# Huawei, Alibaba Cloud, Tencent Cloud, ByteDance scale liquid cooling; Envicool supplies all four

- Source: News · Shenling (T2)
- Published: 2026-09-28
- Score: 66.8
- Tags: Datacenter, Order win, HVAC
- Companies: Vertiv, Envicool (002837.SZ), Shenling (301018.SZ), Hiwave, Emicon (300249.SZ), Alibaba Cloud, tencent_cloud, ByteDance
- Original: http://www.chinaiol.com/News/Content/202609/21_68806.html

## Intelligence brief

### What happened A Chinese industry round-up published on 28 September 2026 dissects the liquid-cooling architectures of the four largest domestic computing-infrastructure players — Huawei, Alibaba Cloud, Tencent Cloud and ByteDance — stating that all four have moved liquid cooling into scaled deployment. The article covers data-centre liquid cooling only and explicitly excludes energy-storage cooling. The common route across all four is cold-plate liquid cooling as the volume workhorse, with immersion reserved for ultra-high-density pilots. Differentiation lies in each vendor's self-developed control unit and its qualified supplier list. Huawei Digital Power runs both cold-plate and phase-change immersion lines. Its differentiator is a self-developed TMU liquid-cooling management unit that replaces the traditional CDU role, performing real-time monitoring of water quality, pressure and leakage plus fault isolation to remove the CDU single point of failure. Cold-plate systems are deployed at Huawei Cloud intelligent-computing nodes in Gui'an, Ulanqab and Wuhu; phase-change immersion targets hundred-kilowatt-class clusters for Pangu model training. Alibaba Cloud's Pangu server liquid-cooling system is cold-plate-led with phase-change immersion as a flagship pilot. Alibaba Cloud began immersion R&D in 2015, making it the earliest domestic cloud vendor to deploy immersion, with representative projects in Zhangbei and Ulanqab. Its self-developed CMC cold-plate unit is integrated behind the rack, giving per-cabinet independent temperature control, a closed ethylene-glycol loop and full-link leak protection. Tencent Cloud's distinctive point is "air-liquid same-source" elastic temperature control, jointly developed with Shenling, which switches the cooling source intelligently between dry-cooler and wet-cooler modes. Immersion is limited to pilots such as the Yangtze River Delta AI supercomputing project supporting the Hunyuan model cluster. ByteDance's Volcano Engine unveiled AI Rack 3.0 at the OCP China Summit in July: a dual-cabinet configuration, 500 kW per cabinet and 1 MW for the pair, housing up to 576 XPUs, with 800 V HVDC power and 100% rack-level liquid cooling as standard. Deployments are at Datong and Huailai. ### Key figures - Huawei cold-plate cooling: heat-dissipation power consumption down 96% versus conventional air cooling; PUE as low as 1.1; adapts to 50 kW-class AI cabinets. - Huawei phase-change immersion: targets hundred-kilowatt-class clusters. - Alibaba Cloud immersion: R&D started 2015; PUE as low as 1.04; CMC cold-plate supports over 100 kW per cabinet. - Tencent Cloud: annual average PUE ≤ 1.15. - ByteDance AI Rack 3.0: 500 kW per cabinet, 1 MW dual-cabinet, up to 576 XPUs, 800 V HVDC, 54 V liquid-cooled busbar, supports XPUs above 3000 W; single-phase immersion PUE below 1.1. - Supplier overlap: Envicool appears in all four vendor lists; Shenling is tied to Huawei, Tencent Cloud and ByteDance; Shuguang Shuchuang covers immersion pilots; Juhua supplies coolant. - The article notes supplier lists are compiled from public tender wins and ecosystem cooperation, and that procurement shares vary by vendor and should defer to official disclosure. ### Why it matters to ebm-papst The article confirms that China's four largest computing-infrastructure buyers have standardised on cold-plate liquid cooling for volume AI capacity, with immersion confined to pilots. That shifts the addressable cooling content per rack toward liquid loops, CDUs and management units, and away from pure air-side thermal hardware. Assessment (inference): ebm-papst's exposure here is indirect but real. As cold-plate systems scale, the residual air-side load — fan walls, rear-door heat exchangers, hybrid air-liquid cabinets and the dry-cooler/wet-cooler heat-rejection side that Tencent Cloud's elastic source depends on — remains a fan and blower opportunity, and hybrid air-liquid designs are explicitly named for Huawei's 50 kW-class cabinets. Assessment (inference): the named supplier lists are dominated by Chinese thermal specialists (Envicool, Shenling, Shuguang Shuchuang, Hiwave, Emicon, Vertiv, Gaolan, Juhua), none of which is ebm-papst, so the direct liquid-loop content is largely closed to us on these accounts. Assessment (inference): the more actionable signal is the heat-rejection and air-movement layer plus any European or global deployments of these same customers, where ebm-papst's fan and control portfolio can still be specified. Assessment (inference): the article provides no procurement volumes or shares, so no sizing of the opportunity is possible from this source alone.

## Full text (English translation)

Huawei TMU, Alibaba CMC, ByteDance AI Rack 3.0: A Full Teardown of the Four Giants' Liquid Cooling Solutions

Huawei, Alibaba Cloud, Tencent Cloud and ByteDance — the four biggest players in China's computing infrastructure — have all brought liquid cooling solutions into scaled deployment. On route selection they share one common answer: cold-plate liquid cooling as the main force, immersion for ultra-high-density pilots. But the control units each has developed in-house and the supplier lists each has tied up differ greatly. This article breaks them down vendor by vendor, with a horizontal comparison at the end. Only data-centre liquid cooling is discussed; energy-storage liquid cooling is out of scope.

1. Huawei: cold-plate first, self-developed TMU replacing traditional CDU

Liquid cooling solution: Huawei Digital Power's liquid cooling system contains two routes, cold-plate liquid cooling and phase-change immersion. The core difference is the self-developed TMU liquid cooling management unit — it replaces the role of the traditional CDU, performing real-time monitoring of water quality, pressure and leakage across the whole link plus fault isolation, solving the old problem of CDU single points of failure.

Cold-plate liquid cooling (main scaled solution): hybrid air-liquid, suited to 50 kW-class AI cabinets, already deployed at Huawei Cloud intelligent computing nodes in Gui'an, Ulanqab and Wuhu. Official data: heat-dissipation power consumption down 96% versus traditional air cooling, PUE as low as 1.1.

Phase-change immersion (ultra-high-density pilot): for hundred-kilowatt-class clusters, serving Pangu large model training.

Liquid cooling & temperature control suppliers:
- CDU/TMU supporting equipment, cooling source units: Shenling, Envicool
- Cold plates and heat dissipation modules: Envicool
- Coolant, piping, pump units: Gaolan, Juhua

2. Alibaba Cloud: self-developed CMC, earliest domestic start in immersion

Liquid cooling solution: Alibaba Cloud's Pangu server liquid cooling system, cold-plate-led with phase-change immersion as a benchmark pilot. Immersion R&D began in 2015, making it the earliest domestic cloud vendor to deploy immersion, with representative projects in Zhangbei and Ulanqab.

Self-developed CMC cold-plate liquid cooling (main scaled solution): the CMC cooling distribution unit is integrated at the rear of the cabinet, with independent temperature control per cabinet, a closed ethylene-glycol loop plus full-link leak protection, and a single cabinet able to support over a hundred kilowatts.

Phase-change immersion: the whole machine is immersed in fluorinated liquid, with no pump-forced circulation and natural heat exchange via phase change, PUE as low as 1.04.

Liquid cooling & temperature control suppliers:
- Cold-plate liquid cooling system, CDU: Envicool (core supplier)
- Immersion turnkey solution: Shuguang Shuchuang
- Cooling towers and heat exchange equipment: Gaolan
- Coolant: Juhua
- Precision air conditioning and room temperature control: Vertiv, Emicon

3. Tencent Cloud: air-liquid same-source, focused on elastic cooling sources

Liquid cooling solution: Tencent uses cold-plate as its main scaled solution, with the original point being "air-liquid same-source" elastic temperature control — the cooling source can switch intelligently between dry-cooler and wet-cooler modes. This technology was jointly developed by Tencent and Shenling, has already run stably over the long term, and delivers annual average PUE ≤ 1.15. Immersion is only piloted in projects such as the Yangtze River Delta AI supercomputing centre, supporting the Hunyuan large model cluster.

Liquid cooling & temperature control suppliers:
- Cold-plate CDU liquid cooling system: Envicool
- Air-liquid same-source temperature control units: Shenling (jointly developed)
- Liquid cooling secondary side and precision temperature control: Hiwave
- Immersion pilot solution: Shuguang Shuchuang

4. ByteDance: AI Rack 3.0, writing liquid cooling into the rack architecture

Liquid cooling solution: ByteDance's Volcano Engine showed AI Rack 3.0 at the July OCP China Summit — dual-cabinet combination, 500 kW per cabinet, 1 MW for the two cabinets, housing up to 576 XPUs, with 800 V HVDC power supply and 100% rack-level liquid cooling as standard across the line. The cabinet has a built-in 54 V liquid-cooled busbar and manifold, suited to multi-chip XPUs above 3000 W. Deployed at bases including Datong and Huailai.

Cold-plate (main force): chips directly connected to cold plates, CDUs centrally distributed outside the cabinet, quick blind-mate connectors reducing deployment and leak-maintenance difficulty.

Single-phase immersion (continuously expanding): the whole machine immersed in insulating fluorinated liquid, natural convection heat exchange, PUE pressed below 1.1, with the Datong base expanding.

Liquid cooling & temperature control suppliers:
- Cold-plate liquid cooling system, CDU: Envicool, Shenling
- Immersion modules and complete solutions: Gaolan, Shuguang Shuchuang
- Room precision temperature control: Emicon
- Coolant: Juhua

Supply chain overlap is more worth pondering: Envicool appears in all four lists at once, Shenling is tied to Huawei, Tencent and ByteDance, Shuguang Shuchuang takes the immersion pilots, and Juhua covers coolant across the board. The harder the giants fight, the steadier the water sellers — of course, share data differs by vendor's own accounting, and the supplier lists above are compiled from public tender wins and ecosystem cooperation information; specific procurement shares are subject to official disclosure.

## Full text (original)

华为、阿里云、腾讯云、字节跳动，国内算力基建的四个头号玩家，液冷方案都已经规模化落地。路线选择上有一个共同答案——冷板式液冷为主力、浸没式做超高密试点，但各家自研的管控单元和绑定的供应商名单，差别很大。本文按厂商逐一拆解，文末给横向对比。只讨论数据中心液冷，储能液冷不在这篇范围。
一、华为：冷板为主，自研 TMU 替代传统 CDU
液冷方案：华为数字能源的液冷体系包含冷板式液冷与相变浸没式两条路线，核心差异点在于自研 TMU 液冷管控单元——它替代了传统 CDU 的角色，做全链路水质、压力、漏液的实时监测和故障隔离，解决 CDU 单点故障的老问题。
冷板式液冷（主力规模化方案）：风液混合，适配 50kW 级 AI 机柜，已部署在贵安、乌兰察布、芜湖等华为云智算节点。官方数据：散热功耗较传统风冷下降 96%，PUE 最低 1.1。
相变浸没式（超高密试点）：面向百千瓦级集群，服务盘古大模型训练。
液冷 & 温控供应商：
- CDU/TMU 配套、冷源机组：申菱环境、英维克 
- 冷板及散热模组：英维克 
- 冷却液、管路、泵组：高澜股份、巨化股份 
二、阿里云：自研 CMC，浸没式国内起步最早
液冷方案：阿里云磐久服务器液冷体系，冷板为主、相变浸没为标杆试点。2015 年就启动浸没式研发，是国内最早落地浸没式的云厂商，代表项目在张北、乌兰察布。
自研 CMC 冷板式液冷（规模化主力）：机柜后侧集成 CMC 冷却分配单元，单柜独立控温，闭式乙二醇循环 + 全链路漏液保护，单机柜可支撑上百千瓦。
相变浸没式：整机浸入氟化液，无泵强制循环、靠相变自然换热，PUE 可低至 1.04。
液冷 & 温控供应商：
- 冷板液冷系统、CDU：英维克（核心供应商） 
- 浸没式整体方案：曙光数创 
- 冷却塔与换热设备：高澜股份 
- 冷却液：巨化股份 
- 精密空调与机房温控：维谛技术、依米康 
三、腾讯云：风液同源，主打弹性冷源
液冷方案：腾讯以冷板式为规模化主力，独创点在"风液同源"弹性温控——冷源可在干冷/湿冷模式间智能切换，这项技术由腾讯与申菱环境联合研发，已经长期稳定运行，年均 PUE≤1.15。浸没式仅在长三角 AI 超算等项目试点，支撑混元大模型集群。
液冷 & 温控供应商：
- 冷板式 CDU 液冷系统：英维克 
- 风液同源温控机组：申菱环境（联合研发） 
- 液冷二次侧与精密温控：海悟科技 
- 浸没式试点方案：曙光数创 
四、字节跳动：AI Rack 3.0，把液冷写进整机柜架构
液冷方案：字节火山引擎在 7 月 OCP 中国峰会亮出 AI Rack 3.0——双柜组合、单柜 500kW、双柜 1MW，最高装 576 颗 XPU，全系标配 800V HVDC 供电 + 100% 整机柜全液冷。机柜内置 54V 液冷 Busbar 和分集水歧管，适配 3000W 以上多 Chip XPU。部署在大同、怀来等基地。
冷板式（主力）：芯片直连冷板，CDU 柜外集中分配，快速盲插接头降低部署和漏液维护难度。
单相浸没式（持续扩容）：整机浸入绝缘氟化液，自然对流换热，PUE 压到 1.1 以内，大同基地在扩。
液冷 & 温控供应商：
冷板液冷系统、CDU：英维克、申菱环境
浸没式模组与成套方案：高澜股份、曙光数创
机房精密温控：依米康
冷却液：巨化股份
供应链重叠度更值得琢磨：英维克同时出现在四家的名单里，申菱环境绑定华为、腾讯、字节三家，曙光数创吃浸没式试点，巨化股份通吃冷却液。巨头打得越凶，卖水的越稳——当然，份额数据各家口径不一，以上供应商名单按公开中标与生态合作信息整理，具体采购份额以官方披露为准。