What happened On 12 October 2026, Hang Lung Environment Technology Co., Ltd. (Shenzhen-listed, stock code 000811) published its investor relations activity record form No. [2026]-059, covering an investor relations event held the same day. The event was conducted as a roadshow via Tencent Meeting. Participants from the investor side were Zhuang Tao, Wang Linsen, Chen Jing, Chen Zhenyang, Chen Qin and Wang Zhen of Panjing Investment. The company was represented by board secretary Sun Xiuxin. According to the record, discussion covered the company's business and industry segments, the application of its products in data centers including liquid-cooling systems, the barriers to entering the North American data-center liquid-cooling cold-source equipment market, and how the company is addressing capacity bottlenecks. The company describes itself as providing advanced system solutions and full-lifecycle services in the energy and power fields, with main products being compressors and heat-exchange devices integrated into units performing temperature control, pressurization and other cold/heat energy management functions across a temperature range of -271°C to 200°C. Product lines include screw compressors, centrifugal compressors, absorption chillers, piston compressors, scroll compressors, industrial heat pumps, energy storage devices, vacuum freeze-drying equipment, quick-freezing equipment, heat-exchange equipment, marine refrigeration equipment and multi-split units. On data centers, the company said its Dunham-Bush and Hang Lung Heat Exchange Technology subsidiaries supply primary-side cold source equipment and heat-exchange devices for data centers and liquid-cooling systems. Dunham-Bush is described as being in the first tier of European and American HVAC manufacturers with more than 130 years of history; it produced its first centrifugal compressor in 1965, a high-efficiency two-stage centrifugal compressor in 2010 and a magnetic-bearing compressor in 2014. Two of its products were included in the Ministry of Industry and Information Technology's catalogue of advanced applicable technology products for national green data centers. In 2024 it launched IDC-specific magnetic-bearing series products and FanWall, which passed UL/ETL certification and began volume supply. Domestic reference projects cited include the National Supercomputing Center in Guangzhou (Tianhe-2), China Mobile (Guizhou) Big Data Center, China Unicom Xi'an Data Center, Beijing Sijiqing Data Center, Bank of Communications Shanghai data processing center, Hengfeng Bank headquarters data center, China CITIC Bank Beijing data center, Hangzhou Iron & Steel Group cloud computing data center, Huaihai Big Data Industrial Park, Shenzhen Meilin Data Center, Digital Fuzhou Cloud Computing Center, Wuhan Big Data Industry Center and Zhejiang Zhijiang National Laboratory. Overseas, it works with local specialist integrators on projects in North America, Australia, Southeast Asia and the Middle East. Hang Lung Heat Exchange Technology supplies evaporative condensers, closed cooling towers, dry coolers, enthalpy-humidifying air coolers, combined dry/wet coolers, plate-fin sealed-channel heat exchangers and air-liquid hybrid heat exchangers. Its low-carbon energy-saving closed cooling technology was recognized as a recommended national energy-saving and carbon-reduction demonstration technology, and its liquid-cooling system heat exchanger was included in the 2024 Shandong Province first-set technical equipment product list. It participated in drafting the Data Center Evaporative Cooling Air Conditioning Technical Specification (T/DZJN10-2020) and the Prefabricated Data Center Technical Specification T/CIEP 0205-2026. On North American market barriers, the company cited three: UL/ETL certification, which is time-consuming and demanding; North American customers' preference for long-established local brands with extensive references in large and medium precision machinery; and high tariffs on Chinese exports to the United States. It said the core HVAC supply chain for North American data centers is concentrated and largely fixed. Primary-side data-center cooling equipment is non-standard and customized, requiring months of joint development and testing between supplier and buyer. Dunham-Bush is described as having a local North American legal entity, more than a century of development, deep product reputation and channel barriers in North America, and AHRI product performance recognition. It is also described as a global nuclear-island refrigeration machine service provider with more than 20 years of nuclear power service experience and a principal drafting unit of the National Energy Administration standard on nuclear air and gas treatment, ventilation, air conditioning and air purification, Part 18: refrigeration equipment. The company said Dunham-Bush is transferring nuclear-island-grade engineering capability to AIDC projects. On capacity, under order delivery pressure the company said it has launched a systematic expansion layout coordinating capacity across three locations: Yantai, China; Malaysia; and North America. In North America it is using leased factory space; in Malaysia it is building a new plant. ### Key figures - Investor relations record number: [2026] No. 059; event date 12 October 2026. - Investor participants: six named individuals from Panjing Investment. - Company temperature coverage range: -271°C to 200°C. - Dunham-Bush history: more than 130 years. - Dunham-Bush first centrifugal compressor: 1965; high-efficiency two-stage centrifugal compressor: 2010; magnetic-bearing compressor: 2014. - IDC-specific magnetic-bearing series and FanWall launched in 2024, passed UL/ETL certification and began volume supply. - Dunham-Bush nuclear power service experience: more than 20 years. - Standards referenced: T/DZJN10-2020 and T/CIEP 0205-2026. - Capacity expansion locations: three (Yantai, China; Malaysia; North America). - No financial figures, order values, capacity volumes or market-share percentages were disclosed. ### Why it matters to ebm-papst Dunham-Bush, a Hang Lung Environment subsidiary, is positioning itself as a primary-side cold source and heat-exchange supplier for data centers and liquid-cooling systems, with UL/ETL-certified magnetic-bearing chillers and FanWall products already in volume supply and a long list of Chinese data-center references. It also claims a local North American legal entity, a century-plus brand history and AHRI recognition, and is expanding capacity in North America and Malaysia. Assessment (inference): This is a competitive signal in the data-center cooling value chain, particularly for air-movement and heat-exchange content where ebm-papst competes. Dunham-Bush's stated advantage in North America — local entity, long references, certification — plus its three-region capacity plan suggests it intends to defend and grow share in exactly the segment where certification and local references are the main barriers. Assessment (inference): The explicit mention of UL/ETL certification and tariff costs as entry barriers implies that suppliers without North American manufacturing or certification face a widening disadvantage, which could affect ebm-papst's own data-center cooling positioning and partnership choices in that region. Assessment (inference): The reference list (China Mobile, China Unicom, hyperscale and bank data centers, national laboratories) indicates a customer base that overlaps with ebm-papst's addressable data-center accounts in China, so account-level competitive monitoring is warranted. Assessment (inference): The Malaysia new-build plant could shift regional cost and lead-time dynamics in Southeast Asia, a market where ebm-papst also operates; this should be tracked as a supply-chain signal rather than an immediate threat. No specific figures on volumes, revenue or market share were disclosed, so the scale of the competitive impact cannot be quantified from this document alone.
原文全文
原文
英文翻译
|
冰轮环境:000811冰轮环境投资者关系管理信息20261012
| | 时间:2026年10月12日 17:41:28 中财网 | |
原标题:冰轮环境 :000811冰轮环境 投资者关系管理信息20261012
证券代码:000811 证券简称:冰轮环境
冰轮环境 技术股份有限公司投资者关系活动记录表
编号:【2026】第 059号
| 投资者关
系
活动类别 | □特定对象调研 □分析师会议
□媒体采访 □业绩说明会
√
□新闻发布会 路演活动
□现场参观 □其他 | | | | | √ | | | | | | 参与单位
名称
及人员姓
名 | 盘京投资庄涛、汪林森、陈静、陈真洋、陈勤、王震 | | | 时间 | 2026年10月12日 | | | 地点 | 腾讯会议 | | | 上市公司
接
待人员姓
名 | 董事会秘书孙秀欣 | |
| 投资者关
系活动主
要内容介
绍 | 活动期间谈论的主要内容如下:
1、讨论了业务情况和产业板块
公司致力于在能源和动力领域提供先进的系统解决方案和全生
命周期服务,主要产品形式为压缩机和换热装置,集成为机组,实施
温控、增压等冷热能管理功能,覆盖-271℃-200℃温度区间。具体有
螺杆式压缩机、离心式压缩机、吸收式制冷机、活塞式压缩机、涡旋
式压缩机、工业热泵、储能蓄能装置、真空冻干设备、速冻装置、换
热设备、船用制冷设备、多联机等。
从客户行业维度看公司产品广泛应用于食品/农副产品冷冻冷藏
及深加工、冷链物流基地建设、食品/药品真空冻干、冰雪运动场馆、
加工预处理产线等商业制冷系统;能源/化工生产工艺冷却、航天风
洞/超导科研等人工特殊环境、建筑骨料冷却、隧道矿井探凿冻结等
工业冷冻系统;轨道交通、商业地产、公共场馆、科研文教等商用舒
适空调;数据中心、核电站、冶金石化、洁净空间、电子厂房、制药、
矿井热害、节能改造等工业特种空调;以及余热余能利用、气体压缩
及液化、储能系统、新能源装备、洁净排放;黑色金属铸造、有色金
属铸造、铸件精密加工、3D智能成型;工业智控、智能产线、智慧
物流等。
2、讨论了公司产品在数据中心包括液冷系统的应用
公司旗下顿汉布什公司和冰轮换热技术公司为数据中心乃至液
冷系统提供一次侧冷源装备和热交换装置等冷却装备。
顿汉布什公司(DUNHAM-BUSH)跻身欧美系暖通空调一线梯队,
已有130+年历史。顿汉布什1965年出产第一台离心式压缩机,2010年
出产高效双级离心式压缩机,2014年出产磁悬浮压缩机。以核级水准
进军数据中心冷却市场,“变频离心式冷水机组”“集成自然冷却功能
的风冷螺杆冷水机组”两项产品入选工信部《国家绿色数据中心先进
适用技术产品目录》,其中,“变频离心式冷水机组”包含“高压变频
离心式冷水机组”和“磁悬浮变频离心式冷水机组”。2024年推出上
市的适应当地工况的IDC专版磁悬浮系列产品和FanWall风墙顺利通
过UL/ETL认证并开始大批量供货。国内已成功服务了国家超级计算广
州中心(天河二号)、中国移动(贵州)大数据中心、中国联通西安
数据中心、北京四季青数据中心、上海交通银行数据处理中心、恒丰
银行总部数据中心、北京中信银行数据中心、杭钢集团云计算数据中
心、淮海大数据产业园、深圳梅林数据中心、数字福州云计算中心、
武汉大数据产业中心、浙江之江国家实验室等诸多项目。在海外,与
多家本土专业集成商合作,服务了北美、澳洲、东南亚、中东众多项
目。
冰轮换热技术公司提供蒸发式冷凝器、闭式冷却塔、干冷器、等
焓加湿空冷器、干湿联合式冷却器、板翅式密封通道热交换器、风液 | | | 混冷换热器等,其中,“低碳节能闭式冷却技术”获评国家节能降碳
示范技术推荐,“液冷系统热交换器”入选《2024年度山东省首台(套)
技术装备产品生产企业及名单》,参与起草《数据中心蒸发冷却空调
技术规范》(T/DZJN10-2020)、《预制化数据中心技术规范》T/CIEP
0205—2026。
3、北美数据中心液冷冷源装备市场的门槛是什么?
切入北美数据中心市场的现实条件较为苛刻,进入壁垒主要来自
三个层面:一是UL/ETL认证,该等认证耗费时间长且对产品要求很
高;二是北美客户在大中型精密机械方面偏好本土历史悠久且有丰富
案例的知名品牌;三是中国产品出口至美国需承担高额关税。北美数
据中心暖通空调供应链核心格局集中且基本固化。
数据中心冷却一次侧设备配置要兼顾数据中心内部产生的热能和
外部气候环境,属于非标订制化产品,前期需要供需双方长达数月的
深度协同研发、测试,供方的灵活技术适配能力和系统解决方案水平
很重要。
顿汉布什具备北美本土法律主体身份,发展逾百年,在北美地区
形成深厚的产品口碑和渠道壁垒,荣获美国空调、供暖与制冷学会
(AHRI)产品性能表彰。
顿汉布什是全球核岛制冷机服务商,拥有20余年核电服务经验,
是国家能源局《核空气和气体处理规范通风、空调与空气净化第18
部分制冷设备》标准的主要起草单位。核电站对制冷系统的要求是
什么?抗震、失电后快速重启、极端工况下持续运行、零故障容忍。
这些标准远高于普通商业建筑或工业场景。顿汉布什是将“核岛级”
的工程能力迁移到AIDC项目。
4、公司如何应对产能瓶颈问题?
在订单交付重压下,公司已启动"中国烟台+马来西亚+北美"三地
产能协同的系统性扩产布局。在北美采用租赁厂房租赁模式,在马来
西亚采取新建工厂模式。 | | 附件清单