovery, material compatibility, sealing design and long-term operational reliability also need to be fully verified.
At present, the engineering application maturity and scale of spray liquid cooling still need to be evaluated in combination with specific technical solutions, and it is more suitable for specific equipment and R&D verification scenarios.

III. How is a server liquid cooling system composed? Analysis of core equipment and workflow
Regardless of which liquid cooling technical route is adopted, a complete server liquid cooling system is not just cold plates or coolant, but is jointly composed of the heat source side, liquid circulation side, heat exchange side and control/O&M side.
Taking the currently widely used cold plate liquid cooling system as an example, its core components mainly include the following parts.
1. Liquid cooling cold plate: directly absorbs chip heat
The cold plate is the key component in a cold plate liquid cooling system that directly exchanges heat with server heat-generating devices.
Its interior is usually designed with microchannels, turbulence structures or other enhanced heat exchange structures to improve the efficiency of chip heat transfer to the coolant by optimizing fluid distribution and heat exchange area.
The design of the cold plate needs to comprehensively consider material thermal conductivity, flow channel structure, pressure drop, sealing performance and long-term reliability.
2. CDU: the core control and heat exchange unit of the liquid cooling system
CDU (Coolant Distribution Unit) is important equipment in the liquid cooling system, mainly undertaking functions such as coolant circulation, flow regulation, heat exchange and system monitoring.
A typical CDU transfers heat through a heat exchanger between the primary side and secondary side loops.
The primary side is usually connected to the data center cold source system and is responsible for providing cooling capacity; the secondary side is connected to the server liquid cooling loop and provides coolant meeting requirements for cold plates or other liquid cooling equipment.
Depending on deployment mode and system requirements, CDUs can adopt different architectures such as rack-level, frame-level or row-level.
Its main functions include:
- Coolant circulation and flow regulation.
- Heat exchange between primary and secondary sides.
- Supply/return liquid temperature and pressure monitoring.
- Pump variable frequency control and redundant operation.
- Water quality and operating status monitoring.
- Fault alarms and system linkage.
The configuration capability, redundancy design and control strategy of the CDU directly affect the operational stability of the liquid cooling system.
3. Manifold: realizing distribution and collection of liquid cooling loops
The manifold is a key component in the liquid cooling system responsible for coolant distribution and recovery.
It distributes coolant from the CDU to different servers or cold plate branches, and then collects the return liquid after absorbing heat into the return pipeline.
A reasonable manifold design can improve flow balance between different branches, reduce local flow insufficiency and improve system operational stability.
4. Liquid cooling hoses and quick disconnects: ensuring reliable circulation connections
Liquid cooling hoses are responsible for connecting the CDU, manifold and server cold plates to form a complete coolant circulation channel.
Quick disconnects are used for quick connection and disconnection between devices, facilitating server installation, maintenance and replacement.
In high-density data centers, pipeline design needs to focus on pressure resistance, sealing performance, fluid resistance, material compatibility and maintenance convenience.
For application scenarios requiring frequent plugging and unplugging, attention should be paid to the reliability of drip-free quick disconnects and their applicable working conditions.
5. Cold source system: continuously discharging server heat out of the room
After the liquid cooling system absorbs server heat, it still needs to discharge the heat into the environment through an external cold source system.
Common equipment includes chillers, cooling towers, dry coolers, plate heat exchangers, etc.
Under suitable climate conditions and supply liquid temperature requirements, free cooling technology can be fully utilized to reduce compressor operating time.
For air-liquid integrated data centers, it is also necessary to comprehensively consider the load distribution of the liquid cooling system and the air cooling system to achieve coordinated heat dissipation of different equipment and different areas.
6. Intelligent monitoring platform: realizing full-link operation management
The operation of the liquid cooling system involves multiple parameters such as temperature, flow, pressure, water quality and equipment status.
Through the intelligent monitoring platform, operating data of CDUs, pumps, valves, pipelines and servers can be collected in real time to achieve equipment status monitoring, abnormal warnings, fault location and operation strategy optimization.
When abnormal flow, temperature rise or liquid leakage occurs in the system, the monitoring platform can issue alarms in time and link relevant equipment according to preset strategies.
Thus, a complete liquid cooling management system is formed from chip heat dissipation, liquid circulation, cold source heat exchange to intelligent O&M.

IV. What key issues must be solved for liquid cooling system implementation?
The application value of liquid cooling technology has been gradually verified, but moving from technical solutions to large-scale deployment still requires solving problems in engineering design, equipment compatibility, operation management and long-term maintenance.
1. Leak risk: a focus of system safety design
The liquid cooling system involves coolant, pipelines, valves, connectors and heat exchange equipment. Seal failure at any connection point may affect the safety of servers and surrounding equipment.
Therefore, liquid cooling projects must establish a multi-level leak prevention system.
First, pipeline pressure and flow should be reasonably designed to reduce system operating risks.
Second, high-reliability quick disconnects meeting application requirements should be selected, with focus on seal life, plugging cycles and drip-free performance.
Third, leak detection devices should be installed at key locations such as the bottom of racks and pipeline connections to achieve real-time monitoring of abnormal conditions.
At the same time, the scope of abnormal impact can be limited through independent secondary-side closed loops, zoned valve control and fault isolation design.
It should be emphasized that leak detection is only one part of risk prevention and control; it also needs to be combined with pressure monitoring, equipment inspection, automatic alarms and emergency operating procedures to form a complete safety guarantee mechanism.
2. High initial investment: needs to be evaluated from a TCO perspective
Compared with traditional air cooling, liquid cooling usually requires additional equipment such as cold plates, CDUs, pipelines, quick disconnects and liquid cooling monitoring, and the initial construction cost may increase.
Under different technical routes, server configurations and room conditions, investment differences are large, and project costs cannot be simply judged by a fixed ratio.
Therefore, liquid cooling projects cannot only look at equipment procurement prices, but also need to comprehensively consider the total cost of ownership (TCO) over the full life cycle.
For example, a data center has an IT load of 15 MW, assuming the air cooling solution PUE is 1.45 and the liquid cooling solution PUE is 1.15.
With the IT load unchanged:
The total power of the air cooling system is about 21.75 MW.
The total power of the liquid cooling system is about 17.25 MW.
The total power difference between the two solutions is 4.5 MW.
Calculated at 8,760 hours per year and an average electricity price of 0.6 CNY/kWh, the theoretical annual electricity cost difference is about CNY 23.65 million.
It should be noted that this is a set of calculations based on assumptions, and not all projects can achieve the same energy-saving effect. Actual benefits also need to consider factors such as load rate, equipment operating efficiency, local electricity prices and cold source system energy consumption.
In addition, liquid cooling improves rack power density; in some projects with limited site space, it can also improve the computing power deployment capability per unit building area and reduce civil construction and space costs per unit of computing power.
3. O&M capability: moving from traditional HVAC management to electromechanical coordination
Liquid cooling systems require not only IT equipment O&M personnel, but also professional knowledge in water systems, fluid control, heat exchange equipment and automation control.
Traditional air cooling O&M mainly focuses on supply/return air temperature, air conditioning operating status and rack airflow organization.
Liquid cooling O&M requires further mastery of:
- Pump operating status and head control.
- Coolant flow and pressure balance.
- Supply/return liquid temperature and temperature difference management.
- Water quality, conductivity and pH monitoring.
- Pipeline sealing and material aging inspection.
- Leak detection and emergency isolation operations.
Therefore, liquid cooling data centers need to establish an O&M system combining electromechanical, HVAC, IT and automation control.
At the project delivery stage, equipment operation training, system start/stop training, fault simulation and emergency drills should be completed simultaneously to ensure the O&M team can independently handle common abnormalities.
4. Existing room retrofit: power supply, load bearing and space conditions need to be re-verified
For existing data centers, deploying liquid cooling not only involves cooling system retrofit, but may also affect the original infrastructure.
First, it is necessary to check the floor load bearing, equipment transport passages, rack dimensions and pipeline layout conditions of the room.
Second, the power supply and distribution capacity needs to be re-verified, including transformers, busbars, UPS and rack power distribution systems.
In addition, it is also necessary to evaluate the installation conditions of outdoor cooling towers, dry coolers and other cold source equipment, as well as the connection method of primary and secondary side pipelines.
For original air-cooled rooms, methods such as zoned retrofit, air-liquid integration or local liquid cooling can be adopted according to rack power density, equipment configuration and infrastructure conditions, to avoid unnecessary overall retrofit investment.
5. Equipment interfaces and standard compatibility: avoiding supply chain dependence
Liquid cooling systems involve multiple equipment links such as servers, cold plates, CDUs, manifolds, quick disconnects and pipelines.
If interface specifications, material standards and performance parameters between different manufacturers are incompatible, subsequent expansion, equipment replacement and maintenance efficiency may be affected.
Therefore, at the early stage of project construction, focus should be placed on clarifying:
- Server liquid cooling interfaces and connection methods.
- Interface specifications of CDU and manifold.
- Dimensions and sealing requirements of quick disconnects.
- Compatibility of coolant and pipeline materials.
- System pressure, flow and temperature parameters.
- Replacement and spare parts guarantee mechanisms in case of equipment failure.
Prioritizing equipment and system architectures with open interfaces and verified compatibility helps improve the flexibility of subsequent expansion.
6. Coolant management: focus on material compatibility and long-term stability
Different liquid cooling technologies have different requirements for cooling media.
Cold plate liquid cooling usually uses water-based coolant that has undergone water quality treatment; some systems add corrosion inhibitors and other additives according to material and operating condition requirements.
Immersion liquid cooling requires dielectric coolant with electrical insulation properties; common types include mineral oil, synthetic oil and some special dielectric liquids.
Different coolants differ in viscosity, thermal conductivity, chemical stability, material compatibility and environmental attributes.
When selecting, focus should be placed on verifying the compatibility of the coolant with metal materials, seals, cable sheaths and plastic parts.
At the same time, corresponding filtration, testing, replenishment and replacement systems should be established according to the coolant type, to avoid affecting long-term system operation due to changes in water quality or medium performance.

V. Why are AI data centers paying increasing attention to liquid cooling technology?
With the continuous upgrading of AI computing infrastructure, the application scenarios of liquid cooling technology are constantly expanding.
1. High-density AI clusters: driving liquid cooling to become an important cooling choice
AI servers usually integrate multiple high-power GPUs or AI acceleration chips, with high computing density and high heat flux density.
In high-density racks, traditional air cooling may face problems such as local hot spots, insufficient supply air capability and increased cooling energy consumption.
Liquid cooling can directly remove most of the heat generated by chips, reducing dependence on large-airflow air circulation and providing cooling guarantees for continuous operation of high-power servers.
Especially in high-density AI training clusters, technologies such as cold plate liquid cooling, air-liquid integration and high-performance CDUs are becoming important components of infrastructure design.
2. Air-liquid integration: balancing heat dissipation needs of different equipment
Not all server components need liquid cooling.
In actual data centers, high-heat chips such as CPUs and GPUs can prioritize cold plate liquid cooling, while memory, power supplies, storage and other auxiliary equipment use air cooling according to actual heat load.
This air-liquid integrated architecture can fully leverage liquid cooling capability while retaining the advantages of air cooling systems in equipment adaptation and auxiliary heat dissipation.
In high-density AI rooms, through coordinated operation of liquid cooling and air cooling, system adaptability can be further improved to meet the deployment needs of servers of different generations.
3. Waste heat recovery: expanding the energy utilization value of liquid cooling systems
Heat generated by traditional air-cooled data centers is usually discharged in a dispersed manner at relatively low temperatures, making recovery and utilization difficult.
Liquid cooling systems can centrally collect heat generated by servers through circulating liquid, creating conditions for waste heat utilization under suitable system design conditions.
For example, through plate heat exchangers and heat pump systems, heat recovered from data centers can be used for campus heating, domestic hot water or some industrial heat scenarios.
However, waste heat utilization is not an automatic additional function of liquid cooling systems; factors such as return water temperature, heat load stability, distance to heat users and seasonal variation also need to be considered.
Through reasonable design, liquid cooling systems can further extend from simple heat dissipation facilities to comprehensive energy utilization systems.
4. Edge computing: liquid cooling applications extending to more scenarios
In addition to large AI data centers, edge computing, industrial computing and high-performance specialized equipment also face cooling challenges.
Some edge nodes are deployed in outdoor rooms, industrial plants and remote areas, limited by space, ambient temperature and power supply conditions.
Liquid cooling technology can centrally transport heat inside equipment to external heat exchange equipment through circulating media, reducing dependence on large-scale air circulation inside the room.
As the power of edge computing equipment continues to increase, liquid cooling is expected to play a role in more high-heat-flux equipment and special application scenarios.

VI. How are server liquid cooling projects implemented? From preliminary assessment to engineering delivery
Liquid cooling projects involve multiple disciplines such as IT equipment, refrigeration systems, power supply and distribution, pipeline engineering and intelligent control, and it is recommended to proceed according to a systematic engineering process.
Step 1: Conduct room power consumption and heat dissipation capability assessment
Before project initiation, a comprehensive investigation of the existing room should be conducted.
Key points include:
- Statistics of actual power and peak power of each rack.
- Analysis of server equipment types and chip power.
- Measurement of rack inlet/outlet air temperature and local hot spots.
- Inspection of the cooling capacity of the existing air conditioning system.
- Verification of power supply and distribution capacity and room space conditions.
Through data analysis, clarify the areas, equipment and number of racks that need liquid cooling, avoiding blind expansion of the retrofit scope.
Step 2: Conduct liquid cooling solution design and technical verification
According to server power, rack density and project construction conditions, determine the suitable liquid cooling technical route.
For existing rooms, focus can be placed on evaluating cold plate liquid cooling and air-liquid integration solutions.
For new high-density computing centers, cold plate, immersion and other liquid cooling technologies can be evaluated in combination with business needs.
Before formal deployment, it is recommended to select representative servers and racks for pilot testing, focusing on verifying:
- Chip temperature under full load conditions.
- Coolant flow and pressure stability.
- CDU heat exchange capability and control accuracy.
- Leak detection and alarm response.
- System fault switching and redundancy capability.
- Convenience of equipment maintenance and component replacement.
The pilot should cover typical business loads and key fault conditions as much as possible to form reliable test data.
Step 3: Determine CDU, pipeline and core equipment configuration
After technical verification is completed, enter the engineering design stage.
CDU selection needs to focus on indicators such as heat exchange capability, flow range, pressure control, pump redundancy, temperature regulation and operation monitoring.
Equipment capacity should be calculated based on actual IT load, future expansion plans and system redundancy requirements, with reasonable design margins reserved.
The pipeline system needs to clarify supply/return pipe diameters, pressure levels, connection methods, valve configuration and exhaust/drain design.
At the same time, verified pipeline materials and quick disconnects should be prioritized to ensure reliable system connections and convenient maintenance.
Step 4: Build monitoring and safety guarantee systems
Liquid cooling systems need to establish a complete monitoring system and incorporate key operating parameters into a unified management platform.
Main monitoring contents include:
- Primary and secondary side supply/return liquid temperatures.
- System flow, pressure and pressure difference.
- Coolant level and water quality status.
- Operating status of pumps and valves.
- Leak detection and fault alarms.
- Operating status of CDU and cold source equipment.
At the same time, formulate handling processes corresponding to different fault levels, and clarify emergency operation requirements for liquid leakage, abnormal flow, increased supply liquid temperature and equipment failure.
Step 5: System commissioning, acceptance and O&M handover
After engineering construction is completed, pipeline flushing, pressure testing, system venting, flow balancing, equipment linkage and full-load testing should be carried out according to design requirements.
For key equipment, backup pump switching, fault isolation and abnormal alarm functions should also be verified.
After system acceptance is completed, establish equipment files, operating parameter baselines, maintenance plans and spare parts management systems.
At the same time, carry out systematic training for O&M personnel so that the liquid cooling system can smoothly transition from the construction delivery stage to the long-term operation stage.

VII. What details still need attention for long-term stable operation of liquid cooling systems?
Completion of project delivery does not mean the end of management work. During long-term operation, the following aspects also deserve attention.
1. Quick disconnect quality and maintenance management
Quick disconnects are frequently operated connection components in liquid cooling systems; focus should be placed on sealing structure, material performance, plugging life and drip-free capability. Regularly check connector status to avoid seal performance degradation due to long-term use.
2. Coolant water quality management
Water-based coolant needs to be monitored for conductivity, pH and other water quality indicators according to system requirements, with regular sampling analysis and filtration treatment to avoid corrosion, scaling and microbial growth.
3. Sealing material aging inspection
Pipeline sealing rings, gaskets and other elastic sealing materials may age with temperature, pressure and use time, and periodic inspection and replacement plans should be formulated according to manufacturer requirements.
4. Emergency plans and regular drills
Emergency plans should be formulated for situations such as liquid leakage, pump failure, pipeline blockage and abnormal supply liquid temperature, and simulation drills should be carried out regularly to improve fault handling efficiency.
5. System expansion capability reservation
As AI server power and computing scale continue to grow, liquid cooling systems need to consider future expansion needs. In the early design, CDU capacity, main pipeline flow, rack connection points and cold source equipment interfaces should be reasonably reserved to reduce later retrofit costs.

VIII. Conclusion: from single-point heat dissipation to system-level thermal management, liquid cooling drives data center upgrading
From cold plate liquid cooling to immersion liquid cooling and further to spray liquid cooling, different technical routes are providing more diverse cooling options for high-density servers.
Among them, cold plate liquid cooling has become an important application direction for current AI data centers due to good equipment compatibility and engineering adaptability; immersion liquid cooling shows application potential in overall immersion cooling and high-density computing scenarios; spray liquid cooling is also being continuously explored in specific technical fields.
In the future, as AI chip power continues to grow and rack power density continues to increase, data center cooling will no longer be limited to a single device or local refrigeration, but will gradually move toward system-level thermal management coordinated by chips, servers, racks, cold sources and intelligent O&M.
For data center builders, a truly valuable liquid cooling solution must not only solve equipment heat dissipation problems, but also balance system efficiency, deployment speed, operational reliability, O&M convenience and full life cycle cost.
Moving from single-point technological innovation to system-level solutions will become an important direction for liquid cooling technology to support the construction of next-generation AI data centers.

## Full text (original)

随着人工智能、大模型训练和高性能计算的快速发展，数据中心服务器正向高功率、高密度方向持续演进。传统风冷散热方式逐渐面临散热能力、空间布局和能耗效率等多方面挑战，液冷技术也由过去的辅助散热方案，逐步成为高密度算力基础设施的重要技术方向。
从冷板式液冷到浸没式液冷，再到喷淋式液冷，不同技术路线在散热原理、系统架构、建设成本和运维模式上存在明显差异。如何根据服务器功耗、机柜密度、机房条件和长期运营需求选择合适的液冷方案，成为数据中心建设与改造过程中需要重点考虑的问题。
本文将围绕服务器液冷技术的工作原理、三大主流技术路线、系统建设难点、应用场景及工程实施路径展开解析，帮助读者全面了解液冷技术及其在新一代数据中心中的应用价值。
一、为什么服务器散热开始从风冷走向液冷？
1. AI算力增长，服务器功率密度持续攀升
在传统数据中心中，CPU、内存及存储设备的功耗相对可控，单机柜功率通常在5kW～10kW左右，采用机房精密空调和服务器内置风扇即可满足大部分散热需求。
随着GPU服务器、AI加速卡和高性能计算设备的大规模部署，服务器功耗出现明显增长。
一台高性能AI服务器可能配置多颗GPU或其他AI加速芯片，整机功耗达到数千瓦。随着高密度服务器集中部署，单机柜功率密度逐步从传统的10kW级向30kW、50kW甚至80kW以上发展。
高功率设备集中运行，不仅会增加机柜内部的热负荷，还会对机房送回风组织、空调制冷能力和供电系统提出更高要求。
当单位空间内产生的热量超过风冷系统的有效散热能力时，即使持续提高风机转速、增加送风量，也难以从根本上解决局部热点和散热不均的问题。
因此，寻找更加高效的热量传递方式，成为高密度算力基础设施建设的重要课题。
2. 空气与液体的物理特性，决定了散热能力差异
液冷技术受到关注，一个重要原因在于空气与液体在热传递能力方面存在明显差异。
空气的定压比热容约为1.005kJ/(kg·K)，密度约为1.2kg/m³；水的比热容约为4.18kJ/(kg·K)，密度约为1000kg/m³。
在相同质量条件下，水的热容量约为空气的4倍。考虑到水和空气的密度差异，相同体积的水能够携带更多热量。
以一颗700W芯片为例：
如果采用风冷方式，假设空气温升为15℃，理论上需要约0.046kg/s的空气质量流量，对应约38L/s的体积流量。
如果采用水冷方式，假设冷却水温升为10℃，理论上只需要约1L/min的水流量，就能够带走相同的热量。
这意味着液体能够以更小的体积流量承载更大的热负荷，有利于提高高功率芯片的散热效率。
当然，实际系统还需要综合考虑换热面积、流道设计、流体阻力、换热温差和设备运行工况，不能仅凭介质比热容判断最终散热能力。
3. 能效与绿色发展要求推动液冷应用
数据中心能耗持续增长，能源利用效率已经成为衡量数据中心建设与运营水平的重要指标。
PUE（Power Usage Effectiveness，电能使用效率）是数据中心常用的能效评价指标，其数值越接近1，代表IT设备以外的辅助设施能耗占比越低。
传统风冷数据中心需要通过空调系统、风机和冷源设备持续带走服务器产生的热量。在高密度部署场景下，空气输送距离、风道阻力和局部热点等问题可能进一步增加制冷能耗。
液冷技术则能够将服务器产生的大部分热量直接通过液体带走，减少对大风量空气循环的依赖。在具备适宜冷却水温度和自然冷却条件的项目中，还可以结合冷却塔、干冷器等设备，提高自然冷却利用率，减少机械制冷运行时间。
因此，液冷不仅是解决高密度服务器散热问题的技术手段，也是数据中心优化能效、降低长期运营成本的重要方向。
需要注意的是，液冷并不意味着所有项目都能实现相同的PUE水平，最终能效表现仍取决于气候条件、冷源架构、设备选型、运行负载及系统控制策略。
二、服务器液冷技术有哪些？冷板、浸没与喷淋三大路线解析
液冷并不是单一的技术方案，而是由不同散热原理和系统架构组成的技术体系。
目前，服务器液冷主要包括冷板式液冷、浸没式液冷和喷淋式液冷三种技术路线。
1. 冷板式液冷：当前应用较成熟的主流路线
冷板式液冷（Cold Plate Liquid Cooling）是目前数据中心应用较广泛的液冷技术之一。
其基本原理是在CPU、GPU等高发热芯片表面安装液冷冷板，通过冷板内部设计的流道，使冷却液持续流动并吸收芯片产生的热量，再将热量传递至外部冷却系统。
整个过程形成相对完整的循环：
冷却液进入冷板 → 吸收芯片热量 → 升温后的冷却液流出 → 进入换热系统 → 降温后重新循环。
冷板式液冷的主要优势：
第一，改造适应性较强。
冷板式液冷通常只需要对CPU、GPU等主要发热器件进行液冷改造，服务器中的部分内存、电源、存储及其他元件仍可采用风冷方式。
因此，服务器整体结构与传统设备相对接近，能够在一定程度上复用原有服务器架构和机房基础设施。
第二，系统成熟度较高。
冷板、CDU、Manifold、液冷管路和快速接头等关键部件已经形成相对完整的产业链，有利于项目设计、设备采购和规模化部署。
第三，适用场景广泛。
无论是新建AI数据中心，还是对现有数据中心进行高密度改造，冷板式液冷都具有较强的应用适应性。
冷板式液冷的主要局限：
冷板通常优先覆盖CPU、GPU等主要发热器件，内存、硬盘、供电模块等其他部件仍可能需要风冷辅助，因此通常属于风液混合散热架构。
同时，冷板的换热能力受到流道结构、冷却液流量、换热面积和接触热阻等因素影响。随着芯片功耗不断提升，对冷板设计、系统流量和供液温度的要求也会持续提高。
总体来看，冷板式液冷兼顾了散热性能、设备兼容性和工程实施难度，是当前AI服务器和高密度数据中心较为成熟的选择。
2. 浸没式液冷：实现服务器整体浸没散热
浸没式液冷（Immersion Cooling）是将服务器或计算设备整体浸入绝缘介电冷却液中，使发热元件直接与冷却液接触，通过液体循环或相变过程带走设备热量。
根据冷却液是否发生相变，浸没式液冷主要分为单相浸没和两相浸没。
单相浸没式液冷
在单相浸没系统中，冷却液始终保持液态，通过泵循环或自然对流吸收服务器热量，再经换热器将热量传递至外部冷却系统。
其系统结构相对简单，运行过程不涉及冷却液沸腾和冷凝，便于建立稳定的循环控制体系。
两相浸没式液冷
两相浸没利用冷却液的相变特性进行散热。
当冷却液接触高温芯片后，吸收热量并发生沸腾汽化，产生的蒸汽上升后进入冷凝区域，释放热量并重新凝结成液体，回流至浸没槽中。
通过液体与气体之间的相变循环，实现热量传递。
两相浸没能够利用相变潜热进行高效换热，但系统对密封、冷却液管理、压力控制和材料兼容性有更高要求。
浸没式液冷的主要优势：
- 
发热器件能够直接与冷却液接触，减少传统散热界面的热阻。 
- 
有利于实现服务器整体散热，降低机箱内部风扇需求。 
- 
具备较高的热负荷承载潜力，适用于高密度计算场景。 
- 
可以降低服务器风扇运行产生的噪声。 
浸没式液冷的主要挑战：
服务器需要满足冷却液浸泡环境下的材料兼容性要求，部分传统硬盘、连接器、电源和密封材料可能无法直接适用。
同时，设备维护方式也发生明显变化。服务器部件更换通常需要经过提取、沥液、清洁和重新安装等流程，对运维工具、人员技能和现场管理提出了更高要求。
因此，浸没式液冷更适合在规划阶段就充分考虑服务器生态、冷却液管理和运维体系的新建项目。
3. 喷淋式液冷：直接向发热器件输送冷却介质
喷淋式液冷（Spray Cooling）是通过喷嘴将冷却介质直接输送至芯片或其他发热元件表面，实现热量快速传递的一种技术路线。
其核心在于利用喷嘴结构、液滴分布和流体控制，使冷却介质能够覆盖目标发热区域，并通过回收系统完成循环利用。
与冷板式液冷相比，喷淋式液冷能够减少部分固体换热界面的影响；与浸没式液冷相比，其冷却介质不需要完全充满整个服务器浸没空间。
喷淋式液冷的主要优势：
- 
冷却介质可以直接作用于发热元件。 
- 
喷淋流量和覆盖区域具有一定的调节空间。 
- 
在特定结构下，可以实现较高的局部换热能力。 
- 
冷却介质用量和系统结构可以根据应用需求进行优化。 
喷淋式液冷的主要挑战：
喷嘴的布置、喷射压力、液滴尺寸和覆盖均匀性直接影响散热效果。
如果喷嘴发生堵塞、喷射角度偏移或局部供液不足，可能造成局部热点。此外，冷却液回收、材料兼容性、密封设计和长期运行可靠性也需要充分验证。
目前，喷淋式液冷的工程应用成熟度和规模化程度仍需结合具体技术方案进行评估，更多适用于特定设备和研发验证场景。
三、服务器液冷系统如何组成？核心设备与工作流程解析
无论采用哪种液冷技术路线，一个完整的服务器液冷系统都不仅仅是冷板或冷却液，而是由热源侧、液体循环侧、换热侧和控制运维侧共同组成。
以当前应用较广泛的冷板式液冷系统为例，其核心组成主要包括以下几个部分。
1. 液冷冷板：直接吸收芯片热量
冷板是冷板式液冷系统中直接与服务器发热器件进行热交换的关键部件。
其内部通常设计有微通道、扰流结构或其他强化换热结构，通过优化流体分布和换热面积，提高芯片热量向冷却液传递的效率。
冷板的设计需要综合考虑材料导热性能、流道结构、压降、密封性能及长期可靠性。
2. CDU：液冷系统的核心控制与换热单元
CDU（Coolant Distribution Unit，冷却液分配单元）是液冷系统的重要设备，主要承担冷却液循环、流量调节、热量交换和系统监控等功能。
典型CDU通过一次侧与二次侧回路之间的换热器实现热量传递。
一次侧通常连接数据中心的冷源系统，负责提供冷却能力；二次侧则连接服务器液冷回路，为冷板或其他液冷设备提供符合要求的冷却液。
根据部署方式和系统需求，CDU可以采用机柜级、机架级或列级等不同架构。
其主要功能包括：
- 
冷却液循环与流量调节。 
- 
一次侧与二次侧热量交换。 
- 
供回液温度及压力监测。 
- 
水泵变频控制和冗余运行。 
- 
水质及运行状态监测。 
- 
故障告警和系统联动。 
CDU的配置能力、冗余设计和控制策略，直接影响液冷系统的运行稳定性。
3. Manifold：实现液冷回路的分配与汇集
Manifold通常称为分配歧管，是液冷系统中负责冷却液分配与回收的关键部件。
它将来自CDU的冷却液分配至不同服务器或冷板支路，再将吸收热量后的回液汇集至回液管路。
合理的Manifold设计能够改善不同支路之间的流量平衡，减少局部流量不足，提高系统运行稳定性。
4. 液冷管路与快速接头：保障循环连接可靠
液冷管路负责连接CDU、Manifold和服务器冷板，形成完整的冷却液循环通道。
快速接头则用于设备之间的快速连接与断开，便于服务器安装、维护和更换。
在高密度数据中心中，管路设计需要重点考虑耐压能力、密封性能、流体阻力、材料兼容性及维护便利性。
对于需要频繁插拔的应用场景，应重点关注无滴漏快接头的可靠性及其适用工况。
5. 冷源系统：将服务器热量持续排出机房
液冷系统吸收服务器热量后，还需要通过外部冷源系统将热量排放到环境中。
常见设备包括冷水机组、冷却塔、干冷器、板式换热器等。
在适宜的气候条件和供液温度要求下，可以充分利用自然冷却技术，减少压缩机运行时间。
对于风液融合数据中心，还需要综合考虑液冷系统与风冷系统的负荷分配，实现不同设备、不同区域的协同散热。
6. 智能监控平台：实现全链路运行管理
液冷系统的运行涉及温度、流量、压力、水质和设备状态等多个参数。
通过智能监控平台，可以实时采集CDU、水泵、阀门、管路和服务器的运行数据，实现设备状态监测、异常预警、故障定位和运行策略优化。
当系统出现流量异常、温度升高或漏液等情况时，监控平台可以及时发出告警，并根据预设策略联动相关设备。
由此形成从芯片散热、液体循环、冷源换热到智能运维的完整液冷管理体系。
四、液冷系统落地，必须解决哪些关键问题？
液冷技术的应用价值已经逐步得到验证，但从技术方案走向规模化部署，仍然需要解决工程设计、设备兼容、运行管理和长期维护等问题。
1. 漏液风险：系统安全设计的重点
液冷系统涉及冷却液、管路、阀门、接头和换热设备，任何连接部位发生密封失效，都可能影响服务器及周边设备的安全。
因此，液冷项目必须建立多层次的防漏液体系。
首先，应合理设计管路压力和流量，降低系统运行风险。
其次，应选择符合应用要求的高可靠性快速接头，重点关注密封寿命、插拔次数及无滴漏性能。
再次，应在机柜底部、管路连接处等重点位置设置漏液检测装置，实现异常状态实时监测。
同时，可以通过独立二次侧封闭回路、分区阀门控制和故障隔离设计，限制异常影响范围。
需要强调的是，漏液检测只是风险防控的一环，还需要结合压力监测、设备巡检、自动告警和应急操作流程，形成完整的安全保障机制。
2. 初始投资较高：需要从TCO角度评估
与传统风冷相比，液冷通常需要增加冷板、CDU、管路、快速接头和液冷监控等设备，初始建设成本可能有所提高。
不同技术路线、服务器配置和机房条件下，投资差异较大，不能简单采用固定比例判断项目成本。
因此，液冷项目不能只看设备采购价格，还需要综合考虑全生命周期总拥有成本（TCO）。
例如，某数据中心IT负载为15MW，假设风冷方案PUE为1.45，液冷方案PUE为1.15。
在IT负载保持不变的情况下：
风冷系统总功率约为21.75MW。
液冷系统总功率约为17.25MW。
两种方案的总功率差异为4.5MW。
按照全年8760小时、平均电价0.6元/kWh计算，理论年度电费差异约为2365万元。
需要注意，这是一组基于假设条件的测算，并非所有项目都能达到相同节能效果。实际收益还需要考虑负载率、设备运行效率、当地电价和冷源系统能耗等因素。
此外，液冷提升了机柜功率密度，在部分场地受限的项目中，还能够提高单位建筑面积的算力部署能力，降低单位算力对应的土建和空间成本。
3. 运维能力：从传统暖通管理走向机电协同
液冷系统不仅需要IT设备运维人员，还涉及水系统、流体控制、换热设备和自动化控制等专业知识。
传统风冷运维主要关注送回风温度、空调运行状态和机柜气流组织。
液冷运维则需要进一步掌握：
- 
水泵运行状态及扬程控制。 
- 
冷却液流量和压力平衡。 
- 
供回液温度及温差管理。 
- 
水质、电导率和pH值监测。 
- 
管路密封和材料老化检查。 
- 
漏液检测及应急隔离操作。 
因此，液冷数据中心需要建立机电、暖通、IT和自动化控制相结合的运维体系。
在项目交付阶段，应同步完成设备操作培训、系统启停培训、故障模拟和应急演练，确保运维团队能够独立处理常见异常。
4. 存量机房改造：供电、承重与空间条件需要重新核验
对于存量数据中心而言，部署液冷不仅涉及散热系统改造，还可能影响原有基础设施。
首先，需要检查机房楼板承重、设备运输通道、机柜尺寸及管路布置条件。
其次，需要重新核验供配电容量，包括变压器、母线、UPS和机柜配电系统等。
此外，还需要评估室外冷却塔、干冷器等冷源设备的安装条件，以及一次侧与二次侧管路的连接方式。
对于原有风冷机房，可以根据机柜功率密度、设备配置和基础设施条件，采用分区改造、风液融合或局部液冷等方式，避免不必要的整体改造投入。
5. 设备接口与标准兼容：避免形成供应链依赖
液冷系统涉及服务器、冷板、CDU、Manifold、快速接头和管路等多个设备环节。
如果不同厂商之间的接口规格、材料标准和性能参数不兼容，可能影响后续扩容、设备替换和维护效率。
因此，在项目建设初期，应重点明确：
- 
服务器液冷接口及连接方式。 
- 
CDU与Manifold的接口规格。 
- 
快速接头的尺寸和密封要求。 
- 
冷却液与管路材料兼容性。 
- 
系统压力、流量及温度参数。 
- 
设备故障时的替换和备件保障机制。 
优先选择接口开放、兼容性经过验证的设备和系统架构，有助于提高后续扩展的灵活性。
6. 冷却液管理：关注材料兼容与长期稳定性
不同液冷技术对冷却介质的要求不同。
冷板式液冷通常采用经过水质处理的水基冷却液，部分系统会根据材料和工况要求添加缓蚀剂等添加剂。
浸没式液冷则需要使用具有电绝缘性能的介电冷却液，常见类型包括矿物油、合成油及部分特种介电液体。
不同冷却液在黏度、导热性能、化学稳定性、材料兼容性和环保属性方面存在差异。
在选型时，应重点验证冷却液与金属材料、密封件、线缆护套和塑料部件的兼容性。
同时，还应根据冷却液类型建立相应的过滤、检测、补充和更换制度，避免因水质或介质性能变化影响系统长期运行。
五、AI数据中心为什么越来越重视液冷技术？
随着AI算力基础设施持续升级，液冷技术的应用场景正在不断扩大。
1. 高密度AI集群：推动液冷成为重要散热选择
AI服务器通常集成多颗高功率GPU或AI加速芯片，计算密度高、热流密度大。
在高密度机柜中，传统风冷可能面临局部热点、送风能力不足和制冷能耗增加等问题。
液冷能够将芯片产生的大部分热量直接带走，降低对大风量空气循环的依赖，为高功率服务器持续运行提供散热保障。
特别是在高密度AI训练集群中，冷板式液冷、风液融合和高性能CDU等技术，正在成为基础设施设计的重要组成部分。
2. 风液融合：兼顾不同设备的散热需求
并不是所有服务器部件都需要采用液冷。
在实际数据中心中，CPU、GPU等高发热芯片可以优先采用冷板液冷，而内存、电源、存储和其他辅助设备则根据实际热负荷采用风冷方式。
这种风液融合架构能够充分发挥液体散热能力，同时保留风冷系统在设备适配和辅助散热方面的优势。
在高密度AI机房中，通过液冷与风冷协同运行，可以进一步提高系统适应性，满足不同代际服务器的部署需求。
3. 余热回收：拓展液冷系统的能源利用价值
传统风冷数据中心产生的热量通常以较低温度分散排放，回收利用难度较大。
液冷系统则能够通过循环液体集中收集服务器产生的热量，在适宜的系统设计条件下，为余热利用创造条件。
例如，可以通过板式换热器和热泵系统，将数据中心回收的热量用于园区供暖、生活热水或部分工业用热场景。
但余热利用并不是液冷系统的自动附加功能，还需要考虑回水温度、热负荷稳定性、热用户距离及季节变化等因素。
通过合理设计，液冷系统可以从单纯的散热设施进一步延伸为能源综合利用系统。
4. 边缘计算：液冷应用向更多场景延伸
除了大型AI数据中心，边缘计算、工业计算和高性能专用设备同样面临散热挑战。
部分边缘节点部署在户外机房、工业厂区和偏远地区，受到空间、环境温度和供电条件限制。
液冷技术可以将设备内部热量通过循环介质集中输送至外部换热设备，降低对机房内部大规模空气循环的依赖。
随着边缘算力设备功率不断提升，液冷有望在更多高热流密度设备和特殊应用场景中发挥作用。
六、服务器液冷项目如何实施？从前期评估到工程交付
液冷项目涉及IT设备、制冷系统、供配电、管路工程和智能控制等多个专业，建议按照系统化工程流程推进。
第一步：开展机房功耗与散热能力评估
项目启动前，应对现有机房进行全面调查。
重点包括：
- 
统计各机柜实际功率及峰值功率。 
- 
分析服务器设备类型和芯片功耗。 
- 
测量机柜进出风温度及局部热点。 
- 
检查现有空调系统的制冷能力。 
- 
核验供配电容量及机房空间条件。 
通过数据分析，明确需要采用液冷的区域、设备及机柜数量，避免盲目扩大改造范围。
第二步：开展液冷方案设计与技术验证
根据服务器功耗、机柜密度和项目建设条件，确定适合的液冷技术路线。
对于存量机房，可以重点评估冷板式液冷和风液融合方案。
对于新建高密度算力中心，可以结合业务需求评估冷板式、浸没式及其他液冷技术。
在正式部署前，建议选择具有代表性的服务器和机柜开展试点测试，重点验证：
- 
满负载条件下的芯片温度。 
- 
冷却液流量及压力稳定性。 
- 
CDU换热能力及控制精度。 
- 
漏液检测及告警响应。 
- 
系统故障切换及冗余能力。 
- 
设备维护和部件更换便利性。 
试点应尽可能覆盖典型业务负载和关键故障工况，形成可靠的测试数据。
第三步：确定CDU、管路及核心设备配置
完成技术验证后，进入工程化设计阶段。
CDU选型需要重点关注换热能力、流量范围、压力控制、水泵冗余、温度调节和运行监控等指标。
设备容量应根据实际IT负载、未来扩容计划及系统冗余要求进行计算，预留合理的设计余量。
管路系统则需要明确供回液管径、压力等级、连接方式、阀门配置及排气排污设计。
同时，应优先采用经过验证的管路材料和快速接头，确保系统连接可靠、维护便利。
第四步：建设监控与安全保障体系
液冷系统需要建立完整的监控体系，将关键运行参数纳入统一管理平台。
主要监测内容包括：
- 
一次侧及二次侧供回液温度。 
- 
系统流量、压力和压差。 
- 
冷却液液位及水质状态。 
- 
水泵和阀门运行状态。 
- 
漏液检测及故障告警。 
- 
CDU及冷源设备运行状态。 
同时，制定不同故障等级对应的处理流程，明确漏液、流量异常、供液温度升高及设备故障时的应急操作要求。
第五步：系统调试、验收与运维交接
工程建设完成后，应按照设计要求开展管路冲洗、压力测试、系统排气、流量平衡、设备联动和满负载测试。
对于关键设备，还应验证备用泵切换、故障隔离和异常告警功能。
在完成系统验收后，建立设备档案、运行参数基线、维护计划和备件管理制度。
同时，对运维人员开展系统化培训，使液冷系统从建设交付阶段平稳过渡至长期运营阶段。
七、液冷系统长期稳定运行，还需要关注哪些细节？
液冷项目完成交付并不意味着管理工作的结束。长期运行过程中，以下几个方面同样值得重视。
1. 快速接头质量与维护管理
快速接头是液冷系统频繁操作的连接部件，应重点关注密封结构、材料性能、插拔寿命及无滴漏能力。定期检查接头状态，避免因长期使用导致密封性能下降。
2. 冷却液水质管理
水基冷却液需要按照系统要求监测电导率、pH值及其他水质指标，定期进行取样分析和过滤处理，避免腐蚀、结垢和微生物滋生。
3. 密封材料老化检查
管路密封圈、垫片和其他弹性密封材料可能随着温度、压力和使用时间发生老化，应根据厂家要求制定周期性检查及更换计划。
4. 应急预案与定期演练
应针对漏液、水泵故障、管路堵塞和供液温度异常等情况制定应急预案，定期开展模拟演练，提高故障处理效率。
5. 系统扩容能力预留
随着AI服务器功耗和算力规模不断增长，液冷系统需要考虑未来扩容需求。在前期设计中，应合理预留CDU容量、主管路流量、机柜连接点和冷源设备接口，减少后期改造成本。
八、结语：从单点散热到系统级热管理，液冷推动数据中心升级
从冷板式液冷到浸没式液冷，再到喷淋式液冷，不同技术路线正在为高密度服务器提供更加多样化的散热选择。
其中，冷板式液冷凭借较好的设备兼容性和工程适应性，成为当前AI数据中心的重要应用方向；浸没式液冷则在整体浸没散热和高密度计算场景中展现出应用潜力；喷淋式液冷也在特定技术领域持续探索。
未来，随着AI芯片功耗持续增长、机柜功率密度不断提升，数据中心散热将不再局限于单一设备或局部制冷，而是逐步走向芯片、服务器、机柜、冷源和智能运维协同的系统级热管理。
对于数据中心建设者而言，真正有价值的液冷方案，不仅要解决设备散热问题，更需要兼顾系统效率、部署速度、运行可靠性、运维便利性和全生命周期成本。
从单点技术创新走向系统级解决方案，将成为液冷技术支撑下一代AI数据中心建设的重要方向。