### What happened Uptime Institute published an analysis on its blog (dated 14 October 2026) drawing on its 2025 and 2026 annual data center surveys to test whether the widely assumed benefit of redundant power and cooling can actually be quantified. Operators were asked whether their primary data center had suffered at least one impactful outage in the past three years, and those who had were asked to rate their most recent impactful outage from category 1 (minimal impact) to category 5 (severe impact), with categories 3-5 treated as outages carrying a meaningful financial impact. Separately, respondents identified the typical power and cooling resiliency configuration of their primary data center, using the standard definitions of N, N+1, N+2 and 2N. The 2025 and 2026 results were combined into a sample of more than 1,200 respondents and cross-tabulated to compare outage incidence against redundancy configuration. The authors, Dr. Owen Rogers (Senior Research Director for Cloud Computing) and Douglas Donnellan (Senior Research Associate), state clearly that correlation is not causation and that the analysis cannot isolate redundancy from related characteristics such as operational maturity, maintenance practices, equipment condition and overall system design. Chris Brown, CTO of Uptime Institute, was consulted for the report. ### Key figures - Combined sample size: over 1,200 respondents from the 2025 and 2026 Uptime Institute annual data center surveys. - Cooling: share of respondents reporting at least one outage in three years rose from 39% under 2N to 70% under N. - Power: the same measure rose from 42% under 2N to 68% under N. - Category 3-5 (financially impactful) outages accounted for roughly 8-11% of respondents with 2N configurations and approximately 19-22% of those using N. - Versus N, the likelihood of at least one financially impactful outage over three years was about 36% lower for N+1 cooling, 53% lower for N+2 and 63% lower for 2N. - Versus N, the corresponding power reductions were approximately 23% (N+1), 37% (N+2) and 44% (2N). - Using N+1 as the baseline instead of N: 2N cooling is 42% less likely to have an outage and N+2 is 26% less likely. - Power and cooling together account for more than two-thirds of reported impactful outages in the 2026 survey. - Uptime notes that N-configuration results rest on relatively small samples and should be interpreted cautiously. ### Why it matters to ebm-papst The report gives data center operators and their design teams a quantified, vendor-neutral argument for specifying higher-redundancy cooling architectures, which is directly relevant to ebm-papst's data center cooling portfolio (fans, fan arrays and air-movement subsystems used in CRAC/CRAH units, in-row and rear-door cooling, and liquid-cooling loops). Assessment (inference): A shift in specification preference toward N+2 and 2N cooling would raise component counts per facility, since redundancy is achieved by duplicating capacity rather than by improving single-component efficiency. For ebm-papst this is primarily a volume and content-per-site opportunity rather than a pure efficiency play, and it favours suppliers that can support multi-fan arrays with matched, individually controllable units and documented reliability data. Assessment (inference): The finding that N+1 remains the realistic baseline, with 2N cooling 42% less likely to suffer an outage, suggests the strongest near-term upgrade conversation is N+1 to N+2 rather than N to 2N. Sales and application engineering teams should be prepared to discuss incremental redundancy economics at that step, where the report indicates a 26% reduction in outage likelihood. Assessment (inference): Uptime's explicit caveat that the figures are indicative benchmarks, not facility-level predictions, means the report is unlikely to be used as a hard design mandate. It is better positioned as supporting evidence in specification discussions, and as a signal that operators are increasingly expected to justify redundancy choices with quantified downtime exposure rather than convention. Assessment (inference): The report does not name any equipment vendors, so no direct competitive threat is identified here. The main risk is indirect: if operators conclude that redundancy is the dominant lever for outage reduction, budget may shift from efficiency retrofits and fan-level upgrades toward duplicated capacity, which could change the mix of ebm-papst demand rather than its overall size.

## Full text (original)

Survey findings link higher redundancy to lower outage risk
To most data center operators, the benefit of redundant power and cooling systems is self-evident. Additional systems provide a backup in case of failure. A data center with redundant equipment should experience less downtime, on average, than the same data center operating without such resiliency measures.
This may seem like common sense — but can the benefit be calculated?
Methodology
In the 2025 and 2026 Uptime Institute annual data center surveys, operators were asked if they had experienced at least one impactful outage in their primary data center in the past 3 years (see Uptime Institute Global Data Center Survey 2026). Those operators that had were asked to rate their most recent impactful outage from category 1 (minimal impact) to category 5 (severe impact). Categories 3, 4, and 5 broadly represent outages with a meaningful financial impact.
Separately, respondents were asked to identify the typical power and cooling resiliency configuration adopted in their primary data centers:
- N. Capacity is sized to meet the expected peak load, with no additional redundant components. If a critical component fails, the system may no longer be able to support the full load.
- N+1. Capacity includes one additional component beyond what is needed to support the peak load. This allows the system to tolerate the failure or maintenance of one component without loss of service.
- N+2. Capacity includes two additional components beyond the required peak-load capacity. This provides a larger redundancy margin and can allow for one component to be offline for maintenance while another fails.
- 2N. The full required system capacity is duplicated, creating two independent paths or systems, each capable of supporting the entire load. If one system fails or is taken offline, the other can continue to support operations.
The 2025 and 2026 survey results were combined to create a large sample size of over 1,200 respondents to aid accuracy and reliability. This sample was then cross tabulated to show the number of respondents who reported at least one outage, against the cooling and power redundancy configuration of their primary data center.
Redundancy decreases outages
Figure 1 shows the number of respondents who reported at least one outage in the past 3 years, segmented by the reported cooling and power redundancy configuration.
Figure 1 Outage incidents segmented by redundancy configuration
The results show a strong and consistent relationship between infrastructure redundancy and outage incidence. For cooling, the proportion of respondents reporting an outage increased from 39% among those using 2N configurations to 70% among those using N. Power followed a similar pattern, rising from 42% for 2N to 68% for N. Respondents using N+1 and N+2 configurations were less likely to experience outages than those using N, and more likely than those with 2N architectures.
Reduced redundancy was also associated with a higher number of serious incidents. Category 3–5 outages accounted for around 8-11% of respondents with 2N configurations, and approximately 19-22% of those using N. The results suggest that greater redundancy is associated not only with fewer outages overall, but also with a substantially lower likelihood of experiencing a serious outage.
The pattern is clear across both power and cooling. However, the results for N configurations should be interpreted cautiously because they are based on relatively small samples. Nevertheless, even if those are excluded, the pattern remains when examining N+1 and N+2 configurations against 2N.
Quantifying gains
Correlation is not causation. The consistency of the association across power and cooling supports the expected value of redundancy. However, the analysis cannot isolate redundancy from other characteristics associated with resilient facilities, including operational maturity, maintenance practices, equipment condition and overall system design. The outages reported were not necessarily directly caused by power or cooling (although these together account for more than two-thirds of reported impactful outages in the 2026 Uptime Institute annual data center survey).
And yet, these figures are reasonable indicators of the probability of a data center experiencing at least one outage over 3 years, segmented by power and cooling redundancy. As a result, an indicator of the reduction in likelihood of a financially impactful outage (categories 3, 4 and 5) due to an increase in redundancy can be calculated (see Figure 2).
Figure 2 Reduction in likelihood of at least one outage due to redundancy upgrades
Redundancy does not eliminate outages, but it is associated with a material reduction in the likelihood of experiencing a serious outage. Moving from N to N+1 is associated with a meaningful improvement, while N+2 and 2N provide progressively greater reductions.
Compared with respondents using N configurations, the likelihood of reporting at least one financially impactful outage in 3 years was approximately 36% lower for N+1 cooling, 53% lower for N+2 and 63% lower for 2N. The corresponding reductions for power were approximately 23%, 37% and 44%.
Few data centers operate without any power or cooling redundancy in an N configuration. A more reasonable baseline is an N+1 configuration. In this case, 2N cooling is 42% less likely to have an outage and N+2 is 26% less likely.
These results are best used as indicative reference points rather than predictions for an individual facility. They do not establish the precise return on an upgrade, because outage risk also depends on factors such as equipment condition, maintenance, operational practices and system design. Nevertheless, they provide a rough order of magnitude for a benefit that is generally understood but rarely quantified: greater infrastructure redundancy is associated with substantially lower outage exposure.
The Uptime Intelligence View
Greater power and cooling redundancy are associated with a substantial reduction in both impactful and financially damaging outages. Although the results cannot predict the benefit for an individual facility, they provide an indicative benchmark that operators can use when weighing the cost of additional infrastructure against their exposure to downtime.