# China's first cold-plate liquid cooling national standard GB/T 48023-2026 approved, effective February 2027, as NVIDIA Rubin mandates liquid cooling

- Source: Hiwave News (T1)
- Published: 2026-10-15
- Score: 43.0
- Tags: Datacenter, Product launch, Policy / standards
- Companies: NVIDIA
- Original: https://www.haiwu.com/news/dynamic/2165.html

## Intelligence brief

### What happened A Chinese industry analysis published by Haiwu Technology on 15 October 2026 surveys the state of liquid cooling for AI compute infrastructure in China, tracing the technology from laboratory research in the mid-2010s to what it describes as a phase of large-scale commercial deployment. The article identifies three turning points. During the technology exploration phase (mid-2010s), a very small number of companies — it names Sugon Liquid Cooling — began developing both cold-plate and immersion liquid cooling, with almost no commercial deployments. During the standards foundation phase (2021–2023), China's Ministry of Industry and Information Technology's 14th Five-Year Plan for ICT called for green digital infrastructure, and the China Academy of Information and Communications Technology (CAICT) published five liquid cooling industry standards covering cold-plate and immersion technical requirements, component specifications and test methods. During the current scale-up phase (2024 onwards), four government departments issued a data centre green and low-carbon action plan encouraging efficient cooling, the 15th Five-Year Plan elevated digital China construction to a standalone chapter, and in July 2026 China's first cold-plate liquid cooling national standard, GB/T 48023-2026, was approved, with implementation set for February 2027. The article states that NVIDIA's Rubin platform changed liquid cooling from an optional high-end configuration to a mandatory standard in 2026. It describes the liquid cooling supply chain in three tiers: upstream high-value components (coolant, cold plates, quick disconnects, CDU coolant distribution units, manifolds, piping and valves), midstream system integration and solutions, and downstream demand from intelligent computing centre operators, cloud service providers and large AI companies. It argues cold-plate liquid cooling currently dominates, with immersion positioned for next-generation ultra-high-density chips, and identifies five trends: liquid cooling becoming mandatory infrastructure, continued cold-plate dominance with immersion as the long-term future, standardisation accelerating under the national standard, expansion into energy storage, new energy vehicles and industrial robotics, and accelerating domestic substitution of core components. ### Key figures - Single AI chip power consumption: exceeds 1,000 W (as stated in the article) - Single rack power: exceeds 200 kW, described as the threshold only liquid cooling can reliably support - PUE requirement for new large and ultra-large data centres: must be reduced to within 1.25; liquid cooling can push PUE below 1.2 or even below 1.1 - GB/T 48023-2026, China's first cold-plate liquid cooling national standard: approved July 2026, effective February 2027 - Five liquid cooling industry standards published by CAICT during 2021–2023 - Market size described qualitatively as a "hundred-billion-level" computing cooling track; no precise monetary figure disclosed - No specific figures disclosed for liquid cooling market share by technology route, supplier capacity, or investment amounts. ### Why it matters to ebm-papst The article confirms that in China, liquid cooling is being treated as mandatory rather than optional infrastructure for AI compute, reinforced by NVIDIA's Rubin platform requiring liquid cooling and by GB/T 48023-2026 taking effect in February 2027. This is a direct signal that the addressable market for traditional air-cooling components in high-density AI racks is being structurally compressed in China, while demand shifts toward liquid cooling subsystems. Assessment (inference): For ebm-papst, the most immediate exposure is in air-cooling content per AI rack, which this trend reduces over time in the highest-density segments. However, the article's description of the indoor liquid cooling loop — CDUs, manifolds, secondary piping, cold plates — implies continued demand for pumps, fans for CDU heat rejection, and airflow management in hybrid racks, which are adjacent to ebm-papst's portfolio. Assessment (inference): the standardisation push described (GB/T 48023-2026) lowers customisation barriers and favours suppliers with scalable, standardised component production, which could benefit ebm-papst if it positions air-movement and drive products for CDU and hybrid cooling architectures. Assessment (inference): the article's emphasis on domestic substitution of core components in China represents a medium-term competitive risk for non-Chinese suppliers in that market, and a signal that ebm-papst should monitor Chinese CDU and cold-plate vendors as both potential competitors and potential customers for fans and blowers. Assessment (inference): the stated expansion of liquid cooling into energy storage, new energy vehicles and industrial robotics opens non-data-centre cooling demand where ebm-papst already has strong customer relationships.

## Full text (English translation)

When the parameter scale of AI large models breaks through the trillion level, the power consumption of a single AI chip breaks through 1,000 W, and a dozen high-power cards are packed into a single rack, the cooling ceiling of traditional air cooling is completely breached. Liquid cooling technology, which was previously discussed only in small industry circles, has now changed from an "optional energy-saving solution" into a rigid demand that supports the survival of the entire AI computing industry.

From being ignored in laboratories more than a decade ago to the official landing of the first liquid cooling national standard today, the liquid cooling industry has taken less than ten years to complete the full path from technological exploration to large-scale explosion. Behind this is the combined push of three forces: the explosion of AI computing power, hard policy constraints, and the maturity of the industrial chain. A hundred-billion-level computing cooling track is opening up in full.

I. AI computing liquid cooling: from the laboratory to the core of computing infrastructure

Many people's understanding of liquid cooling still stays at the shallow level of "installing water cooling for servers," but liquid cooling for AI computing is a complete set of professional heat dissipation technology systems specifically adapted to high-density computing. It uses the specific heat capacity and thermal conductivity of liquid, which are far higher than those of air, to quickly export huge amounts of heat through direct or indirect contact with chips. It is currently the only mature technical path that can stably carry computing power above 200 kW per rack.

From the perspective of system architecture, a complete liquid cooling system is divided into two major sections: outdoor and indoor. The outdoor side consists of cooling towers, primary-side pipe networks and coolant, and is responsible for discharging the heat carried out of the machine room into the atmosphere; the indoor side consists of CDU coolant distribution units, liquid cooling racks, AI servers, secondary-side pipe networks and coolant, precisely and safely carrying away the heat generated by chips. Liquid cooling is now far from being ancillary supporting equipment for data centres; it is an irreplaceable core component of AI computing infrastructure. Without a mature liquid cooling solution, ultra-large-scale intelligent computing clusters simply cannot operate stably.

Looking back at the development history of the entire industry, three key turning points pushed liquid cooling to where it is today:

- Technology exploration period (early to mid-2010s): a very small number of enterprises such as Sugon Liquid Cooling took the lead in laying out liquid cooling, simultaneously advancing research and development on both cold-plate and immersion routes, but industry awareness was extremely low, there were almost no commercial landing projects, and the vast majority of practitioners regarded liquid cooling as "an unrealistic laboratory technology."
- Standards foundation period (2021–2023): the Ministry of Industry and Information Technology's 14th Five-Year Plan for information and communications clearly proposed building green new digital infrastructure. The China Academy of Information and Communications Technology, together with the whole industry, released five liquid cooling industry standards, covering the technical requirements, component specifications and test methods of cold-plate and immersion types, completely ending the chaotic situation in which each company in the industry "fought its own battle," and for the first time the liquid cooling industry had unified rules.
- Large-scale commercial explosion period (2024 to present): four departments issued a special action plan for green and low-carbon data centres, directly encouraging the landing of efficient heat dissipation technologies such as liquid cooling; the 2026 15th Five-Year Plan made digital China construction an independent chapter, elevating the support of computing facilities to the height of a national strategy; in July of the same year, China's first cold-plate liquid cooling national standard, GB/T 48023-2026, was officially approved and will be implemented in February 2027. The liquid cooling industry has officially entered a new stage of high-quality development featuring unified standards and ecological coordination.

Now the entire industry has completely crossed the cognitive threshold of "whether to use liquid cooling" and entered the deep-water zone of "how to use liquid cooling well on a large scale." Cold-plate liquid cooling, with the advantages of flexible deployment, low operation and maintenance thresholds, and controllable retrofit costs, occupies an absolutely dominant position in the current market; immersion liquid cooling, relying on extreme heat dissipation capability, has become a forward-looking layout direction for next-generation ultra-high-power chips. In 2026, NVIDIA's Rubin platform directly changed liquid cooling from "optional high-end configuration" to "mandatory standard," which was a final word to the whole industry: the large-scale volume ramp of liquid cooling has already begun.

Policy support has also completed an upgrade from "direction guidance" to "full-chain landing": at the national level, national standards provide the backstop, ultra-large-scale intelligent computing clusters and computing-power coordination are included in new infrastructure projects, and seven departments jointly issued documents supporting liquid cooling technology innovation; at the local level, AI industry clusters such as Shenzhen and Dongguan directly list liquid cooling as a core development direction of the AI server industry chain. All pathways from top-level design to landing scenarios have been opened up, and the certainty of industry development is unprecedented.

II. Liquid cooling industry chain: an interlocking computing cooling ecosystem

The AI computing liquid cooling industry chain is a typical positive-cycle system. Technological breakthroughs in upstream core components directly determine the competitiveness of midstream solutions, and the explosion of downstream AI computing demand in turn drives upstream capacity expansion and technological iteration. The three are tightly bound and indispensable.

Upstream is the link with the highest technical barriers in the entire industry chain. High-value components such as coolant, cold plates, quick disconnects (QDC), CDU coolant distribution units, manifolds, and piping and valves directly determine the heat dissipation efficiency, leakage risk and long-term operational reliability of the entire liquid cooling system, and are the technical cornerstone of the entire industry chain. In the past, many manufacturers thought liquid cooling was just "assembling systems by piecing together components." It was only when large-scale deployment arrived that they discovered that in-house research and development capability for core components is the real core that separates delivery capability and operation and maintenance stability.

Midstream is the system integration and solution link, integrating upstream core components to form directly deliverable liquid cooling servers, liquid cooling racks and complete machine-room-level liquid cooling solutions. It is the key bridge connecting upstream component manufacturers and downstream data centre customers.

Downstream is the demand side centred on intelligent computing centre operators, cloud service providers and large AI enterprises. Their large-scale centralized procurement directly pulled liquid cooling from million-level pilot projects to a ten-billion-level large-scale commercial track.

III. Three technical routes, no absolute right or wrong, only stage-optimal

At present, there is no situation in the liquid cooling industry where one completely replaces another; different technical routes suit different computing densities and application scenarios.

Cold-plate liquid cooling is the current absolute mainstream: coolant flows inside metal cold plates and does not directly contact server chips throughout the process. The technical principle is clear, more than a decade of engineering practice has accumulated a large amount of landing experience, it is the most friendly to existing data centre retrofits, and the threshold for operation and maintenance personnel to get started is the lowest. NVIDIA's liquid cooling solution for the Rubin platform has already been continuously upgrading toward microchannel cold plates and fine flow channel design. For a considerable period in the future, cold-plate liquid cooling will firmly occupy the dominant position in the market.

Immersion liquid cooling is the ultimate direction for next-generation high-density computing: server core components are directly and completely immersed in insulating coolant, and heat is directly carried away by the liquid, achieving extreme heat exchange efficiency. Among these, single-phase immersion technology is already fully mature, and multiple domestic supercomputing centres have achieved large-scale deployment; two-phase immersion relies on boiling phase change of coolant to absorb heat, taking heat exchange capability up another level. Against the background of next-generation AI chip power continuing to rise, it is rapidly moving toward commercial landing. In scenarios in Europe and the United States with extremely high requirements for PUE and waste heat recovery, the market share of immersion liquid cooling will continue to rise rapidly.

In addition, cutting-edge directions such as chip-level precision spray liquid cooling and high-bandwidth optical module liquid cooling are also maturing rapidly. Innovative technologies such as intelligent flow control algorithms, zero-leakage connectors and microchannel flow boiling are constantly emerging, continuously pushing the heat dissipation limit of liquid cooling to a higher level.

IV. The liquid cooling explosion was never conceptual hype, but the inevitable result of multiple rigid drivers

The reason liquid cooling could move from the edge of the industry to the centre of the stage in just a few years is not a trend hyped by marketing, but an inevitable result forced out by several core driving factors.

The most direct driving force is the exponential explosion of AI computing demand. Large model training computing demand multiplies several times every year, AI chip power has broken through from several hundred watts all the way to the kilowatt level, and single-rack power has directly broken through 200 kW. The heat dissipation upper limit of traditional air cooling was long ago breached. Without liquid cooling, servers are at risk of thermal runaway and downtime at any time. This is a real survival-level rigid demand.

Second, policy and energy efficiency regulation have become hard constraints. New large and ultra-large data centres are required to reduce PUE to within 1.25, and traditional air cooling simply cannot stably meet the standard. Liquid cooling can easily press PUE below 1.2, or even below 1.1. If enterprises do not use liquid cooling, they cannot even cross the most basic compliance threshold.

In addition, the 2025 Central Economic Work Conference clearly stated "deepening and expanding AI+", the 2026 government work report directly listed ultra-large-scale intelligent computing clusters and computing-power coordination as new infrastructure projects, and the 15th Five-Year Plan wrote the supply of computing facilities into top-level design, paving a massive landing scenario for liquid cooling from the national strategic level. There is no suspense left about the explosion of the entire industry.

V. The future of the liquid cooling industry: five major trends are already clear

Standing at the 2026 node and looking back, the next development path of the liquid cooling industry is already very clear, and five certain trends are rapidly landing.

First, liquid cooling has completely changed from "optional high-end configuration" to a mandatory standard for computing infrastructure. After NVIDIA's Rubin platform mandated liquid cooling, the scale of liquid cooling centralized procurement by leading cloud vendors has doubled year after year. The core competitive point of the industry has shifted from "whether the technology can be used" to who has sufficient capacity, fast delivery speed and a complete operation and maintenance system.

Second, cold-plate will dominate the market for a long time, while immersion locks in the long-term future. In the coming years, cold-plate liquid cooling will remain the absolute mainstream. When the power of next-generation AI chips continues to break through key thresholds, the advantages of immersion liquid cooling will be fully released. Single-phase immersion will first achieve large-scale popularization, and two-phase immersion will rise rapidly in ultra-high-density computing scenarios.

Third, the landing of national standards accelerates standardisation across the industry. In the past, liquid cooling was a non-standard model of "one project, one customisation," with high costs and slow replication. Now that the national standard unifies the entire process of system design, component requirements, test verification, and deployment and operation and maintenance, liquid cooling will change from customised projects into standardised commodities. The coordination cost of the industry chain will drop significantly, and the speed of large-scale replication will far exceed everyone's expectations.

Fourth, industry boundaries continue to expand outward. Not only will new intelligent computing centres adopt liquid cooling on a large scale, but the demand for liquid cooling retrofits of existing air-cooled machine rooms will also be released in a concentrated manner. At the same time, liquid cooling technology will also extend to non-data-centre scenarios such as energy storage, new energy vehicles and industrial robots. The application boundaries of liquid cooling will continue to be opened up.

Fifth, domestic substitution of core components is accelerating across the board. Today, for core components such as coolant, cold plates, CDUs and quick disconnects, domestic manufacturers have fully entered the stage of batch delivery from the stage of sample verification. As national standards land and the industry chain continues to mature, the comprehensive competitiveness of domestic liquid cooling solutions in performance, cost and delivery capability will become stronger and stronger, and their share in the global market will also steadily increase.

In the final analysis, liquid cooling has never been a short-term trend created by hype. It is the path the industry must inevitably take after AI computing power develops to a certain stage. In the past, everyone was still discussing "when liquid cooling will arrive." Now it is already standing in front of us, becoming a key core force supporting the computing foundation of the entire digital China.

## Full text (original)

当AI大模型的参数规模突破万亿级，单张AI芯片功耗冲破1000W，单机柜塞进十几张高功率卡之后，传统风冷的散热天花板被彻底击穿。过去还在行业小圈子里讨论的液冷技术，如今已经从"可选的节能方案"变成了支撑整个AI算力产业活下去的刚性需求。
从十几年前的实验室无人问津，到现在首部液冷国家标准正式落地，液冷产业用了不到十年时间，走完了从技术探索到规模化爆发的完整路径。这背后是AI算力爆炸、政策硬约束、产业链成熟三重力量的共同推动，一个千亿级的算力散热赛道，正在全面打开。
一、AI算力液冷：从实验室走向算力基建核心
很多人对液冷的认知还停留在"给服务器装水冷"的浅层面，但面向AI算力的液冷，是一整套专门适配高密算力的专业散热技术体系。它利用液体远高于空气的比热容和导热系数，通过直接或间接接触芯片的方式，把巨量热量快速导出，是当前唯一能稳定承载单机柜200kW以上算力的成熟技术路径。
从系统架构来看，完整的液冷系统分为室外、室内两大板块：室外侧由冷却塔、一次侧管网和冷却液组成，负责把从机房带出来的热量排放到大气中；室内侧则由CDU冷量分配单元、液冷机柜、AI服务器、二次侧管网和冷却液组成，精准把芯片产生的热量安全导走。如今液冷早已不是数据中心的配套附属设备，而是AI算力基础设施里不可替代的核心组成部分，没有成熟的液冷方案，超大规模智算集群根本无法稳定运行。
回望整个行业的发展历程，三次关键转折把液冷推到了今天的位置：
- 
技术探索期（2010年代中前期）：曙光数创等极少数企业率先下场布局液冷，同步推进冷板式和浸没式两条路线的技术研发，但整个行业认知度极低，几乎没有商业化落地项目，绝大多数从业者都把液冷当成"不切实际的实验室技术"。 
- 
标准奠基期（2021-2023年）：工信部"十四五"信息通信规划明确提出建设绿色新型数字基础设施，中国信通院联合全行业发布5项液冷行业标准，覆盖冷板式、浸没式的技术要求、部件规范和测试方法，彻底结束了行业各家"各自为战"的混乱局面，液冷产业第一次有了统一的规则。 
- 
规模化商用爆发期（2024年至今）：四部门发布数据中心绿色低碳专项行动计划，直接鼓励液冷等高效散热技术落地；2026年"十五五"规划将数字中国建设独立成篇，算力设施支撑上升到国家战略高度；同年7月国内首部冷板式液冷国标GB/T 48023-2026正式获批，2027年2月开始实施，液冷产业正式迈入标准统一、生态协同的高质量发展新阶段。 
现在整个行业已经彻底跨过了"要不要用液冷"的认知门槛，进入了"如何大规模用好液冷"的深水区。冷板式液冷凭借部署灵活、运维门槛低、改造成本可控的优势，占据了当前市场的绝对主导地位；浸没式液冷靠着极致的散热能力，成为下一代超高功率芯片的前瞻性布局方向。2026年英伟达Rubin平台直接把液冷从"高配可选"改成"强制标配"，更是给全行业一锤定音：液冷的大规模放量，现在就已经开始了。
政策端的支撑也完成了从"方向引导"到"全链条落地"的升级：国家层面国标兜底，超大规模智算集群、算电协同被纳入新基建工程，七部门联合发文支持液冷技术创新；地方层面深圳、东莞等AI产业聚集区直接把液冷列为AI服务器产业链的核心发展方向，从顶层设计到落地场景的全部通路已经打通，行业发展的确定性前所未有。
二、液冷产业链：环环相扣的算力散热生态
AI算力液冷产业链是一个典型的正向循环体系，上游核心部件的技术突破直接决定中游方案的竞争力，下游AI算力的需求爆发反过来拉动上游产能扩张和技术迭代，三者紧密绑定，缺一不可。
上游是整条产业链技术壁垒最高的环节，冷却液、冷板、快速接头QDC、CDU冷量分配单元、歧管Manifold、管路阀门这些高价值部件，直接决定了整个液冷系统的散热效率、漏液风险和长期运行可靠性，是整条产业链的技术基石。过去很多厂商以为液冷就是"拼部件攒系统"，等到大规模落地才发现，核心部件的自研能力，才是真正拉开交付能力和运维稳定性差距的核心。
中游是系统集成与解决方案环节，把上游的核心部件整合起来，形成可直接交付的液冷服务器、液冷机柜和完整的机房级液冷解决方案，是连接上游零部件厂商和下游数据中心客户的关键桥梁。
下游则是以智算中心运营商、云服务商、大型AI企业为核心的需求端，他们的大规模集中采购，直接把液冷从百万级的试点项目，拉到了百亿级的规模化商用赛道。
三、三条技术路线，没有绝对对错，只有阶段最优
当前液冷行业不存在谁完全替代谁的局面，不同技术路线适配不同的算力密度和应用场景。
冷板式液冷是当前绝对的主流：冷却液在金属冷板内部流动，全程不直接接触服务器芯片，技术原理清晰，十几年的工程实践积累了大量落地经验，对现有数据中心改造最友好，运维人员上手门槛最低。英伟达Rubin平台的液冷方案，已经在向微通道冷板、精细流道设计方向持续升级，未来相当长一段时间里，冷板式液冷都会牢牢占据市场的主导地位。
浸没式液冷是下一代高密度算力的终极方向：把服务器核心部件直接完全浸入绝缘冷却液中，热量被液体直接带走，换热效率达到极致。其中单相浸没式技术已经完全成熟，国内多个超算中心已经实现大规模部署；两相浸没式依靠冷却液沸腾相变吸热，换热能力再上一个台阶，在下一代AI芯片功耗继续冲高的背景下，正在快速走向商业化落地。在欧美地区对PUE和余热回收要求极高的场景中，浸没式液冷的市场占比还会持续快速攀升。
除此之外，芯片级精准喷淋液冷、高带宽光模块液冷这些前沿方向也在快速成熟，智能流量控制算法、零泄漏连接器、微通道流动沸腾等创新技术不断涌现，正在持续把液冷的散热极限推到更高水平。
四、液冷爆发，从来不是概念炒作，是多重刚性驱动的必然结果
液冷能在短短几年内从行业边缘走到舞台中央，根本不是营销出来的风口，是几个核心驱动因素硬推出来的必然结果。
最直接的动力就是AI算力需求的指数级爆发，大模型训练算力需求每年翻好几倍，AI芯片功耗从几百瓦一路冲破千瓦级，单机柜功率直接突破200kW，传统风冷的散热上限早就被击穿，再不用液冷，服务器随时有热失控宕机的风险，这是实打实的生存级刚性需求。
其次是政策和能效监管变成了硬约束，新建大型、超大型数据中心PUE要求必须降到1.25以内，传统风冷根本无法稳定达标，液冷可以轻松把PUE压到1.2以下，甚至1.1以下，企业不用液冷，连最基本的合规门槛都跨不过去。
再加上2025年中央经济工作会议明确"深化拓展人工智能+"，2026年政府工作报告直接把超大规模智算集群、算电协同列为新基建工程，"十五五"规划把算力设施供给写进顶层设计，从国家战略层面给液冷铺好了海量落地场景，整个行业的爆发已经没有任何悬念。
五、液冷产业的未来，五大趋势已经清晰显现
站在2026年的节点回头看，液冷产业接下来的发展路径已经非常明确，五大确定性趋势正在快速落地。
第一，液冷彻底从"高配可选"变成算力基建的必选标配。英伟达Rubin平台强制液冷之后，头部云厂商的液冷集采规模连年翻倍，行业的核心竞争点已经从"技术能不能用"，转向了谁的产能充足、交付速度快、运维体系完善。
第二，冷板式长期主导市场，浸没式锁定长期未来。未来数年内冷板式液冷依然是绝对主流，等下一代AI芯片功耗继续突破关键阈值，浸没式液冷的优势会彻底释放，单相浸没先实现大规模普及，两相浸没会在超高密算力场景中快速崛起。
第三，国标落地加速全行业标准化。过去液冷都是"一项目一定制"的非标模式，成本高、复制慢，现在国标把系统设计、部件要求、测试验证、部署运维全流程统一之后，液冷会从定制项目变成标准化商品，产业链协同成本大幅下降，规模化复制的速度会远超所有人的预期。
第四，产业边界持续向外拓展。不光新建智算中心大规模采用液冷，存量风冷机房的液冷改造需求也会集中释放，同时液冷技术还会向储能、新能源车、工业机器人等非数据中心场景延伸，液冷的应用边界会不断被打开。
第五，核心部件的国产替代全面加速。如今冷却液、冷板、CDU、快速接头这些核心部件，国内厂商已经从送样验证阶段，全面进入批量交付阶段，随着国标落地和产业链持续成熟，国产液冷方案在性能、成本、交付能力上的综合竞争力会越来越强，在全球市场的份额也会稳步提升。
说到底，液冷从来不是一个炒出来的短期风口，它是AI算力发展到一定阶段之后，行业必然要走的路。过去大家还在讨论"液冷什么时候来"，现在它已经站在我们面前，成为支撑整个数字中国算力底座的关键核心力量。