Bitzer launches Helicom CS60 screw compressor for data centre cooling, targeting 45°C supply and 800 VDC
Intelligence brief
What happened Bitzer, the German refrigeration and air conditioning compressor manufacturer, announced on 12 October 2026 that it will launch a new screw compressor developed specifically for data centre cooling. The product, the Helicom CS60, is being presented at the Chillventa exhibition in Germany, which opened the following day. According to Bitzer, the Helicom CS60 is designed to enable scalable cooling concepts and to take into account the requirements of future 800 VDC infrastructures. Rainer Große-Kracht, vice-chairman of the management board and chief technology officer, described the launch as "one of the most significant developments in our screw compressor technology," adding that the new series supports cooling systems for the latest generation of AI chips with supply temperatures of up to 45°C and enables standardised cooling platforms that can be deployed consistently around the world. The series supports a range of refrigerants including R1234ze(E), R513A and R515B. Bitzer states that wide application limits provide flexibility in system design and support cooling solutions across different locations and climate zones with minimal adaptation effort. Standard operating limits with evaporating temperatures of up to 30°C and condensing temperatures of up to 70°C also enable system concepts with heat recovery, and higher evaporating temperatures are said to be achievable thanks to the flexible compressor concept. Bitzer says advanced CFD simulations used during development of the rotor profile achieved an optimised internal geometry for high volumetric and isentropic efficiency, while a wide capacity modulation range ensures high energy efficiency across operating conditions. The compressors can run at fixed speed or with a frequency inverter; a specially developed motor variant enables speeds of up to 4,800rpm, supporting high power density and efficient full-load and part-load operation down to minimum loads of 25%. Different VI variants allow the internal volume ratio to be matched to operating conditions. The range is supported by Bitzer's IQ Module CM-SW-02 with a comprehensive sensor package, which monitors key operating parameters and supports predictable operation and early detection of critical operating conditions. An integrated oil connection allows an oil pump to be connected, ensuring oil supply independently of system pressure and supporting operation at very low pressure differentials, which Bitzer says maintains stable lubrication and oil circulation while extending application limits. Bitzer also states that dry coolers used in data centre cooling can be partially downsized or operated more efficiently than in systems relying solely on free cooling. ### Key figures - Supply temperatures supported: up to 45°C - Future infrastructure compatibility: 800 VDC - Standard evaporating temperatures: up to 30°C - Standard condensing temperatures: up to 70°C - Maximum compressor speed: up to 4,800rpm - Minimum part-load operation: down to 25% load - Displacements, CS600: 805m³/h at 50Hz, 972m³/h at 60Hz, 1,305m³/h at 160Hz - Displacements, CS605: 910m³/h at 50Hz, 1,098m³/h at 60Hz, 1,475m³/h at 160Hz - Refrigerants supported: R1234ze(E), R513A, R515B - Announcement date: 12 October 2026; venue: Chillventa, Germany - Pricing, production capacity and delivery timelines: No specific figures disclosed. ### Why it matters to ebm-papst Bitzer's entry into purpose-built data centre cooling compressors is a direct signal that the data centre thermal chain is being re-engineered around AI chip loads, high supply temperatures and future 800 VDC power architectures. For ebm-papst, this is primarily a market signal and a competitive context indicator rather than a direct product overlap: Bitzer competes in the compressor layer, while ebm-papst supplies fans, blowers and air-moving subsystems that sit in the same cooling loops, including dry coolers, air-cooled condensers, CRAC/CRAH units and liquid-cooling support equipment. Assessment (inference): The emphasis on 45°C supply temperatures and heat recovery capability points to wider adoption of high-temperature, warm-water and heat-reuse cooling architectures, which shifts demand toward fans and blowers rated for higher ambient and fluid temperatures, higher efficiency at part load, and compatibility with variable-speed control. Assessment (inference): The stated ability to partially downsize or more efficiently operate dry coolers suggests that compressor-side improvements may reduce, but not eliminate, air-moving content per installation; the net effect for ebm-papst is likely a mix shift toward higher-value, higher-efficiency fan assemblies rather than simple volume growth. Assessment (inference): Bitzer's positioning around standardised, globally deployable cooling platforms implies that OEMs and data centre operators will increasingly specify modular, region-agnostic cooling skids, favouring suppliers that can offer globally certified, consistent fan and blower platforms with digital monitoring interfaces comparable to Bitzer's IQ Module. Assessment (inference): The 800 VDC reference indicates that Bitzer is preparing for next-generation data centre power distribution; ebm-papst should verify its own roadmap for EC fans and motors compatible with higher DC bus voltages and with the monitoring/telemetry expectations of AI-era cooling systems. Assessment (inference): Chillventa serves as the competitive showcase for this segment, so ebm-papst's presence and messaging there should explicitly address AI data centre cooling, high supply temperatures and heat recovery to avoid being framed as a component supplier rather than a thermal-solution partner.
Full text
Bitzer debuts screw compressor for data centre cooling
12th October 2026GERMANY: Bitzer is to launch a new screw compressor specifically developed for data centre cooling at the Chillventa exhibition, which begins tomorrow.
The Helicom CS60 is said to enable scalable cooling concepts and also takes into account the requirements of future 800 VDC infrastructures.
“With Helicom, we are presenting one of the most significant developments in our screw compressor technology,” said Rainer Große-Kracht, vice-chairman of the management board and chief techology officer. “The new series supports cooling systems for the latest generation of AI chips with supply temperatures of up to 45°C and enables standardised cooling platforms that can be deployed consistently around the world.”
The new series support operation with a wide range of refrigerants, including R1234ze(E), R513A and R515B.
According to Bitzer, wide application limits provide flexibility in system design and support cooling solutions for different locations and climate zones with minimal adaptation effort. Standard operating limits with evaporating temperatures of up to 30°C and condensing temperatures of up to 70°C also enable system concepts with heat recovery. Higher evaporating temperatures are also said to be achieved thanks to the flexible compressor concept.
The use of advanced CFD simulations during the development of the new compressor’s rotor profile is said to have achieved an optimised internal geometry to ensure high volumetric and isentropic efficiency.
The wide capacity modulation range ensures high energy efficiency under all operating conditions.
The Helicom compressors will be able to be operated at fixed speed or with a frequency inverter. A specially developed motor variant enables speeds of up to 4,800rpm. This allows the compressors to achieve high power density and enables efficient full load and part load operation down to minimum loads of 25%.
Different VI variants enable the internal volume ratio to be matched to the respective operating conditions. This helps maintain efficiency even under varying load conditions.
The compressors are available with different displacements: 805m3/h at 50Hz, 972m3/h at 60Hz, 1,305 m3/h at 160Hz for the CS600, and 910m3/h at 50Hz, 1098m3/h at 60Hz, 1,475m3/h at 160Hz for the CS605.
The range is supported by Bitzer’s IQ Module CM-SW-02 with a comprehensive sensor package. The module monitors key operating parameters and supports predictable operation and the early detection of critical operating conditions.
The integrated oil connection provides additional benefits for operation with low system pressure differentials. It enables the connection of an oil pump, ensuring oil supply independently of system pressure and thereby supporting operation at very low pressure differentials. According to Bitzer, this helps maintain stable lubrication and oil circulation while extending the application limits. At the same time, dry coolers used in data centre cooling can be partially downsized or operated more efficiently than in systems relying solely on free cooling.