# AI rack power to hit 1.5 MW by 2030, opening overseas window for Chinese power and liquid-cooling vendors

- Source: News · Envicool (T2)
- Published: 2026-10-15
- Score: 65.0
- Tags: Market data, Datacenter, HVAC
- Companies: Delta Electronics (2308.TW), Envicool (002837.SZ), NVIDIA
- Original: https://www.seetao.com/details/280954.html

## Intelligence brief

### What happened A recent industry report, published by Seetao's high-tech channel and aggregated under Envicool (002837.SZ) coverage, describes how AI data center expansion in North America is increasingly constrained not by chip supply but by power availability and heat dissipation. The report cites a case in which a North American cloud provider's racks were fully populated with chips but could not be energized because grid interconnection queuing stretched to 24 months and large transformer lead times ran to several years, with on-site construction costs also high. Against this backdrop, the report argues that Chinese power equipment and thermal-management suppliers have an opening to expand overseas. The report cites Bank of America projections that, following NVIDIA's technology roadmap, a single AI rack will exceed 1.5 MW of power by 2030, close to 100 times that of a conventional rack, pushing traditional air cooling to its physical limits. McKinsey data is cited showing liquid cooling can cut energy consumption by more than 27%, and Bank of America expects global liquid-cooling penetration in newly built AI data centers to rise from roughly 30% today to 70% by 2030. McKinsey also forecasts global data center investment approaching USD 7 trillion by 2030. On the order side, the report says JInpan Technology's new data center orders in the first half of 2026 more than tripled year on year, while Envicool, Delta Electronics and other supply-chain players are positioning themselves across leading compute ecosystems, with thermal management and power transformation equipment described as the most certain incremental categories in this build-out. The report further highlights solid-state transformers, which it says improve power efficiency by 4% and offer smaller footprint and more flexible dispatch, as being snapped up by major cloud providers as next-generation energy gateways; UBS is cited forecasting 40% penetration in data centers by 2030, with Chinese firms expected to take core share on technology and cost advantages. It also notes stringent overseas qualification requirements: North American UL and IEEE certification, European CE and local grid-code compliance, with power equipment certification cycles typically 12 to 18 months; EU data center energy-efficiency rules require full lifecycle carbon traceability, and equipment with high-carbon inputs or without green-power manufacturing proof risks losing bids. Buyers, the report adds, prioritize local installation, rapid-response O&M and warranty capability in Europe, North America or the Middle East. For Chinese firms, the suggested path is high prefabrication and integration of transformers, switchgear, liquid-cooling CDUs and storage systems in domestic factories to trade delivery speed for premium pricing, building full carbon-footprint accounting to support pricing power, and bundling PV-storage-direct-flexible, power distribution and liquid cooling into integrated energy solutions. ### Key figures - 1.5 MW: projected power per single AI rack by 2030 under NVIDIA's roadmap, per Bank of America; close to 100x a conventional rack. - 27%+: energy consumption reduction achievable with liquid cooling, per McKinsey. - ~30% to 70%: expected rise in liquid-cooling penetration in newly built global AI data centers by 2030, per Bank of America. - USD 7 trillion: projected global data center investment by 2030, per McKinsey. - More than 3x: year-on-year growth in JInpan Technology's new data center orders in H1 2026. - 24 months to 8 years: data center grid interconnection waiting times in North America and Europe. - 6 months: compute delivery window cloud giants are compressing to. - 4%: power efficiency gain attributed to solid-state transformers. - 40%: forecast penetration of solid-state transformers in data centers by 2030, per UBS. - 12 to 18 months: typical certification cycle for power equipment (UL/IEEE in North America, CE in Europe). ### Why it matters to ebm-papst The report frames a structural shift in data center cooling: air cooling is described as reaching physical limits as rack power climbs toward 1.5 MW, while liquid cooling penetration is projected to more than double by 2030. For ebm-papst, a supplier of fans and air-movement components for data center cooling, this is a direct market signal that the addressable content per rack in pure air-movement hardware may face pressure in high-density AI halls, while demand grows for fans and blowers inside liquid-cooling infrastructure — CDU pumps and heat-exchanger airflow, dry coolers, and hybrid air-assisted liquid cooling — as well as for high-efficiency EC fans in the power conversion and transformer equipment that accompanies these builds. The report's emphasis on delivery speed, local installation and O&M presence in Europe, North America and the Middle East aligns with ebm-papst's own regional footprint and could favor suppliers able to support fast local service. Assessment (inference): The named positioning of Envicool and Delta Electronics in leading compute ecosystems suggests ebm-papst will face increasingly integrated competitors that bundle thermal management at the system level, potentially compressing the standalone fan-component value proposition unless ebm-papst attaches itself to those same platforms as a preferred air-movement supplier. Assessment (inference): The certification and carbon-footprint requirements described (UL/IEEE, CE, lifecycle carbon traceability) likely raise barriers that ebm-papst, with established Western manufacturing and compliance records, is comparatively well placed to meet — a potential competitive advantage versus Chinese entrants in European and North American tenders. Assessment (inference): The report does not quantify fan or air-movement content per rack, so the net revenue impact on ebm-papst cannot be derived from this source alone and should be treated as a directional signal pending customer-level confirmation.

## Full text (English translation)

AI data centers accelerate! Chinese power and liquid-cooling equipment go overseas.

Recently, racks at a North American cloud provider were already fully loaded with chips but could not be powered up for a long time — grid interconnection queuing of 24 months, lead times for large transformers running to several years, and high on-site construction costs. The bottleneck to compute expansion is shifting from a shortage of chips to a shortage of power and insufficient heat dissipation, which has also opened an overseas window for Chinese power and thermal-management equipment.

Single-rack power heads toward 1.5 MW

Bank of America forecasts that, following NVIDIA's technology roadmap, power consumption per single AI rack will exceed 1.5 MW by 2030, close to 100 times that of a conventional rack, and traditional air cooling has reached its physical limit; McKinsey data shows liquid-cooling technology can reduce energy consumption by more than 27%, and Bank of America expects global liquid-cooling penetration in newly built AI data centers to climb from about 30% at present to 70% by 2030. McKinsey also forecasts that global data center investment will approach USD 7 trillion by 2030. Demand has already shown up in orders: JInpan Technology's new data center orders in the first half of 2026 surged more than threefold, and supply-chain companies such as Envicool and Delta are positioning themselves comprehensively across leading compute ecosystems, with thermal management and power transformation equipment becoming the most certain incremental categories in this round of compute infrastructure.

Solid-state transformers become hot items

Aging grid equipment and insufficient capacity in North America and Europe, combined with data center interconnection waiting times of as long as 24 months or even 8 years, while cloud giants compress compute delivery to within 6 months, mean delivery cycles have become a key competitive factor in winning framework orders. Solid-state transformers can improve power efficiency by 4%, are smaller and offer more flexible dispatch, and are being snapped up by major vendors as next-generation energy gateways; UBS forecasts their penetration in data centers will reach 40% by 2030, and Chinese companies, with technology and cost advantages, are expected to occupy a core share. Keywords: Seetao, compute, AI infrastructure.

Certified carbon footprint and local O&M

Overseas cloud giants are extremely stringent in selecting suppliers: North American UL and IEEE certification, European CE and local grid-code compliance requirements are high, and power equipment certification cycles often run 12 to 18 months; the EU data center energy-efficiency directive requires full lifecycle carbon traceability, and equipment using high-carbon-footprint raw materials or lacking proof of green-power manufacturing easily loses competitiveness in tenders. Data centers have zero tolerance for power outages and cooling failures, and buyers place more value on whether suppliers have local installation, rapid-response O&M and warranty capability in Europe, North America or the Middle East. For Chinese companies, highly prefabricating and integrating transformers, distribution cabinets, liquid-cooling coolant distribution units and energy storage systems in domestic factories, trading delivery speed for premium pricing; establishing a complete carbon footprint accounting system to support pricing power with green manufacturing; and packaging PV-storage-direct-flexible, power transformation and distribution, and liquid cooling into integrated comprehensive energy solutions — these are the key steps to move from a domestic leader to a global tier-one supplier. (This article is from the Seetao official website www.seetao.com; unauthorized reproduction is prohibited; please indicate Seetao + original link when reprinting.) Seetao high-tech channel editor/Gao Xue.

Comments

Write something...

## Full text (original)

近日，北美一家云厂商的机柜已经装满芯片，却迟迟无法通电——电网接入排队24个月，大型变压器交期动辄数年，现场施工成本高企。算力扩张的瓶颈，正从缺芯片转向缺电与散热不足，这也为中国电力与散热设备打开了出海窗口。
单机柜功耗冲向1.5兆瓦
美银预测，按英伟达技术路线图，到2030年单个AI机柜功耗将突破1.5兆瓦，接近传统机柜的100倍，传统风冷散热已达物理极限；麦肯锡数据显示液冷技术可减少27%以上能源消耗，美银预计到2030年全球新建AI数据中心液冷渗透率将从目前的约30%攀升至70%。麦肯锡同时预测，到2030年全球数据中心投资额将逼近7万亿美元。需求传导到订单端已经显形：金盘科技2026年上半年数据中心新订单暴增超三倍，英维克、台达等产业链企业正全面卡位头部算力生态，温控与变电设备成为这轮算力基建中最确定的增量品类。
固态变压器成抢手货
北美与欧洲电网设备老化叠加产能不足，数据中心申请并网等待时间已长达24个月甚至8年，而云巨头把算力交付压缩到6个月内，交付周期因此成为拿下框架订单的关键竞争力。固态变压器可提升4%电能效率，体积更小、调度更灵活，被大厂当作下一代能量网关抢购，瑞银预测到2030年其在数据中心渗透率将达40%，中国企业凭技术与成本优势有望占据核心份额。关键词：高新新闻网、算力、AI基建
认证碳足迹与本地运维
海外云巨头遴选供应商极为严苛，北美UL与IEEE认证、欧洲CE及当地网联代码合规要求高，电力设备认证周期往往长达12到18个月；欧盟数据中心能效指令要求全生命周期碳轨迹穿透，使用高碳足迹原料或缺乏绿电制造证明的设备容易在招投标中失去竞争力。数据中心对断电与温控失效零容忍，买家更看重供应商在欧洲、北美或中东是否具备本地安装、快速响应运维及质保能力。对中国企业而言，把变压器、配电柜、液冷冷液分配单元与储能系统在国内工厂高度预制化集成，用交付速度换取溢价；建立完整碳足迹核算体系，以绿色制造支撑定价权；并将光储直柔、变配电与液冷打包为一体化综合能源方案，是从本土龙头迈向全球一级供应商的关键一步。（此文出自见道官网www.seetao.com未经允许不得转载否则必究，转载请注明见道网+原文链接）见道网高新栏目编辑/高雪
评论
写点什么吧~